AWG wire gauge chart and converter

Diameter, mm², circular mils, resistance and weight of every AWG size from 4/0 to 40, or the gauge of a measured wire, with the matching metric size.

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem

Introduction

American Wire Gauge (AWG) is the wire size system used in North America. The numbers run backwards: the higher the gauge, the thinner the wire. 12 AWG, the usual size for a 20 A household circuit, is 2.05 mm across and has a cross-section of 3.31 mm². Every six gauges halve the diameter, and every three gauges halve the area.

This calculator gives the diameter, area in mm² and circular mils, resistance and weight of any gauge from 4/0 to 40, in copper or aluminium, solid or stranded, at any temperature. It also works backwards from a measured diameter or a metric cross-section to the gauge, and shows the metric IEC size to use instead. The full chart is in the next section.

Formulas and AWG chart

ASTM B258 defines every gauge from two fixed points, 0000 at 0.4600 in and 36 at 0.0050 in, with 39 steps of equal ratio between them:

d = 0.005 in × 92^((36 − n) / 39)
A = π × d² / 4
area in circular mils = (d in mils)²

Resistance and weight per unit length:

R' = ρ20 × (1 + α (T − 20)) / A × k_s
m' = ρ_m × A × k_s
  • n — gauge number; 0 (1/0) is 0, 00 (2/0) is −1, 000 (3/0) is −2 and 0000 (4/0) is −3
  • ρ20 — resistivity at 20 °C: copper 1.7241 × 10⁻⁸ Ω·m, aluminium 2.8264 × 10⁻⁸ Ω·m
  • α — temperature coefficient: copper 0.00393 /K, aluminium 0.00403 /K
  • k_s — 1.02 for concentric stranded conductors (ASTM B8), 1 for solid wire
  • ρ_m — mass density: copper 8 890 kg/m³, aluminium 2 705 kg/m³

AWG chart

Solid copper at 20 °C, from the formulas above. For stranded wire add 2 % to the resistance; for aluminium multiply the copper resistance by 1.64. The last column is the smallest IEC metric size with at least the same area.

AWGDiameter (in)Diameter (mm)Area (mm²)Area (kcmil)Copper Ω/kmCopper Ω/1000 ftNext IEC size
4/00.460011.684107.2211.60.1610.0490120 mm²
3/00.409610.40585.03167.80.2030.061895 mm²
2/00.36489.26667.43133.10.2560.077970 mm²
1/00.32498.25153.48105.50.3220.098370 mm²
10.28937.34842.4183.690.4070.12450 mm²
20.25766.54433.6366.370.5130.15635 mm²
30.22945.82726.6752.630.6460.19735 mm²
40.20435.18921.1541.740.8150.24825 mm²
50.18194.62116.7733.101.0280.31325 mm²
60.16204.11513.3026.251.2960.39516 mm²
70.14433.66510.5520.821.6340.49816 mm²
80.12853.2648.36616.512.0610.62810 mm²
90.11442.9066.63413.092.5990.79210 mm²
100.10192.5885.26110.383.2770.9996 mm²
110.09072.3054.1728.2344.1321.2606 mm²
120.08082.0533.3096.5305.2111.5884 mm²
130.07201.8282.6245.1786.5712.0034 mm²
140.06411.6282.0814.1078.2852.5252.5 mm²
150.05711.4501.6503.25710.453.1842.5 mm²
160.05081.2911.3092.58313.174.0151.5 mm²
170.04531.1501.0382.04816.615.0631.5 mm²
180.04031.0240.8231.62420.956.3851 mm²
190.03590.9120.6531.28826.418.0510.75 mm²
200.03200.8120.5181.02233.3110.150.75 mm²
210.02850.7230.4100.81042.0012.80—
220.02530.6440.3260.64252.9616.14—
230.02260.5730.2580.50966.7820.36—
240.02010.5110.2050.40484.2125.67—
250.01790.4550.1620.320106.232.37—
260.01590.4050.1290.254133.940.81—
270.01420.3610.1020.202168.951.47—
280.01260.3210.08100.160212.964.90—
290.01130.2860.06420.127268.581.83—
300.01000.2550.05090.101338.5103.2—
310.00890.2270.04040.0797426.9130.1—
320.00800.2020.03200.0632538.3164.1—
330.00710.1800.02540.0501678.8206.9—
340.00630.1600.02010.0398856.0260.9—
350.00560.1430.01600.03151079329.0—
360.00500.1270.01270.02501361414.8—
370.00450.1130.01000.01981716523.1—
380.00400.1010.007970.01572164659.6—
390.00350.0900.006320.01252729831.8—
400.00310.0800.005010.0098934411049—

