Electrical engineering practice problems

10 multiple-choice problems in the style of the FE and PE engineering exams. Pick an answer to check it, then open the worked solution. Every answer is recomputed by the electrical calculator that solves it, and the solution opens that calculator with the problem's numbers filled in.

  1. Full-load line current of a three-phase motor

    A 75 kW induction motor drives a process fan from a 400 V, three-phase supply. At rated load the motor efficiency is 94 % and the power factor is 0.86. The 75 kW is the rated shaft output. What line current does the motor draw at rated load?

    Show the answer and worked solution

    Answer: A, 134 A

    1. Electrical input: P_in = P_shaft / η = 75 / 0.94 = 79.8 kW.
    2. Line current: I = P_in / (√3 V cos φ) = 79 787 / (√3 × 400 × 0.86) = 134 A.
    3. The traps: 126 A forgets the efficiency and uses the shaft power as the input, 115 A leaves out the power factor (that is the apparent-power current at cos φ = 1), and 232 A uses the single-phase formula I = P / (V cos φ) without the √3.
  2. Voltage drop on a three-phase copper feeder

    A 400 V three-phase feeder carries 95 A at a power factor of 0.85 lagging over a route of 120 m. Each conductor is 35 mm² copper with a resistance of 0.524 Ω/km at 20 °C and a temperature coefficient of 0.00393 per K. The XLPE cable runs at its 90 °C conductor temperature, and its reactance is 0.08 Ω/km. What is the voltage drop as a percentage of the nominal voltage?

    Show the answer and worked solution

    Answer: B, 3.01 %

    1. Resistance at 90 °C: R = 0.524 × (1 + 0.00393 × 70) = 0.668 Ω/km, so R = 0.0802 Ω and X = 0.0096 Ω over 120 m.
    2. With sin φ = 0.527: ΔU = √3 I (R cos φ + X sin φ) = √3 × 95 × (0.0802 × 0.85 + 0.0096 × 0.527) = 12.0 V.
    3. As a percentage: 12.0 / 400 = 3.01 %.
    4. The traps: 2.41 % uses the 20 °C resistance, 3.48 % uses the single-phase factor 2 instead of √3, and 6.02 % doubles the route length as if the three-phase drop needed the return path.
  3. Capacitor bank rating to raise the power factor

    A factory takes 320 kW at a power factor of 0.72 lagging. The utility charges for reactive energy below a power factor of 0.95, so the plant engineer will install a capacitor bank at the main switchboard to raise the power factor to 0.95. What rating must the capacitor bank have?

    Show the answer and worked solution

    Answer: C, 203 kvar

    1. tan φ₁ = tan(acos 0.72) = 0.964 and tan φ₂ = tan(acos 0.95) = 0.329.
    2. Q_c = P (tan φ₁ − tan φ₂) = 320 × (0.964 − 0.329) = 203 kvar.
    3. The traps: 308 kvar corrects all the way to unity power factor (P tan φ₁), 170 kvar keeps the apparent power at 444 kVA and subtracts S (sin φ₁ − sin φ₂), and 108 kvar is the released capacity S₁ − S₂ in kVA, not the reactive power.
  4. Total losses of a distribution transformer at part load

    A 1000 kVA, 11/0.4 kV distribution transformer supplies a load of 600 kW at a power factor of 0.9. The nameplate gives no-load losses of 1.7 kW and load losses of 10.5 kW at rated current. What are the total transformer losses at this load?

    Show the answer and worked solution

    Answer: D, 6.37 kW

    1. Apparent load: S = P / cos φ = 600 / 0.9 = 667 kVA, so the load fraction is x = 667 / 1000 = 0.667.
    2. Load losses scale with the square of the current: P_loss = P_0 + x² P_k = 1.7 + 0.667² × 10.5 = 1.7 + 4.67 = 6.37 kW.
    3. The traps: 12.20 kW adds the full-load copper losses as if the transformer ran at rated current, 8.70 kW scales the load losses with x instead of x², and 5.48 kW takes the load fraction from kW (600 / 1000 = 0.6) instead of kVA.
  5. Voltage dip when a motor starts on a generator

    A 110 kW, 400 V pump motor starts direct on line from a 500 kVA standby generator with a transient reactance X'd of 0.20 per unit. The motor has a rated efficiency of 93 %, a power factor of 0.86 and a locked-rotor current of 6.5 times rated current. Using the reactance divider estimate, what voltage dip does the start cause?

