Pump and pipe system simulator

Change pump speed, pipe size and valve opening and watch the operating point move along the pump and system curves, with a cavitation check.

What the simulator shows

A centrifugal pump always runs where its curve crosses the system curve. The pump curve says how much head the pump gives at each flow; the system curve says how much head the pipework needs to pass that flow. Change anything on either side and the crossing, the operating point, moves.

The top chart draws both curves and marks the operating point, with the pump's efficiency as a dashed line. The lower chart compares the suction head the installation supplies, NPSH available, with the head the pump needs to avoid boiling at the impeller eye, NPSH required. Where the required line rises above the available line, the pump cavitates.

Things to try

  1. Throttle the valve. Close it from 100 % to 30 %. The system curve steepens, the flow falls and the head rises, and the pump moves left of its best efficiency point. Throttling works, but it burns energy in the valve.
  2. Slow the pump instead. Reopen the valve and reduce the speed to 80 %. The pump curve drops by the square of the speed ratio, to 64 % of its head. Compare the shaft power with the throttled case at the same flow: the slower pump uses far less.
  3. Make it cavitate. Set the liquid level to −5 m, a suction lift, and the water to 80 °C. The vapour pressure of hot water eats most of the atmospheric head, NPSH available drops below NPSH required and the warning appears.
  4. Try a smaller pipe. Halve the bore from 100 to 50 mm. Friction loss grows roughly with the fifth power of the bore, so the system curve rises steeply and the flow collapses.
  5. Lift too high. Raise the static lift above the shut-off head and the pump can no longer deliver at all.

The model behind it

System curve. The head needed at a flow Q is the static lift plus the pipe friction and the minor losses:

H_sys = H_s + (f · L/D + ΣK + K_valve) · v² / (2g),   v = Q / (π D² / 4)

The Darcy friction factor f comes from the Colebrook equation for the Reynolds number and the relative roughness, the same routine the pipe flow calculator uses. Water density and vapour pressure come from IAPWS-IF97, the formulation behind the steam tables; viscosity from the Vogel equation, within about 2 % from 0 to 100 °C. The valve is a linear valve with K = 0.2 fully open, rising as 1/x² as it closes.

Pump curve. A generic centrifugal pump: the head falls as a parabola from the shut-off head at zero flow to zero at the maximum flow. The best efficiency point sits at 60 % of the maximum flow with a peak efficiency of 78 %. The affinity laws scale the whole curve with speed: flow with the speed ratio n, head with n². NPSH required is 3 m at the best efficiency point, rising with the square of the flow ratio and with n². Real pumps follow their maker's tested curves, which differ in shape; the behaviour shown here is the behaviour of the class.

NPSH available is the absolute pressure on the liquid surface less the vapour pressure, as a head, plus the height of the liquid above the pump, less the suction line loss (friction plus an entrance loss of K = 0.5):

NPSH_a = (p_surface − p_vapour) / (ρ g) + z_s − h_f,suction

The simulator flags a margin under 0.5 m or 10 % of NPSH required, whichever is larger, as too thin; many pump standards ask for more on hot or volatile liquids.

FAQ

Why does closing a valve raise the pressure at the pump?
The valve adds resistance, so the system curve steepens and crosses the pump curve further left, where a centrifugal pump gives more head at less flow.

Is a variable speed drive always better than throttling?
For systems dominated by friction, yes: power falls with roughly the cube of the speed. Where most of the head is static lift, slowing the pump saves less, and below a certain speed it delivers nothing.

Why does hot water cavitate more easily?
Its vapour pressure is higher: about 2.3 kPa at 20 °C but 47 kPa at 80 °C, so less of the atmospheric pressure is left to keep it liquid at the impeller.

Can I use this to choose a pump?
Use it to understand the behaviour. To select a pump, draw your system curve with the total dynamic head calculator and lay it over the manufacturer's tested curves.

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.