Interactive psychrometric chart

Click air states onto a live psychrometric chart and draw heating, cooling, dehumidifying, mixing and humidifying processes with their loads.

What the simulator shows

A psychrometric chart maps every state of moist air on one sheet. Dry-bulb temperature runs along the bottom and humidity ratio, the mass of water vapour per kilogram of dry air, up the left side. The curved lines show relative humidity, wet bulb, enthalpy and specific volume, so one point gives every property at once.

Click the chart to place up to four air states, A to D, and drag them about. Then chain up to two processes: heating or cooling, a cooling coil, an evaporative or steam humidifier, or the mixing of two streams. A red dot carries a parcel of air along each process line. The side panel gives the properties of the selected point and the sensible, latent and total loads for the airflow you set.

Things to try

  1. Read the default air handler. Return air A at 25 °C and 50 % mixes with 30 % outdoor air B at 32 °C and 45 %. The mix sits at 27.1 °C on the straight line between them. The coil, with an apparatus dew point of 10 °C and a bypass factor of 0.15, delivers 12.6 °C air at 90 %. At 5 000 m³/h it removes 25.2 kW sensible and 12.2 kW latent heat, a sensible heat ratio of 0.67, and drains 17.2 kg of condensate an hour.
  2. Change the bypass factor, then the apparatus dew point. Drag outlet 2 along its line. A bypass factor of 0.05 gives 10.9 °C air and 42.0 kW; 0.30 gives 15.1 °C and 30.5 kW. The sensible heat ratio stays at 0.67, because the line keeps its slope. Now raise the apparatus dew point to 16 °C, above the 15.4 °C dew point of the mixed air. The coil stays dry, the ratio becomes 1 and no water drains.
  3. Heat winter air, then humidify it. Set A to 5 °C and 80 %, process 1 to heat to 22 °C and process 2 to steam. Heating alone keeps the humidity ratio at 4.31 g/kg, so the relative humidity falls to 26 %. Adding 3.3 g/kg of steam lifts it to 45 % and warms the air by only 0.5 K.
  4. Cool desert air with water. Set A to 38 °C and 20 %, process 1 to evaporative at 85 % effectiveness and process 2 to none. The air leaves at 23.4 °C and 80 % with its wet bulb unchanged at 20.8 °C. At 5 000 m³/h it takes up 35 kg of water an hour, while its enthalpy hardly changes.
  5. Go up a mountain. Set the altitude to 1 500 m. The pressure falls to 84.6 kPa and the whole chart moves up. Air at 25 °C and 50 % now holds 11.88 g/kg instead of 9.88 g/kg, its density drops from 1.177 to 0.981 kg/m³, and its dew point stays at 13.9 °C.
  6. Make fog. Set A to 30 °C and 90 %, B to −5 °C and 90 %, and mix them half and half. The straight line between them cuts through the saturation curve. The mix lands beyond it at 12.8 °C, so the extra water must appear as fog.

The model behind it

Properties. All the properties come from the site's shared psychrometrics module, which follows ASHRAE Handbook Fundamentals, chapter 1. The saturation pressure p_ws is the Hyland–Wexler formula, over water at and above 0 °C and over ice below it (eqs. 5 and 6). The pressure comes from the altitude Z by the standard atmosphere (eq. 3):

p   = 101.325 (1 − 2.25577×10⁻⁵ Z)^5.2559         kPa, Z in m
W   = 0.621945 p_w / (p − p_w),   p_w = φ p_ws(t)   kg/kg dry air  (eq. 20)
h   = 1.006 t + W (2501 + 1.86 t)                  kJ/kg dry air  (eq. 30)
v   = 0.287042 (t + 273.15)(1 + 1.607858 W) / p     m³/kg dry air  (eq. 26)
ρ   = (1 + W) / v

The dew point is the temperature at which p_ws equals p_w. The wet bulb t* solves the adiabatic saturation balance (eq. 33, or eq. 35 over ice), where W*_s is the saturation humidity ratio at t*:

W = [(2501 − 2.326 t*) W*s − 1.006 (t − t*)] / (2501 + 1.86 t − 4.186 t*)

The same equations draw the chart lines. The 100 % line is the saturation curve. Each wet-bulb line starts on it where t = t*, and each enthalpy line holds h constant out to it. The chart uses dry bulb and humidity ratio as straight axes. The ASHRAE chart uses enthalpy and humidity ratio, so its dry-bulb lines lean slightly. Readings are the same on both. A mixing line is exactly straight on the ASHRAE chart and within about 0.1 K of straight on this one.

Processes. Heating or cooling keeps W and moves t. It stops at the dew point, since colder air would condense. The cooling coil uses the apparatus dew point (ADP) and bypass factor (BF) method: the outlet lies on the straight line from the inlet to the ADP on the saturation curve. If the ADP is above the inlet dew point, the coil stays dry. The evaporative humidifier follows the inlet wet bulb with water supplied at the wet bulb. The steam humidifier adds steam at 100 °C, whose enthalpy is taken as 2 687 kJ/kg from the vapour term of eq. 30; steam tables give 2 676 kJ/kg. Mixing conserves dry air, water and enthalpy:

Coil:        t₂ = t_ADP + BF (t₁ − t_ADP),   W₂ = W_ADP + BF (W₁ − W_ADP)
Evaporative: t₂ = t₁ − ε (t₁ − t*),   W₂ on the wet-bulb line of t*
Steam:       W₂ = W₁ + ΔW,   h₂ = h₁ + ΔW × 2687
Mixing:      W₃ = (1 − x) W₁ + x W₂,   h₃ = (1 − x) h₁ + x h₂,   x = share of stream 2 by dry-air mass

Loads. The airflow is measured at the outlet of the last process, the supply air. Its specific volume gives the dry-air mass flow ṁ, and each mixing step upstream takes away the second stream. The split is the one the latent and sensible heat calculator uses:

Q_total    = ṁ (h₂ − h₁)
Q_latent   = ṁ (W₂ − W₁)(2501 + 1.86 t₁)
Q_sensible = ṁ (1.006 + 1.86 W₂)(t₂ − t₁)
SHR        = Q_sensible / Q_total,   water = ṁ (W₂ − W₁) × 3600 kg/h

Limits. Loads are air-side; a cooling coil's refrigeration load is less by the enthalpy of its condensate, under 1 % in normal duty. A real coil does not follow a straight line, and its bypass factor depends on rows, fins and face velocity; the default of 0.15 is a typical value, not a rating. The pressure is the standard atmosphere for the altitude; weather moves it by a few per cent. States beyond the saturation curve are flagged as fog and have no wet bulb.

Sources. ASHRAE Handbook, Fundamentals (SI), 2017, chapter 1, Psychrometrics: eqs. 3, 5, 6, 20, 26, 30, 33 and 35, Tables 1 and 3, and its worked examples for heating, cooling and mixing, which the checks reproduce. Carrier Air Conditioning Company, Handbook of Air Conditioning System Design, McGraw-Hill, 1965, part 1, applied psychrometrics, for the apparatus dew point and bypass factor.

FAQ

Why does heating air lower its relative humidity?
Heating leaves the water content alone, but warmer air can hold far more vapour. The same 4.31 g/kg is 80 % of saturation at 5 °C and only 26 % at 22 °C.

What is the apparatus dew point?
It is the effective surface temperature of a wet cooling coil, a point on the saturation curve. Air that touches the fins leaves at the ADP; the bypass factor is the share that passes untouched.

Why is evaporative cooling free of energy but not of water?
The water's evaporation takes its heat from the air, so the enthalpy barely changes while the dry bulb falls. The cost is water: about 35 kg an hour for 5 000 m³/h of desert air in the example above.

Does the chart change with altitude?
Yes. At lower pressure the same vapour pressure gives a higher humidity ratio, so every humidity line moves up. Use the chart for your site's pressure, as the air density calculator does for density.

Where can I check a single number?
Use the dew point calculator for one state and the mixed air temperature calculator for a mix of outdoor and return air. Both share this simulator's equations.

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.