Skip to content
Engineering Bible

Results appear as you type. Use the arrow keys to move through them and Enter to open one.

Popular

↑ ↓ moveEnter openEsc close

Latent and sensible heat calculator (air and water)

Sensible, latent and total heat of an airstream by psychrometrics and the 1.08 and 4840 rules, SHR and coil load; and the heat to melt or boil water.

Units
Cooling load 38,481 Btu/h: 26,439 Btu/h sensible, 12,042 Btu/h latent, SHR 0.69.sensible 26,439 Btu/hlatent 12,042 Btu/htotal 38,481 Btu/hSensible heat ratio 0.69Sensible 26,439 Btu/h + latent 12,042 Btu/h = 38,481 Btu/hBar to scale: the share of the load that changes temperature, and the share that removes moisture
Drawn for the default inputs. It redraws as you change them.

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem

Introduction

Sensible heat changes the temperature of air or water. Latent heat changes its state, such as condensing moisture out of air or melting ice, without changing the temperature. A cooling coil does both: 1 000 cfm cooled from 80 °F dry bulb and 67 °F wet bulb to 55/54 °F removes 26 440 Btu/h of sensible heat and 12 040 Btu/h of latent heat.

This calculator splits the load of an airstream between two states into sensible and latent heat. It uses exact psychrometric enthalpies and also shows the 1.08, 4 840 and 4.5 rules. It gives the sensible heat ratio, the coil load in tons and the condensate. A second mode gives the heat to warm, melt, boil, condense or freeze water, with the latent heats of 334 and 2 257 kJ/kg. It is for HVAC engineers, technicians and students.

Formulas

Exact, per kilogram of dry air (ASHRAE Fundamentals Ch. 1):

ṁ = Q / v1
Q_total = ṁ (h1 − h2),   h = 1.006 t + W (2 501 + 1.86 t)
Q_latent = ṁ (W1 − W2)(2 501 + 1.86 t1)
Q_sensible = ṁ (1.006 + 1.86 W2)(t1 − t2)
SHR = Q_sensible / Q_total

Standard-air rules, IP units (Btu/h, cfm, °F, lb/lb, Btu/lb):

Q_s = 1.08 × cfm × ΔT     (1.10 in ASHRAE Ch. 18)
Q_l = 4 840 × cfm × ΔW
Q_t = 4.5 × cfm × Δh

SI equivalents per L/s: 1.21 (or 1.23) W/K, 3 010 W per kg/kg, 1.20 W per kJ/kg.

Water at atmospheric pressure:

Q = m [c_ice ΔT_ice + L_f + c_w ΔT_w + L_v + c_steam ΔT_steam]
  • Q — airflow at the entering state; v1 — its specific volume per kg of dry air
  • W — humidity ratio; h — enthalpy per kg of dry air; t — dry bulb temperature
  • L_f = 334 kJ/kg, L_v = 2 257 kJ/kg; c — specific heats of ice, water and steam

Assumptions and limitations

  • The airflow is measured at the entering condition. The rules assume standard air at 0.075 lb/ft³, so they overstate the heat for warm air or at altitude.
  • The exact split takes the latent heat as removing the moisture at the entering temperature. The sensible heat is the cooling of the drier air. The two add up exactly to the total.
  • The coil load subtracts the small enthalpy of the condensate leaving the coil.
  • Water changes state at 0 °C and 100 °C, which holds at sea-level pressure. The specific heats are constant, and all five values can be changed.

Worked example

A cooling coil handles 1 000 cfm. Air enters at 80 °F dry bulb and 67 °F wet bulb and leaves at 55 °F dry bulb and 54 °F wet bulb, at sea level.

  1. Entering air: W1 = 0.01117 lb/lb, h1 = 55.31 kJ/kg, v1 = 13.85 ft³/lb.
  2. Leaving air: W2 = 0.00863 lb/lb, h2 = 34.65 kJ/kg.
  3. Dry air flow: 1 000 / 13.85 = 72.2 lb/min, or 0.546 kg/s.
  4. Latent: 0.546 × 0.00253 × (2 501 + 1.86 × 26.7) = 3.53 kW, or 12 040 Btu/h.
  5. Sensible: 0.546 × (1.006 + 1.86 × 0.00863) × 13.9 = 7.75 kW, or 26 440 Btu/h.
  6. Total: 11.28 kW, or 38 480 Btu/h. SHR = 26 440 / 38 480 = 0.69.
  7. Coil load less the condensate enthalpy: 3.19 TR, removing 11.0 lb/h of water.

The 1.08 rule gives 1.08 × 1 000 × 25 = 27 000 Btu/h of sensible heat. It is 2 % high because air at 80 °F is lighter than standard air.

Cooling load 38,481 Btu/h: 26,439 Btu/h sensible, 12,042 Btu/h latent, SHR 0.69.
The worked example, drawn by the same code as the live drawing above.

FAQ

What is the difference between sensible and latent heat?

Sensible heat changes the temperature you can read on a thermometer. Latent heat changes the state, such as water vapour condensing on a coil or ice melting, at constant temperature.

Where does the 1.08 in Q = 1.08 × cfm × ΔT come from?

Standard air weighs 0.075 lb/ft³ and has a specific heat of 0.24 Btu/(lb·°F). Multiply by 60 minutes an hour: 0.075 × 60 × 0.24 = 1.08.

Where does 4 840 come from?

It is 0.075 lb/ft³ × 60 min/h × about 1 076 Btu/lb, the heat to condense water vapour from air. Multiply it by the cfm and the change in humidity ratio in lb/lb.

What is the sensible heat ratio?

The sensible share of the total cooling load. A dry climate or a server room has an SHR near 1; a coil that removes a lot of moisture, as in the example, is about 0.7.

How much heat does it take to melt ice?

334 kJ per kilogram, the same heat that warms liquid water by about 80 K. Taking 1 kg of ice at −10 °C to water at 20 °C needs 438.7 kJ.

Why does boiling take so much energy?

Vaporising water needs 2 257 kJ/kg, 5.4 times the 419 kJ/kg that warms it from 0 to 100 °C. That is why steam carries so much heat.

Related calculators

What this calculator is checked against

Before every release the calculator must reproduce each case below. The note under each case says where the expected answer comes from: a standard, a textbook, a published table, or a hand calculation shown in full.

  1. Rules for 1 000 cfm cooled 25 °F: 1.08 × 1 000 × 25 = 27 000 Btu/h, 1.10 gives 27 500; latent 4 840 cfm ΔW; total 4.5 cfm ΔhASHRAE Handbook — Fundamentals Ch. 18 (q_s = 1.10 Q Δt, q_l = 4 840 Q ΔW, q_t = 4.5 Q Δh); classic 1.08 = 0.075 × 60 × 0.24
  2. Exact split for 80/67 °F to 55/54 °F at 1 000 cfm: sensible 26 440, latent 12 040, total 38 480 Btu/h; sensible + latent = totalASHRAE Fundamentals Ch. 1 eq. 30, h = 1.006 t + W (2 501 + 1.86 t); hand calculation (ṁ = 0.546 kg/s, Δh = 20.66 kJ/kg)
  3. Dry air at 70 °F (0.0749 lb/ft³, close to standard 0.075) cooled by 10 °F: the exact sensible heat equals the 1.08 rule within 0.1 %Standard air 0.075 lb/ft³ and c_p 0.24 Btu/(lb·°F) behind the 1.08 constant; ASHRAE Fundamentals Ch. 1
  4. Serway heating curve: 1 g of ice at −30 °C to steam at 120 °C needs 62.7 + 333 + 419 + 2 260 + 40.2 J = 3.11 kJSerway & Jewett, Physics for Scientists and Engineers, 9th ed., Ch. 20 (c_ice 2 090, c_w 4 186, c_steam 2 010 J/(kg·K); L_f 3.33e5, L_v 2.26e6 J/kg)
  5. Latent heats: melting 1 kg of ice at 0 °C takes 334 kJ, boiling 1 kg at 100 °C 2 257 kJ; condensing gives them back; 1 kW boils it in 37.6 minLatent heats of water 334 and 2 257 kJ/kg (IAPWS-IF97: 2 256.5 kJ/kg at 1 atm)
  6. Invalid input: ice above 0 °C, steam below 100 °C, a wet bulb above the dry bulb and zero airflow are rejectedBehaviour check: warnings and rejected inputs
  7. Worked example of the article: the calculator reproduces 26 440 Btu/h, 12 040 Btu/h, 38 480 Btu/h, 0.69, 3.19 TR, 27 000 Btu/h to the digits printedThe worked example on this page, to the digits printed

Assumptions and sources

Assumptions and limits

  • The airflow is the volume at the entering condition; it is converted to dry air mass with the moist-air specific volume (ASHRAE Fundamentals Ch. 1) at the standard pressure of the altitude entered.
  • The exact split takes the latent heat as the enthalpy change of removing the moisture at the entering temperature, (W1 − W2)(2 501 + 1.86 t1), and the sensible heat as the cooling of the drier air; the two add up to the total enthalpy change.
  • The rules use standard air (0.075 lb/ft³): 1.08 Btu/h per cfm per °F with c_p = 0.24, or 1.10 with the moist-air c_p of ASHRAE Fundamentals Ch. 18, 4 840 per cfm per lb/lb of humidity ratio and 4.5 per cfm per Btu/lb of enthalpy; SI equivalents 1.21 or 1.23 W per L/s per K, 3 010 and 1.20.
  • Positive heat is removed from the air (cooling); a negative value means heat or moisture is added. The coil load subtracts the enthalpy of the condensate leaving at the air outlet temperature.
  • Water phase changes are at atmospheric pressure: melting at 0 °C and boiling at 100 °C, with constant specific heats; the latent heats default to 334 kJ/kg for fusion and 2 257 kJ/kg for vaporisation and can be changed.

Sources

  • ASHRAE Handbook — Fundamentals (2017), Ch. 1 Psychrometrics (enthalpy eq. 30, wet bulb eqs. 33/35, moist-air cooling and dehumidification) and Ch. 18 (q_s = 1.10 Q Δt, q_l = 4 840 Q ΔW, q_t = 4.5 Q Δh; SI 1.23, 3 010, 1.20)
  • R. A. Serway & J. W. Jewett, Physics for Scientists and Engineers, 9th ed., Ch. 20 (specific and latent heats of water; heating 1 g of ice at −30 °C to steam at 120 °C needs 3.11 kJ)
  • IAPWS-IF97: enthalpy of vaporisation of water at 1 atm, 2 256.5 kJ/kg (the 2 257 kJ/kg default)

Cite this calculator

Papandreou, C. (2026). Latent and sensible heat calculator (air and water). Engineering Bible. https://engineeringbible.com/hvac/latent-sensible-heat/

Embed this calculator on your site

Copy this HTML into your page. The calculator stays free to use and links back here.

By Christos Papandreou. Updated . How the numbers are checked.