HVAC practice problems
10 multiple-choice problems in the style of the FE and PE engineering exams. Pick an answer to check it, then open the worked solution. Every answer is recomputed by the hvac and building services calculator that solves it, and the solution opens that calculator with the problem's numbers filled in.
-
Supply airflow for 10 air changes per hour
A school science laboratory is 12 m long and 8 m wide with a 3.2 m ceiling. The design calls for 10 air changes per hour of supply air. What supply airflow is needed, in litres per second?
Show the answer and worked solution
Answer: B, 853 L/s
- Room volume: V = 12 × 8 × 3.2 = 307.2 m³.
- Airflow: Q = ACH × V / 3600 = 10 × 307.2 / 3600 = 0.853 m³/s = 853 L/s.
- The traps: 267 L/s uses the floor area and forgets the ceiling height, 3 072 L/s is the flow in m³/h labelled as L/s, and 51 200 L/s divides by 60 instead of 3600.
Check every step: Air changes per hour (ACH) and CFM calculator, opened with this problem’s numbers
-
Density of humid outdoor air at a high-altitude site
An air handling unit at a high-altitude site, where the barometric pressure is 85.0 kPa, draws outdoor air at 32 °C and 40 % relative humidity. The saturation vapour pressure at 32 °C is 4.76 kPa. What is the density of the moist outdoor air?
Show the answer and worked solution
Answer: A, 0.962 kg/m³
- Vapour pressure: p_v = 0.40 × 4.76 = 1.90 kPa; dry-air partial pressure p_a = 85.0 − 1.90 = 83.10 kPa. T = 305.15 K.
- Density of the mixture: ρ = p_a / (R_a T) + p_v / (R_v T) = 83 100 / (287.05 × 305.15) + 1 904 / (461.5 × 305.15) = 0.9487 + 0.0135 = 0.962 kg/m³.
- The traps: 0.984 kg/m³ adds the vapour mass to dry air at the full 85 kPa (humid air is lighter, not heavier), 1.149 kg/m³ uses the sea-level pressure of 101.325 kPa, and 1.225 kg/m³ is standard sea-level air.
Check every step: Air density calculator, opened with this problem’s numbers
-
Dew point to check for pipe sweating in an office
A chilled-water pipe runs through an office held at 24 °C and 55 % relative humidity at sea level (101.325 kPa). To decide whether the pipe needs insulation against condensation, find the dew point of the room air.
Show the answer and worked solution
Answer: C, 14.4 °C
- Saturation vapour pressure at 24 °C (Hyland–Wexler): p_ws = 2.986 kPa.
- Vapour pressure: p_v = 0.55 × 2.986 = 1.642 kPa.
- The dew point is the temperature at which p_ws = 1.642 kPa: t_d = 14.4 °C. Any pipe surface below this will sweat.
- The traps: 17.8 °C is the wet-bulb temperature, not the dew point, 15.0 °C is the rough rule t − (100 − RH) / 5, and 13.2 °C multiplies the temperature by the relative humidity.
Check every step: Dew point calculator, opened with this problem’s numbers
-
Round duct diameter for a target air velocity
A main supply duct must carry 1.2 m³/s of air. To keep noise down the designer limits the air velocity to 5 m/s. What inside diameter of round duct gives exactly this velocity?
Show the answer and worked solution
Answer: D, 553 mm
- Area needed: A = Q / V = 1.2 / 5 = 0.24 m².
- Diameter: D = √(4 A / π) = √(4 × 0.24 / π) = 0.553 m = 553 mm.
- The traps: 276 mm solves A = π D² without the 4 (the radius taken for the diameter), 306 mm forgets the square root, and 490 mm takes √A, the side of a square duct.
Check every step: Duct size calculator, opened with this problem’s numbers
-
Rectangular duct width with the same friction as a round duct
A branch duct carries 0.9 m³/s and is sized round at 6 m/s. The ceiling void only allows a rectangular duct 300 mm deep. Using the Huebscher equivalent diameter D_e = 1.30 (a b)^0.625 / (a + b)^0.25, what width b gives the same friction loss as the round duct?
Show the answer and worked solution
Answer: B, 545 mm
- Round size: D = √(4 Q / (π V)) = √(4 × 0.9 / (π × 6)) = 0.437 m.
- Set D_e = 0.437 m with a = 0.300 m and solve 1.30 (0.3 b)^0.625 / (0.3 + b)^0.25 = 0.437 by trial: b = 0.545 m = 545 mm.
- The traps: 500 mm matches the area (0.15 m² / 0.3 m), which gives more friction than the round duct, 637 mm divides D² by a and forgets π / 4, and 386 mm matches the perimeter.
Check every step: Duct size calculator, opened with this problem’s numbers
-
Design heat loss of a house: fabric and ventilation
A house has walls of 120 m² (U 0.28), windows of 24 m² (U 1.4), a roof of 80 m² (U 0.16) and a ground floor of 80 m² (U 0.22), all U in W/(m²·K). The heated volume is 240 m³ with 0.6 air changes per hour and no heat recovery. Design temperatures are 20 °C inside and −5 °C outside. Take air at 1.204 kg/m³ and 1006 J/(kg·K). What is the total design heat loss?
Show the answer and worked solution
Answer: A, 3.65 kW
- Fabric: Σ U A = 120 × 0.28 + 24 × 1.4 + 80 × 0.16 + 80 × 0.22 = 97.6 W/K; Q_f = 97.6 × 25 = 2 440 W.
- Ventilation: Q_v = ρ c_p (n V / 3600) ΔT = 1.204 × 1006 × (0.6 × 240 / 3600) × 25 = 1 211 W.
- Total: 2 440 + 1 211 = 3 651 W = 3.65 kW.
- The traps: 2.44 kW leaves out the ventilation loss, 2.19 kW uses ΔT = 20 − 5 = 15 K (the sign of the outdoor temperature lost), and 3.45 kW leaves the air density out of the ventilation term.
Check every step: Building heat loss calculator (U-values), opened with this problem’s numbers
-
Ventilation heat loss of a flat with heat recovery
A flat with a heated volume of 180 m³ is ventilated at 1.0 air change per hour through a heat recovery unit with an efficiency of 85 %. Design temperatures are 21 °C inside and −4 °C outside. Take air at 1.204 kg/m³ and 1006 J/(kg·K). What is the design ventilation heat loss?
Show the answer and worked solution
Answer: C, 227 W
- Without recovery: Q = ρ c_p (n V / 3600) ΔT = 1.204 × 1006 × (1.0 × 180 / 3600) × (21 − (−4)) = 1 514 W.
- The recovery unit returns 85 % of it: Q_v = 1 514 × (1 − 0.85) = 227 W.
- The traps: 1 514 W ignores the heat recovery, 1 287 W multiplies by the efficiency instead of by (1 − η), and 154 W uses ΔT = 21 − 4 = 17 K.
Check every step: Building heat loss calculator (U-values), opened with this problem’s numbers
-
Heat to turn ice at −10 °C into steam at 110 °C
A humidifier test starts with 2 kg of ice at −10 °C and ends with steam at 110 °C at atmospheric pressure. Take c_ice = 2.09, c_water = 4.19 and c_steam = 2.01 kJ/(kg·K), latent heat of fusion 334 kJ/kg and of vaporisation 2257 kJ/kg. How much heat must be added?
Show the answer and worked solution
Answer: D, 6.10 MJ
- Ice −10 → 0 °C: 2 × 2.09 × 10 = 41.8 kJ. Melting: 2 × 334 = 668 kJ.
- Water 0 → 100 °C: 2 × 4.19 × 100 = 838 kJ. Boiling: 2 × 2257 = 4 514 kJ.
- Steam 100 → 110 °C: 2 × 2.01 × 10 = 40.2 kJ.
- Total: 41.8 + 668 + 838 + 4 514 + 40.2 = 6 102 kJ = 6.10 MJ.
- The traps: 1.59 MJ leaves out the latent heat of vaporisation, 5.43 MJ leaves out the latent heat of fusion, and 5.18 MJ counts only the two latent heats.
Check every step: Latent and sensible heat calculator (air and water), opened with this problem’s numbers
-
Mixed air temperature in an air handling unit
An air handling unit at sea level mixes 1.0 m³/s of outdoor air at 32 °C and 40 % relative humidity with 4.0 m³/s of return air at 24 °C and 50 % relative humidity. What is the dry-bulb temperature of the mixed air?
Show the answer and worked solution
Answer: B, 25.6 °C
- Mixing is a mass and energy balance; with flows this close in density the volume-weighted average is a good estimate.
- T_MA = (1.0 × 32 + 4.0 × 24) / (1.0 + 4.0) = 25.6 °C. The full psychrometric balance gives 25.57 °C, because the warm outdoor air is slightly less dense.
- The traps: 28.0 °C is the plain average of the two temperatures, 30.4 °C swaps the weights of the two streams, and 22.4 °C subtracts the outdoor-air share of the difference instead of adding it.
Check every step: Mixed air temperature calculator (outdoor and return air), opened with this problem’s numbers
-
Outdoor airflow from measured mixing temperatures
An air handling unit supplies 5.0 m³/s. During a commissioning check the return air is at 24 °C, the outdoor air at 35 °C and the mixed air at 26.5 °C. Estimate the outdoor airflow in the supply from the temperature balance.
Show the answer and worked solution
Answer: C, 1.14 m³/s
- Outdoor-air fraction: X = (T_MA − T_RA) / (T_OA − T_RA) = (26.5 − 24) / (35 − 24) = 0.227.
- Outdoor airflow: Q_OA = X × Q_total = 0.227 × 5.0 = 1.14 m³/s.
- The traps: 3.86 m³/s uses (T_OA − T_MA) / (T_OA − T_RA), which is the return-air fraction, 1.47 m³/s divides by (T_OA − T_MA) instead of (T_OA − T_RA), and 0.36 m³/s divides by the outdoor temperature itself.
Check every step: Mixed air temperature calculator (outdoor and return air), opened with this problem’s numbers
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.