Assumptions and limitations

  • Diameters are those of solid round wire. A stranded conductor of the same gauge has the same metal area but a larger overall diameter, so measure stranded wire by its strand count and strand gauge, not by its outside diameter.
  • Resistance is the DC value from ρ/A. Tinned copper, coated wire and real manufacturing tolerances give values a few percent higher.
  • The metric size is the smallest IEC 60228 size at least as large in area. IEC conductors are specified by maximum resistance, so a 4 mm² conductor can carry slightly less copper than 4.00 mm².
  • This page does not give the allowed current. Ampacity depends on the insulation rating, installation, bundling and ambient temperature, and is set by the wiring code: NEC Table 310.16 in the US, IEC 60364-5-52 elsewhere. Use the wire size calculator for the voltage drop.

Worked example

What are the size and resistance of 12 AWG solid copper wire at 20 °C, and which metric cable replaces it?

  1. Gauge number n = 12, so d = 0.005 × 92^(24 / 39) = 0.0808 in = 2.053 mm.
  2. Area: A = π × 2.053² / 4 = 3.309 mm², or 80.8² = 6 530 circular mils.
  3. Resistance at 20 °C: R' = 1.7241 × 10⁻⁸ / 3.309 × 10⁻⁶ = 5.211 × 10⁻³ Ω/m = 5.211 Ω/km, which is 1.588 Ω/1000 ft.
  4. Weight: 8 890 × 3.309 × 10⁻⁶ = 0.0294 kg/m, or 19.8 lb per 1 000 ft.
  5. The smallest IEC 60228 size with at least 3.309 mm² is 4 mm².

So 12 AWG copper is 2.05 mm thick with 3.31 mm² of copper, and 4 mm² is its metric replacement; 2.5 mm² would have 24 % less copper.

FAQ

What does the AWG number mean?

It counts the drawing steps in the original wire-making process, which is why bigger numbers mean thinner wire. Today the sizes are fixed by the ASTM B258 formula.

How many mm² is 12 AWG? And 14 AWG?

12 AWG is 3.31 mm² and 14 AWG is 2.08 mm². The nearest metric sizes at least as large are 4 mm² and 2.5 mm².

What is 1/0 or 4/0 wire?

Sizes larger than 1 AWG are 1/0, 2/0, 3/0 and 4/0, spoken as one-aught to four-aught. 4/0 is 0.46 in across and 107 mm². Beyond 4/0, sizes are given in kcmil, starting at 250 kcmil.

What is a kcmil or MCM?

A circular mil is the area of a circle one mil, a thousandth of an inch, across. A kcmil, also written MCM, is 1 000 circular mils, about 0.5067 mm².

How do I measure the gauge of a wire?

Strip the insulation and measure the bare diameter with a micrometer, then enter it in the diameter mode. For stranded wire, measure one strand, find its gauge, and multiply its area by the number of strands.

How much current can 12 AWG carry?

The wiring code sets that, from the insulation and the installation. In US homes, NEC 240.4(D) limits the overcurrent protection of 12 AWG copper to 20 A and of 14 AWG to 15 A.

Is aluminium wire the same gauge as copper for the same current?

No. Aluminium has about 64 % more resistance, so it is usually two gauges larger for the same current and voltage drop.