Transformer full-load current chart (kVA to amps)

The full-load current is the current a transformer delivers at its rated kVA: I = S / (√3 × V) for three-phase, with V the line-to-line voltage, and I = S / V for single-phase. It sets the size of the cables and protection on each side. A 1 000 kVA transformer at 400 V delivers 1 443 A; at 11 kV, 52.5 A.

Free to reuse under CC BY 4.0 with a link to this page. Each table downloads as a CSV file.

To compute any value directly: kVA to amps

Three-phase, IEC ratings (A)

kVA400 V415 V690 V3.3 kV6.6 kV11 kV
2536.134.820.94.372.191.31
5072.269.641.88.754.372.62
10014413983.717.58.755.25
16023122313428.014.08.40
25036134820943.721.913.1
31545543826455.127.616.5
40057755633570.035.021.0
50072269641887.543.726.2
63090987652711055.133.1
8001 1551 11366914070.042.0
1 0001 4431 39183717587.552.5
1 2501 8041 7391 04621910965.6
1 6002 3092 2261 33928014084.0
2 0002 8872 7821 673350175105
2 5003 6083 4782 092437219131
3 1504 5474 3822 636551276165

Download this table as CSV

Three-phase, US ratings (A)

kVA208 V240 V480 V600 V4.16 kV13.8 kV
1541.636.118.014.42.080.63
3083.372.236.128.94.161.26
4512510854.143.36.251.88
7520818090.272.210.43.14
112.531227113510815.64.71
15041636118014420.86.28
22562554127121731.29.41
30083372236128941.612.6
5001 3881 20360148169.420.9
7502 0821 80490272210431.4
1 0002 7762 4061 20396213941.8
1 5004 1643 6081 8041 44320862.8
2 0005 5514 8112 4061 92527883.7
2 5006 9396 0143 0072 406347105

Download this table as CSV

Single-phase (A)

kVA120 V230 V240 V480 V
541.721.720.810.4
1083.343.541.720.8
1512565.262.531.3
2520810910452.1
37.531316315678.1
50417217208104
75625326313156
100833435417208
1671 392726696348

Download this table as CSV

How the table was made

Each value is the kVA to amps calculator’s line current for that rating and voltage. The current is the same whatever the load’s power factor; the power factor changes only how many kW the kVA can supply.

Cables and breakers are sized from this current with the factors in the wiring rules. Inrush current at switch-on can be 8 to 12 times the full-load current for a fraction of a second.

FAQ

What is the full-load current of a 500 kVA transformer at 480 V?
601 A, three-phase.

How many amps is 100 kVA single-phase at 240 V?
417 A.

  • kVA to amps: Line current from kVA and voltage for single-phase and three-phase supplies, kVA from amps, and the kW at a given power factor.
  • Transformer size calculator (kVA): Transformer kVA size from the load, power factor and growth, the next IEC or ANSI standard rating, rated currents, voltage regulation and losses.
  • Short-circuit current (IEC 60909): Three-phase short-circuit current at a switchboard from source, transformer and cable impedances; peak current and breaker check.
  • Cable sizing and voltage drop: Voltage drop, power loss and the minimum IEC conductor size for DC, single-phase and three-phase circuits from current, length, material and allowed drop.

Sources

  • IEC 60076-1:2011, Power transformers: general, clause 3.4 (rated power and rated current).
  • Hughes, Electrical and Electronic Technology, 12th edition, Three-phase systems (S = √3 V I).

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem