HVAC formulas
The formulas behind the 8 hvac and building services calculators, on one page you can print or save as a PDF. Each block lists its variables and standard; the heading opens the calculator, with its assumptions and a worked example.
Air changes per hour (ACH) and CFM calculator
Air changes and airflow for a room of volume V:
ACH = 60 × CFM / V_ft³ = Q_m³/h / V_m³
CFM = ACH × V_ft³ / 60
Whole-dwelling ventilation (ASHRAE 62.2):
Q = 0.03 × A_floor + 7.5 × (N_br + 1) cfm, A in ft²
Q = 0.15 × A_floor + 3.5 × (N_br + 1) L/s, A in m²
- V — room volume, length × width × ceiling height
- A_floor — conditioned floor area; N_br — number of bedrooms
- 1 CFM = 1.699 m³/h = 0.4719 L/s
Air density calculator
Moist air as a mixture of ideal gases (ASHRAE Fundamentals, Chapter 1):
W = 0.621945 × p_w / (p − p_w), p_w = RH × p_ws(t)
v = 287.042 × (t + 273.15) × (1 + 1.607858 W) / p
ρ = (1 + W) / v
Pressure at altitude Z in the standard atmosphere, and density altitude:
p = 101 325 × (1 − 2.25577 × 10⁻⁵ Z)^5.2559
h_ρ = (1 − (ρ / 1.225)^(1/4.2559)) / 2.25577 × 10⁻⁵
- p_ws — saturation pressure of water vapour at t (Hyland–Wexler)
- W — humidity ratio, kg of water per kg of dry air; v — m³ per kg of dry air
- ρ — density of the moist air, kg/m³
BTU calculator: AC size for a room
Capacity from the ENERGY STAR chart for the floor area A, then the adjustments:
Q = chart(A) × f_sun + 600 × (people − 2) + 4 000 × kitchen Btu/h
| Area (ft²) | Area (m²) | Capacity (Btu/h) |
|---|---|---|
| 100 to 150 | 9 to 14 | 5 000 |
| 150 to 250 | 14 to 23 | 6 000 |
| 250 to 300 | 23 to 28 | 7 000 |
| 300 to 350 | 28 to 33 | 8 000 |
| 350 to 400 | 33 to 37 | 9 000 |
| 400 to 450 | 37 to 42 | 10 000 |
| 450 to 550 | 42 to 51 | 12 000 |
| 550 to 700 | 51 to 65 | 14 000 |
| 700 to 1 000 | 65 to 93 | 18 000 |
| 1 000 to 1 200 | 93 to 111 | 21 000 |
| 1 200 to 1 400 | 111 to 130 | 23 000 |
| 1 400 to 1 500 | 130 to 139 | 24 000 |
| 1 500 to 2 000 | 139 to 186 | 30 000 |
| 2 000 to 2 500 | 186 to 232 | 34 000 |
Conversions:
1 Btu/h = 0.29307 W, 1 ton of refrigeration = 12 000 Btu/h = 3.517 kW
- f_sun — 0.9 for a heavily shaded room, 1.1 for a very sunny one, 1 otherwise
- people — regular occupants; the chart already allows for two
- kitchen — add 4 000 Btu/h if the unit serves a kitchen
Building heat loss calculator (U-values)
Transmission (fabric) loss and ventilation loss at the design temperatures:
Φ_T = Σ U_i × A_i × (θ_int − θ_ext)
Φ_V = ρ c_p × n × V × (1 − η) × (θ_int − θ_ext) / 3600
Heat loss coefficient and yearly heat:
H = Σ U_i A_i + ρ c_p n V (1 − η) / 3600 W/K
E = H × HDD × 24 / 1000 kWh
- U — thermal transmittance, W/(m²·K) or Btu/(h·ft²·°F); U = 1/R
- A — area of the element; n — air changes per hour; V — heated volume
- ρ c_p — 1 211 J/(m³·K) for air, i.e. 0.336 W per m³/h per K, or 1.08 Btu/h per cfm per °F
