Generator size calculator

What size generator you need: running watts of your loads, the surge of the largest motor starting, and the minimum running, starting and kVA ratings.

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem

Introduction

To size a generator, add up the running watts of everything you want to power, then add the extra surge that the largest motor draws for a few seconds when it starts. The generator's running rating must cover the first number with some margin, and its starting rating must cover the second. A fridge, sump pump, furnace fan, lights, microwave and TV run on about 4 450 W, but need 6 000 W for the moment the furnace fan starts.

This calculator does that sum for any list of loads, for a home backup generator, an RV, a job site or a cabin. It gives the running and starting watts, the minimum ratings to look for on a generator, and the kVA rating of a permanently installed standby set.

Formulas

Running load and starting surge:

W_run = Σ W_running
surge = max(W_starting − W_running)       motors starting one at a time
surge = Σ (W_starting − W_running)        all starting together
W_peak = W_run + surge

Minimum ratings:

running rating ≥ W_run / k_max
starting rating ≥ W_peak
standby kVA = running rating / 0.8
  • W_running, W_starting — running and starting watts of each load, from the nameplate or manual
  • k_max — the highest share of its rating you want the generator to run at, 80 % by default
  • 0.8 — the power factor at which standby generators are rated (ISO 8528-1)

Assumptions and limitations

  • The default list is an example. Real running and starting watts vary by model, so read them from nameplates or manuals. A motor that shows only amps draws about volts × amps watts while running.
  • Motors usually start one at a time. After a power cut several may start together when the power returns; choose "all together" or use a transfer switch that staggers them.
  • Running a generator at no more than about 80 % of its rating leaves room for loads switching on and spares the engine. Inverter generators handle surges less well than their running rating suggests, so check their surge rating too.
  • Altitude and heat reduce an engine generator's output. A permanently connected standby generator must be installed with a transfer switch by a licensed electrician.

Worked example

A house wants to back up a fridge (700 W running, 2 200 W starting), a 1/2 hp sump pump (1 050 W, 2 150 W), a 1/2 hp furnace fan (800 W, 2 350 W), 600 W of lights, a 1 000 W microwave and 300 W of TV and internet. What generator is needed?

  1. Running watts: 700 + 1 050 + 800 + 600 + 1 000 + 300 = 4 450 W.
  2. Surges: fridge 1 500 W, sump pump 1 100 W, furnace fan 1 550 W. The largest is 1 550 W.
  3. Peak while the furnace fan starts: 4 450 + 1 550 = 6 000 W.
  4. Running rating at 80 % loading: 4 450 / 0.8 = 5 563 W.

So look for a generator rated at least about 5 600 running watts and 6 000 starting watts; a common 7 500 W portable model covers both. If all three motors could start together, the peak would be 8 600 W.

FAQ

What size generator do I need to run a house?

For essentials such as a fridge, sump pump, furnace fan, lights and a few outlets, typically 5 000 to 8 000 running watts. Whole-house backup with central air conditioning and electric cooking usually needs a 15 to 25 kW standby generator.

What is the difference between running and starting watts?

Running watts are what a load draws once it is going. Starting watts are the brief surge a motor needs to get moving, often two to three times its running watts.

Can a 3 500 W generator run a refrigerator?

Usually yes. A typical fridge runs on 600 to 800 W and starts at around 2 000 W, well within a 3 500 W generator's surge rating, leaving some capacity for lights and a few small loads.

Why not size the generator exactly to the load?

A generator running flat out for hours wears faster and has no capacity left to start another motor. Sizing for about 80 % leaves that margin.

What is the difference between kW and kVA on a generator?

Standby generators are rated in kVA at a power factor of 0.8, so a 25 kVA set delivers 20 kW. Portable generators are rated in watts.

How do I find the watts of an appliance?

Read the nameplate or manual. If it lists only amps, multiply by the voltage: a 5 A appliance on 120 V draws about 600 W.