    Show the answer and worked solution

    Answer: A, 26.3 %

    1. Rated input: S_n = P / (η cos φ) = 110 / (0.93 × 0.86) = 137.5 kVA, so the starting kVA is 6.5 × 137.5 = 894 kVA.
    2. Per-unit drop: x = X'd × S_start / S_gen = 0.20 × 894 / 500 = 0.358.
    3. Divider: dip = x / (1 + x) = 0.358 / 1.358 = 26.3 %.
    4. The traps: 35.8 % stops at X'd S_start / S_gen and ignores the divider, 22.2 % takes the starting kVA from the 110 kW shaft power without efficiency and power factor (715 kVA), and 10.7 % applies the star-delta current of one third.
  6. Number of luminaires for a workshop by the lumen method

    A workshop 20 m long and 12 m wide needs a maintained illuminance of 500 lx on the bench plane. The LED high-bays give 6000 lm each and hang 4.0 m above the working plane. The utilisation factor is 0.60 and the maintenance factor is 0.80. By the lumen method, how many luminaires are needed before rounding up to a layout?

    Show the answer and worked solution

    Answer: B, 41.7 luminaires

    1. Floor area: A = 20 × 12 = 240 m².
    2. Lumen method: N = E A / (Φ UF MF) = 500 × 240 / (6000 × 0.60 × 0.80) = 120 000 / 2880 = 41.7 luminaires, so 42 or more are installed.
    3. The traps: 33.3 forgets the maintenance factor, 25.0 forgets the utilisation factor, and 26.7 multiplies by the maintenance factor instead of dividing by it.
  7. Runtime of a 48 V battery bank with the Peukert effect

    A 48 V battery bank rated 200 Ah at the 20 h rate feeds a 2.4 kW AC load through an inverter with 92 % efficiency. The batteries have a Peukert exponent of 1.25, are new and at room temperature (no capacity derating), and may be discharged to 50 % depth of discharge. How long does the bank supply the load?

    Show the answer and worked solution

    Answer: C, 1.21 h

    1. DC current: I = P / (η V) = 2400 / (0.92 × 48) = 54.3 A.
    2. Peukert time to empty: t = H (C / (I H))^k = 20 × (200 / (54.3 × 20))^1.25 = 2.41 h.
    3. Runtime to 50 % depth of discharge: 0.5 × 2.41 = 1.21 h.
    4. The traps: 1.84 h ignores the Peukert effect (0.5 × 200 / 54.3), 2.41 h discharges the bank fully instead of to 50 %, and 1.34 h forgets the inverter efficiency (50.0 A).
  8. Capacitor voltage during RC charging

    A 22 µF capacitor in a delay circuit charges from 0 V through a 47 kΩ resistor when a 12 V supply is switched on. What is the capacitor voltage 1.5 s after the supply is switched on?

    Show the answer and worked solution

    Answer: D, 9.19 V

    1. Time constant: τ = R C = 47 000 × 22 × 10⁻⁶ = 1.034 s.
    2. Charging: V = V_s (1 − e^(−t/τ)) = 12 × (1 − e^(−1.5/1.034)) = 12 × (1 − 0.234) = 9.19 V.
    3. The traps: 2.81 V uses the discharge formula V_s e^(−t/τ), 7.59 V takes the 63 % value of one time constant, and 12.00 V treats kΩ × µF as milliseconds so the capacitor looks fully charged.
  9. Bandwidth of a series LC resonant circuit

    A series resonant circuit in a radio receiver front end has a 220 µH coil, a 470 pF capacitor and a total series loss resistance of 8 Ω. What is the −3 dB bandwidth of the circuit?

    Show the answer and worked solution

    Answer: A, 5.79 kHz

    1. Resonant frequency: f0 = 1 / (2π √(L C)) = 1 / (2π √(220 × 10⁻⁶ × 470 × 10⁻¹²)) = 495 kHz.
    2. Quality factor: Q = √(L / C) / R = √(220 × 10⁻⁶ / 470 × 10⁻¹²) / 8 = 684 / 8 = 85.5.
    3. Bandwidth: BW = f0 / Q = 495 / 85.5 = 5.79 kHz (the same as R / (2π L)).
    4. The traps: 36.36 kHz is R / L in rad/s read as hertz, 2.89 kHz is the half-bandwidth f0 / (2Q) from the centre to one −3 dB point, and 11.57 kHz doubles the bandwidth by counting f0 ± BW.
  10. Output of a voltage divider under load

    A sensor input is fed from a 24 V supply through a voltage divider with R1 = 10 kΩ at the top and R2 = 4.7 kΩ at the bottom. The input connected across R2 has a resistance of 10 kΩ. What voltage does the input see?

    Show the answer and worked solution

    Answer: B, 5.81 V

    1. The load is in parallel with R2: R2 ∥ R_L = 4.7 × 10 / (4.7 + 10) = 3.20 kΩ.
    2. Loaded output: V_out = V_in × 3.20 / (10 + 3.20) = 24 × 0.242 = 5.81 V.
    3. The traps: 7.67 V is the unloaded divider 24 × 4.7 / 14.7, 11.63 V puts the load in parallel with R1 instead of R2, and 11.28 V uses the ratio R2 / R1 instead of R2 / (R1 + R2).