- η — efficiency of any heat recovery; HDD — heating degree-days for the location
Dew point calculator
Vapour pressure from the relative humidity, and the dew point where saturation is reached:
p_w = RH × p_ws(t)
p_ws(t_d) = p_w → t_d
Moisture content and enthalpy:
W = 0.621945 × p_w / (p − p_w)
h = 1.006 t + W (2501 + 1.86 t) kJ/kg
The quick Magnus approximation, good to about 0.1 °C between −40 and 50 °C:
γ = ln(RH) + 17.625 t / (243.04 + t)
t_d = 243.04 γ / (17.625 − γ)
- t — air temperature, °C; RH — relative humidity as a fraction
- p_ws — saturation pressure of water vapour (Hyland–Wexler equation in ASHRAE)
- p — barometric pressure, which falls with altitude
Duct size calculator
Friction loss in a round duct (Darcy–Weisbach) with the Colebrook friction factor:
Δp/L = f × ρ V² / (2 D)
1/√f = −2 log10( ε/(3.7 D) + 2.51/(Re √f) ), Re = ρ V D / μ
Velocity and the rectangular equivalent (Huebscher):
V = Q / (π D² / 4)
D_e = 1.30 × (a b)^0.625 / (a + b)^0.25
- Q — airflow; V — velocity; D — round diameter
- ρ = 1.204 kg/m³ and μ = 1.81 × 10⁻⁵ Pa·s, standard air at 20 °C
- ε — roughness: 0.09 mm for galvanized steel duct
- a, b — sides of the rectangular duct with the same friction as diameter D_e
Latent and sensible heat calculator (air and water)
Exact, per kilogram of dry air (ASHRAE Fundamentals Ch. 1):
ṁ = Q / v1
Q_total = ṁ (h1 − h2), h = 1.006 t + W (2 501 + 1.86 t)
Q_latent = ṁ (W1 − W2)(2 501 + 1.86 t1)
Q_sensible = ṁ (1.006 + 1.86 W2)(t1 − t2)
SHR = Q_sensible / Q_total
Standard-air rules, IP units (Btu/h, cfm, °F, lb/lb, Btu/lb):
Q_s = 1.08 × cfm × ΔT (1.10 in ASHRAE Ch. 18)
Q_l = 4 840 × cfm × ΔW
Q_t = 4.5 × cfm × Δh
SI equivalents per L/s: 1.21 (or 1.23) W/K, 3 010 W per kg/kg, 1.20 W per kJ/kg.
Water at atmospheric pressure:
Q = m [c_ice ΔT_ice + L_f + c_w ΔT_w + L_v + c_steam ΔT_steam]
- Q — airflow at the entering state; v1 — its specific volume per kg of dry air
- W — humidity ratio; h — enthalpy per kg of dry air; t — dry bulb temperature
- L_f = 334 kJ/kg, L_v = 2 257 kJ/kg; c — specific heats of ice, water and steam
Mixed air temperature calculator (outdoor and return air)
Dry air mass flow of each stream, then the mass balances:
ṁ_i = Q_i / v_i
W_mix = (ṁ_OA W_OA + ṁ_RA W_RA) / (ṁ_OA + ṁ_RA)
h_mix = (ṁ_OA h_OA + ṁ_RA h_RA) / (ṁ_OA + ṁ_RA)
Mixed dry bulb from enthalpy and humidity ratio (SI, ASHRAE eq. 30):
h = 1.006 t + W (2 501 + 1.86 t) → t_mix = (h_mix − 2 501 W_mix) / (1.006 + 1.86 W_mix)
Outdoor-air fraction from measured temperatures:
x_OA = (t_RA − t_MA) / (t_RA − t_OA)
- Q — airflow at the stream's own condition; v — specific volume per kg of dry air
- W — humidity ratio, kg of water per kg of dry air; h — enthalpy, kJ/kg of dry air
- t_OA, t_RA, t_MA — outdoor, return and mixed air dry bulb temperatures
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.