Introduction
The log-mean temperature difference method answers the sizing question for any two-fluid heat exchanger: given the four terminal temperatures, how much heat is exchanged and how much surface is needed for a given overall heat transfer coefficient. This calculator computes the LMTD for counterflow and parallel flow, the Bowman correction factor F for a one-shell-pass shell-and-tube unit with an even number of tube passes, the duty from either stream's mass flow and specific heat (or taken directly), the service U after fouling, and the required area. It also reports effectiveness, NTU and capacity ratio, which follow from the temperatures alone and link to the ε-NTU method.
Marine engineers use it for lube-oil and jacket-water coolers, fuel heaters and central coolers; process and HVAC engineers for any shell-and-tube or plate exchanger pre-sizing; students for the standard heat transfer course problems.
Formulas
Heat duty (energy balance on either stream):
Q = ṁ_h c_p,h (T_h,in − T_h,out) = ṁ_c c_p,c (T_c,out − T_c,in)
- ṁ — mass flow, kg/s; c_p — specific heat, J/(kg·K); T — terminal temperatures, °C
Log-mean temperature difference:
LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂) (LMTD = ΔT₁ when ΔT₁ = ΔT₂)
Counterflow: ΔT₁ = T_h,in − T_c,out, ΔT₂ = T_h,out − T_c,in
Parallel: ΔT₁ = T_h,in − T_c,in, ΔT₂ = T_h,out − T_c,out
Correction factor for one shell pass, 2/4/6… tube passes (Bowman, Mueller and Nagle 1940), applied to the counterflow LMTD:
R = (T_h,in − T_h,out) / (T_c,out − T_c,in), P = (T_c,out − T_c,in) / (T_h,in − T_c,in)
F = √(R²+1) ln[(1−P)/(1−RP)] / { (R−1) ln[ (2 − P(R+1−√(R²+1))) / (2 − P(R+1+√(R²+1))) ] }
R = 1: F = P√2 / { (1−P) ln[ (2 − P(2−√2)) / (2 − P(2+√2)) ] }
Area and fouling:
1/U_service = 1/U_clean + R_f
A = Q / (U_service × F × LMTD)
- U — overall heat transfer coefficient, W/(m²·K); R_f — total fouling resistance, m²·K/W
Effectiveness, NTU and capacity ratio (from the temperatures alone):
ε = max(ΔT_h, ΔT_c) / (T_h,in − T_c,in)
NTU = U A / C_min = max(ΔT_h, ΔT_c) / (F × LMTD)
C_r = min(ΔT_h, ΔT_c) / max(ΔT_h, ΔT_c)
Assumptions and limitations
- Steady state, no heat loss to the surroundings, constant specific heats and constant U along the exchanger. For large temperature ranges or condensing/boiling, split the exchanger into zones.
- The LMTD method needs all four temperatures. When only inlets are known (rating an existing exchanger), use the ε-NTU method; the ε, NTU and C_r outputs here are the bridge.
- The F factor is the Bowman analytical result for one shell pass with any even number of tube passes. Two or more shell passes in series, cross-flow and plate exchangers have different F curves; for plate exchangers F is close to 1 in pure counterflow arrangement.
- F below about 0.75 means the design sits on the steep part of the curve and small temperature changes cause large area changes; add shell passes or use counterflow.
- Fouling resistances are the TEMA design values; actual fouling depends on velocity, temperature and cleaning schedule. Fouling on each side should be referred to the same area basis as U.
- U values in the help text are order-of-magnitude ranges for pre-sizing; a real design computes U from the film coefficients, wall resistance and fin efficiency.
Worked example
Incropera, Example 11.1. A counterflow concentric-tube cooler takes lubricating oil from 100 °C to 60 °C at 0.1 kg/s (c_p = 2 131 J/(kg·K)); cooling water at 0.2 kg/s enters at 30 °C. U = 38.1 W/(m²·K) based on the 25 mm inner tube.
- Duty: 0.1 × 2 131 × (100 − 60) = 8 524 W.
- Water outlet: 30 + 8 524 / (0.2 × 4 178) = 40.2 °C.
- Terminal differences, counterflow: ΔT₁ = 100 − 40.2 = 59.8 K, ΔT₂ = 60 − 30 = 30 K.
- LMTD: (59.8 − 30) / ln(59.8/30) = 43.2 K.
- Area: 8 524 / (38.1 × 43.2) = 5.18 m²; as a 25 mm tube that is 5.18 / (π × 0.025) = 65.9 m, Incropera's answer.
- Effectiveness: oil has the smaller capacity rate; ε = 40 / 70 = 0.571; NTU = 40 / 43.2 = 0.93; C_r = 10.2 / 40 = 0.255.
In parallel flow the same temperatures give LMTD = 39.75 K and about 9 % more area. In a 1-2 shell-and-tube with the water heated to 60 °C instead (R = 1, P = 0.5), F = 0.80 and the effective difference drops from 40 K to 32 K.
FAQ
Counterflow or parallel flow — which needs less area?
Counterflow, always, for the same four temperatures. It is also the only simple arrangement that can heat the cold fluid above the hot outlet temperature (a temperature cross).
When do I need the F correction?
Whenever the flow is not purely counter or parallel: multi-pass shell-and-tube, cross-flow, and most compact exchangers. F multiplies the counterflow LMTD and is always ≤ 1.
My F comes out undefined or the calculator says the cross is not achievable.
A single shell pass cannot deliver that combination of temperatures no matter how large the area. Use two shell passes in series (or a counterflow plate exchanger), or relax the cold outlet temperature.
What U value should I use?
Pre-sizing ranges: water-to-water 800–1 500, oil-to-water 100–350, gas-to-liquid 20–60, condensing steam to water 1 500–4 000 W/(m²·K). Plate exchangers reach 3 000–7 000 for water-to-water. Confirm with the vendor's thermal design.
How do fouling factors change the result?
They add a resistance in series with 1/U. With U = 1 000 and R_f = 0.0005 m²·K/W, the service U is 667 and the area 50 % larger. TEMA per-side values: treated cooling water 0.00018, sea water 0.00009, fuel oil 0.0009, lube oil 0.00018 m²·K/W.
Why does the calculator compute effectiveness when I gave four temperatures?
Because the same four temperatures define ε, NTU and C_r, and seeing them tells you how hard the exchanger is working: ε above 0.8 or NTU above 3 means diminishing returns on extra area.
Can I use this for a plate heat exchanger?
Yes, in counterflow with F = 1 for single-pass arrangements. Use the manufacturer's U, which is much higher than for shell-and-tube.