HVAC formulas

The formulas behind the 8 hvac and building services calculators, on one page you can print or save as a PDF. Each block lists its variables and standard; the heading opens the calculator, with its assumptions and a worked example.

Air changes per hour (ACH) and CFM calculator

Air changes and airflow for a room of volume V:

ACH = 60 × CFM / V_ft³ = Q_m³/h / V_m³
CFM = ACH × V_ft³ / 60

Whole-dwelling ventilation (ASHRAE 62.2):

Q = 0.03 × A_floor + 7.5 × (N_br + 1)    cfm, A in ft²
Q = 0.15 × A_floor + 3.5 × (N_br + 1)    L/s, A in m²
  • V — room volume, length × width × ceiling height
  • A_floor — conditioned floor area; N_br — number of bedrooms
  • 1 CFM = 1.699 m³/h = 0.4719 L/s

Air density calculator

Moist air as a mixture of ideal gases (ASHRAE Fundamentals, Chapter 1):

W = 0.621945 × p_w / (p − p_w),   p_w = RH × p_ws(t)
v = 287.042 × (t + 273.15) × (1 + 1.607858 W) / p
ρ = (1 + W) / v

Pressure at altitude Z in the standard atmosphere, and density altitude:

p = 101 325 × (1 − 2.25577 × 10⁻⁵ Z)^5.2559
h_ρ = (1 − (ρ / 1.225)^(1/4.2559)) / 2.25577 × 10⁻⁵
  • p_ws — saturation pressure of water vapour at t (Hyland–Wexler)
  • W — humidity ratio, kg of water per kg of dry air; v — m³ per kg of dry air
  • ρ — density of the moist air, kg/m³

BTU calculator: AC size for a room

Capacity from the ENERGY STAR chart for the floor area A, then the adjustments:

Q = chart(A) × f_sun + 600 × (people − 2) + 4 000 × kitchen    Btu/h
Area (ft²)Area (m²)Capacity (Btu/h)
100 to 1509 to 145 000
150 to 25014 to 236 000
250 to 30023 to 287 000
300 to 35028 to 338 000
350 to 40033 to 379 000
400 to 45037 to 4210 000
450 to 55042 to 5112 000
550 to 70051 to 6514 000
700 to 1 00065 to 9318 000
1 000 to 1 20093 to 11121 000
1 200 to 1 400111 to 13023 000
1 400 to 1 500130 to 13924 000
1 500 to 2 000139 to 18630 000
2 000 to 2 500186 to 23234 000

Conversions:

1 Btu/h = 0.29307 W,   1 ton of refrigeration = 12 000 Btu/h = 3.517 kW
  • f_sun — 0.9 for a heavily shaded room, 1.1 for a very sunny one, 1 otherwise
  • people — regular occupants; the chart already allows for two
  • kitchen — add 4 000 Btu/h if the unit serves a kitchen

Building heat loss calculator (U-values)

Transmission (fabric) loss and ventilation loss at the design temperatures:

Φ_T = Σ U_i × A_i × (θ_int − θ_ext)
Φ_V = ρ c_p × n × V × (1 − η) × (θ_int − θ_ext) / 3600

Heat loss coefficient and yearly heat:

H = Σ U_i A_i + ρ c_p n V (1 − η) / 3600      W/K
E = H × HDD × 24 / 1000                          kWh
  • U — thermal transmittance, W/(m²·K) or Btu/(h·ft²·°F); U = 1/R
  • A — area of the element; n — air changes per hour; V — heated volume
  • ρ c_p — 1 211 J/(m³·K) for air, i.e. 0.336 W per m³/h per K, or 1.08 Btu/h per cfm per °F
  • η — efficiency of any heat recovery; HDD — heating degree-days for the location

Dew point calculator

Vapour pressure from the relative humidity, and the dew point where saturation is reached:

p_w = RH × p_ws(t)
p_ws(t_d) = p_w    →   t_d

Moisture content and enthalpy:

W = 0.621945 × p_w / (p − p_w)
h = 1.006 t + W (2501 + 1.86 t)    kJ/kg

The quick Magnus approximation, good to about 0.1 °C between −40 and 50 °C:

γ = ln(RH) + 17.625 t / (243.04 + t)
t_d = 243.04 γ / (17.625 − γ)
  • t — air temperature, °C; RH — relative humidity as a fraction
  • p_ws — saturation pressure of water vapour (Hyland–Wexler equation in ASHRAE)
  • p — barometric pressure, which falls with altitude

Duct size calculator

Friction loss in a round duct (Darcy–Weisbach) with the Colebrook friction factor:

Δp/L = f × ρ V² / (2 D)
1/√f = −2 log10( ε/(3.7 D) + 2.51/(Re √f) ),   Re = ρ V D / μ

Velocity and the rectangular equivalent (Huebscher):

V = Q / (π D² / 4)
D_e = 1.30 × (a b)^0.625 / (a + b)^0.25
  • Q — airflow; V — velocity; D — round diameter
  • ρ = 1.204 kg/m³ and μ = 1.81 × 10⁻⁵ Pa·s, standard air at 20 °C
  • ε — roughness: 0.09 mm for galvanized steel duct
  • a, b — sides of the rectangular duct with the same friction as diameter D_e

Latent and sensible heat calculator (air and water)

Exact, per kilogram of dry air (ASHRAE Fundamentals Ch. 1):

ṁ = Q / v1
Q_total = ṁ (h1 − h2),   h = 1.006 t + W (2 501 + 1.86 t)
Q_latent = ṁ (W1 − W2)(2 501 + 1.86 t1)
Q_sensible = ṁ (1.006 + 1.86 W2)(t1 − t2)
SHR = Q_sensible / Q_total

Standard-air rules, IP units (Btu/h, cfm, °F, lb/lb, Btu/lb):

Q_s = 1.08 × cfm × ΔT     (1.10 in ASHRAE Ch. 18)
Q_l = 4 840 × cfm × ΔW
Q_t = 4.5 × cfm × Δh

SI equivalents per L/s: 1.21 (or 1.23) W/K, 3 010 W per kg/kg, 1.20 W per kJ/kg.

Water at atmospheric pressure:

Q = m [c_ice ΔT_ice + L_f + c_w ΔT_w + L_v + c_steam ΔT_steam]
  • Q — airflow at the entering state; v1 — its specific volume per kg of dry air
  • W — humidity ratio; h — enthalpy per kg of dry air; t — dry bulb temperature
  • L_f = 334 kJ/kg, L_v = 2 257 kJ/kg; c — specific heats of ice, water and steam

Mixed air temperature calculator (outdoor and return air)

Dry air mass flow of each stream, then the mass balances:

ṁ_i = Q_i / v_i
W_mix = (ṁ_OA W_OA + ṁ_RA W_RA) / (ṁ_OA + ṁ_RA)
h_mix = (ṁ_OA h_OA + ṁ_RA h_RA) / (ṁ_OA + ṁ_RA)

Mixed dry bulb from enthalpy and humidity ratio (SI, ASHRAE eq. 30):

h = 1.006 t + W (2 501 + 1.86 t)   →   t_mix = (h_mix − 2 501 W_mix) / (1.006 + 1.86 W_mix)

Outdoor-air fraction from measured temperatures:

x_OA = (t_RA − t_MA) / (t_RA − t_OA)
  • Q — airflow at the stream's own condition; v — specific volume per kg of dry air
  • W — humidity ratio, kg of water per kg of dry air; h — enthalpy, kJ/kg of dry air
  • t_OA, t_RA, t_MA — outdoor, return and mixed air dry bulb temperatures

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.