AWG wire size chart (AWG to mm²)

American Wire Gauge numbers run backwards: the larger the number, the thinner the wire. Each step of three gauges halves the area. This chart gives the diameter and area of each solid conductor, its resistance in copper at 20 °C, and the smallest IEC metric cable size at least as large. 12 AWG is 3.31 mm², so the next metric size up is 4 mm².

Free to reuse under CC BY 4.0 with a link to this page. Each table downloads as a CSV file.

To compute any value directly: AWG wire gauge chart and converter

AWG solid conductor sizes, ASTM B258

AWGd (in)d (mm)Area (mm²)Area (kcmil)Cu Ω/km at 20 °CNext IEC size (mm²)
4/00.460011.684107.2211.60.1608120
3/00.409610.40585.03167.80.202895
2/00.36489.26667.43133.10.255770
1/00.32498.25153.48105.50.322470
10.28937.34842.4183.690.406650
20.25766.54433.6366.370.512735
30.22945.82726.6752.630.646435
40.20435.18921.1541.740.815225
50.18194.62116.7733.101.02825
60.16204.11513.3026.251.29616
70.14433.66510.5520.821.63416
80.12853.2648.36616.512.06110
90.11442.9066.63413.092.59910
100.10192.5885.26110.383.2776
110.09072.3054.1728.2344.1326
120.08082.0533.3096.5305.2114
130.07201.8282.6245.1786.5714
140.06411.6282.0814.1078.2852.5
150.05711.4501.6503.25710.452.5
160.05081.2911.3092.58313.171.5
170.04531.1501.0382.04816.611.5
180.04031.0240.82301.62420.951
190.03590.9120.65271.28826.410.75
200.03200.8120.51761.02233.310.75
210.02850.7230.41050.810142.000.50
220.02530.6440.32550.642452.960.50
230.02260.5730.25820.509566.780.50
240.02010.5110.20470.404084.210.50
250.01790.4550.16240.3204106.20.50
260.01590.4050.12880.2541133.90.50
270.01420.3610.10210.2015168.90.50
280.01260.3210.080980.1598212.90.50
290.01130.2860.064220.1267268.50.50
300.01000.2550.050930.1005338.50.50
310.00890.2270.040390.07970426.90.50
320.00800.2020.032030.06321538.30.50
330.00710.1800.025400.05013678.80.50
340.00630.1600.020140.03975856.00.50
350.00560.1430.015970.031521 0790.50
360.00500.1270.012670.025001 3610.50
370.00450.1130.010050.019831 7160.50
380.00400.1010.0079670.015722 1640.50
390.00350.0900.0063180.012472 7290.50
400.00310.0800.0050100.0098883 4410.50

Download this table as CSV

How the table was made

Diameters from the AWG definition in ASTM B258, d = 0.005 in × 92^((36 − n)/39), with 4/0 as n = −3. Resistance is for solid annealed copper at 20 °C (resistivity 1.7241 × 10⁻⁸ Ω·m, IEC 60028); stranded wire is about 2 % higher (ASTM B8). The metric column is the smallest size in IEC 60228 at least as large as the AWG area, the size to choose when replacing an AWG cable with a metric one.

Wire size is chosen for current rating, voltage drop and short-circuit withstand together. The current a conductor may carry depends on its insulation, installation and grouping, and is given in the wiring rules (NEC Table 310.16, IEC 60364-5-52), not here.

FAQ

What is 10 AWG in mm²?
5.26 mm². The next metric size up is 6 mm².

Is 2.5 mm² the same as 14 AWG?
Close but not the same: 14 AWG is 2.08 mm², a little smaller than 2.5 mm². 12 AWG is 3.31 mm².

  • AWG wire gauge chart and converter: Diameter, mm², circular mils, resistance and weight of every AWG size from 4/0 to 40, or the gauge of a measured wire, with the matching metric size.
  • Cable sizing and voltage drop: Voltage drop, power loss and the minimum IEC conductor size for DC, single-phase and three-phase circuits from current, length, material and allowed drop.
  • Wire size calculator (AWG and mm²): Smallest AWG and metric wire size that keeps the voltage drop within your limit for a DC, single-phase or three-phase circuit, with the drop and the loss.

Sources

  • ASTM B258-18, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires.
  • IEC 60028, International standard of resistance for copper.
  • IEC 60228:2004, Conductors of insulated cables (metric sizes).

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem