Heat transfer and thermodynamics formulas
The formulas behind the 13 thermal calculators, on one page you can print or save as a PDF. Each block lists its variables and standard; the heading opens the calculator, with its assumptions and a worked example.
Boiler efficiency calculator (direct and indirect method)
Direct method:
η = ṁ_s × (h_s − h_fw) / (ṁ_f × CV)
h_s = h_f + x (h_g − h_f) for wet steam, or h(p, T) for superheated steam
Indirect method, flue gas loss by the Siegert formula (1. BImSchV), LHV basis:
q_A = (t_A − t_L) × (A2 / (21 − O2) + B) in %
η_LHV = (1 − q_A − q_rad) × (1 − r)
r = b' (h_f − h_fw) / [(h_s − h_fw) + b' (h_f − h_fw)], b' = b / (1 − b)
η_HHV = η_LHV × LHV / HHV
- ṁ_s, ṁ_f — steam and fuel mass flows; CV — gross (HHV) or net (LHV) calorific value
- h_s, h_f, h_fw — enthalpy of the steam, of saturated water at boiler pressure, and of the feedwater
- t_A, t_L — flue gas and combustion air temperatures in °C; O2 — oxygen in the dry flue gas, %
- A2, B — fuel constants: natural gas 0.66 and 0.009, heating oil 0.68 and 0.007, LPG 0.63 and 0.008
- q_rad — radiation and convection loss; b — blowdown as a share of the feedwater
Cargo tank heating time and steam
E = m c_p (T_target − T_initial)
Q_loss(T) = U_deck A_deck (T − T_air) + U_shell A_shell (T − T_sea) + U_bhd A_bhd (T − T_adjacent)
P = E/t + Q_loss(T_mean) (or t = E/(P − Q_loss(T_mean)))
ṁ_steam = P / h_fg, total steam = ṁ t, maintaining: ṁ = Q_loss(T_target)/h_fg
A_coil = P / (U_coil (T_sat − T_mean))
Saturated steam: 5 bar g 158.8 °C / 2 085 kJ/kg; 7 bar g 170.4 / 2 047; 10 bar g 184.1 / 1 999; 16 bar g 204.3 / 1 919. Typical U: shell to sea 6–8, deck to air 5–7, to adjacent empty tanks 2–4, insulated 0.5–1.5 W/(m²·K); coil 100–150 for crude, 60–90 for heavy oils.
Carnot efficiency and COP calculator
With temperatures in kelvin, T = °C + 273.15:
heat engine: η_C = 1 − T_c / T_h
heat pump: COP_h = T_h / (T_h − T_c)
refrigerator: COP_c = T_c / (T_h − T_c)
Real machines and energy balance:
COP_real = f × COP_Carnot (or η_real = f × η_C)
heat pump: Q_h = COP × W, Q_source = Q_h − W
engine: W = η × Q_in, Q_rejected = Q_in − W
- T_h, T_c — hot and cold reservoir temperatures
- f — second-law efficiency, the fraction of Carnot a real machine reaches
- W — electrical or mechanical work; Q — heat flow
Heat exchanger effectiveness–NTU calculator
Heat capacity rates, NTU and the duty:
C_h = ṁ_h c_p,h, C_c = ṁ_c c_p,c, C_r = C_min / C_max
NTU = U A / C_min
q = ε C_min (T_h,in − T_c,in)
T_h,out = T_h,in − q / C_h, T_c,out = T_c,in + q / C_c
Effectiveness (Incropera, Table 11.3):
Parallel: ε = [1 − exp(−NTU (1 + C_r))] / (1 + C_r)
Counterflow: ε = [1 − exp(−NTU (1 − C_r))] / [1 − C_r exp(−NTU (1 − C_r))], ε = NTU / (1 + NTU) at C_r = 1
One shell: ε₁ = 2 {1 + C_r + √(1 + C_r²) [1 + exp(−NTU₁ √(1 + C_r²))] / [1 − exp(−NTU₁ √(1 + C_r²))]}⁻¹
n shells: ε = [((1 − ε₁ C_r)/(1 − ε₁))ⁿ − 1] / [((1 − ε₁ C_r)/(1 − ε₁))ⁿ − C_r], NTU₁ = NTU / n
Cross, both unmixed: ε ≈ 1 − exp{(1/C_r) NTU^0.22 [exp(−C_r NTU^0.78) − 1]}
Cross, C_max mixed: ε = (1/C_r) {1 − exp[−C_r (1 − exp(−NTU))]}
Cross, C_min mixed: ε = 1 − exp{−(1/C_r) [1 − exp(−C_r NTU)]}
Any, C_r = 0: ε = 1 − exp(−NTU)
- ṁ — mass flow; c_p — specific heat; U — overall heat transfer coefficient; A — area
- C_min, C_max — the smaller and larger of C_h and C_c
- n — number of shell passes, each with 2, 4 or more tube passes
Heat exchanger LMTD
Heat duty (energy balance on either stream):
Q = ṁ_h c_p,h (T_h,in − T_h,out) = ṁ_c c_p,c (T_c,out − T_c,in)
- ṁ — mass flow, kg/s; c_p — specific heat, J/(kg·K); T — terminal temperatures, °C
Log-mean temperature difference:
LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂) (LMTD = ΔT₁ when ΔT₁ = ΔT₂)
Counterflow: ΔT₁ = T_h,in − T_c,out, ΔT₂ = T_h,out − T_c,in
Parallel: ΔT₁ = T_h,in − T_c,in, ΔT₂ = T_h,out − T_c,out
Correction factor for one shell pass, 2/4/6… tube passes (Bowman, Mueller and Nagle 1940), applied to the counterflow LMTD:
R = (T_h,in − T_h,out) / (T_c,out − T_c,in), P = (T_c,out − T_c,in) / (T_h,in − T_c,in)
F = √(R²+1) ln[(1−P)/(1−RP)] / { (R−1) ln[ (2 − P(R+1−√(R²+1))) / (2 − P(R+1+√(R²+1))) ] }
R = 1: F = P√2 / { (1−P) ln[ (2 − P(2−√2)) / (2 − P(2+√2)) ] }
Area and fouling:
1/U_service = 1/U_clean + R_f
A = Q / (U_service × F × LMTD)
- U — overall heat transfer coefficient, W/(m²·K); R_f — total fouling resistance, m²·K/W
Effectiveness, NTU and capacity ratio (from the temperatures alone):
ε = max(ΔT_h, ΔT_c) / (T_h,in − T_c,in)
NTU = U A / C_min = max(ΔT_h, ΔT_c) / (F × LMTD)
C_r = min(ΔT_h, ΔT_c) / max(ΔT_h, ΔT_c)
Heat transfer calculator: conduction, convection, radiation
Conduction through a plane wall (Fourier):
Q = k A (T₁ − T₂) / L
Convection from a surface (Newton):
Q = h A (T_s − T_∞)
Radiation from a surface to large surroundings (Stefan–Boltzmann):
Q = ε σ A (T_s⁴ − T_sur⁴), σ = 5.670 × 10⁻⁸ W/(m²·K⁴), T in kelvin
Thermal resistance and heat flux:
R = ΔT / Q, q″ = Q / A
- k — thermal conductivity, W/(m·K); L — wall thickness
- h — convection coefficient, W/(m²·K); ε — emissivity, 0 to 1
Ideal gas law (PV = nRT)
The ideal gas law:
P V = n R T
Rearranged for each unknown:
n = P V / (R T), P = n R T / V, V = n R T / P, T = P V / (n R)
Mass, density and the specific gas constant:
m = n M
ρ = P M / (R T)
R_specific = R / M
- P — absolute pressure, Pa
- V — volume, m³
- n — amount of gas, mol
- T — absolute temperature, K (T = t + 273.15 for t in °C)
- R — molar gas constant, 8.314 462 618 J/(mol·K), exact
- M — molar mass, kg/mol (air 0.028 965, N₂ 0.028 013, CO₂ 0.044 010)
Newton's law of cooling calculator
Temperature and time (Incropera eq. 5.6):
T(t) = T∞ + (T0 − T∞) × e^(−t/τ)
t = τ × ln[(T0 − T∞) / (T − T∞)]
Time constant of a lumped body, and the validity check (Incropera Section 5.2):
τ = ρ V c / (h A) = m c / (h A)
Bi = h L_c / k, L_c = V / A, lumped model valid for Bi < 0.1
Time constant from two readings, T0 at the start and T1 after time t1:
τ = t1 / ln[(T0 − T∞) / (T1 − T∞)]
- T0 — initial temperature; T∞ — surrounding fluid temperature; τ — time constant
- ρ, V, c, m — density, volume, specific heat and mass of the body
- h — heat transfer coefficient; A — surface area; k — conductivity of the body
- L_c — characteristic length: D/6 for a sphere
Pipe and tank insulation heat loss
Pipe (per metre of length), radii r₁ (inside wall), r₂ (outside wall), r₃, r₄ (insulation layers):
R_i = 1/(h_i 2π r₁), R_wall = ln(r₂/r₁)/(2π k_wall), R_1 = ln(r₃/r₂)/(2π k₁), R_2 = ln(r₄/r₃)/(2π k₂), R_o = 1/(h_o 2π r₄)
q = (T_in − T_amb) / ΣR [W/m], T_surface = T_amb + q R_o, T_interface = T_in − q (R_i + R_wall)
r_cr = k₁ / h_o (critical insulation radius)
Flat wall (per m²): R = 1/h_i + t_wall/k_wall + t₁/k₁ + t₂/k₂ + 1/h_o.
Totals: Q = q × length (or area); annual energy = Q × hours.
Typical values: mineral wool k 0.035–0.045 W/(m·K) at 50 °C (0.06–0.08 at 200 °C), calcium silicate 0.06, PUR 0.025; h_o 8–10 W/(m²·K) still air with radiation, 20–30 in wind; h_i 1 000+ for liquids and condensing steam, 20–50 for gases.
Specific heat calculator (Q = mcΔT)
Sensible heat and heating time:
Q = m × c × (T₂ − T₁)
t = Q / (P × η)
Solved for the other quantities:
T₂ = T₁ + Q / (m c), m = Q / (c ΔT), c = Q / (m ΔT)
- Q — heat, J; 1 kWh = 3.6 MJ; 1 Btu = 1 055 J
- m — mass, kg; c — specific heat, J/(kg·K)
- P — heater power, W; η — fraction of it that reaches the material
Steam table calculator (IAPWS-IF97)
Saturation line (IF97 region 4): the saturation pressure p_s(T) and its inverse T_s(p) are closed-form equations.
Single-phase properties come from the dimensionless Gibbs free energy γ(π, τ):
region 1 (water): π = p / 16.53 MPa, τ = 1 386 K / T
region 2 (steam): π = p / 1 MPa, τ = 540 K / T
v = R T π γ_π / p, h = R T τ γ_τ, s = R (τ γ_τ − γ), u = h − p v
Wet steam with dryness fraction x:
h = h_f + x h_fg, s = s_f + x (s_g − s_f), v = v_f + x (v_g − v_f)
- R = 0.461526 kJ/(kg·K), the gas constant of water in IF97
- h_f, h_g — saturated liquid and vapour enthalpy; h_fg = h_g − h_f is the latent heat
- Enthalpy and entropy are zero for liquid water at the triple point, as in published tables
Thermal expansion and restraint stress
Linear expansion of a solid:
ΔL = α L ΔT free expansion
ε_T = α ΔT thermal strain
σ = E (α ΔT − δ / L) stress when the member may move only δ (δ = 0 fully restrained; σ = 0 when δ ≥ |ΔL|)
F = σ A force on the anchors
E α stress per kelvin for full restraint
Sign: heating a restrained member gives compression (positive here); cooling gives tension (negative).
Volumetric expansion of a liquid:
ΔV = β V ΔT unconfined (vented tank)
Δp = K (β − 3 α_pipe) ΔT blocked in, completely filled, rigid walls (3 α_pipe credits the container's own volume growth)
V_relief = (β − 3 α_pipe) V ΔT liquid that must escape to hold the pressure
- α — linear expansion coefficient (steel 12, stainless 304 17.3, aluminium 23.1, copper 16.5, PVC 70, HDPE 150 µm/m·K)
- β — volumetric expansion coefficient of the liquid (water 20 °C 0.21, sea water 0.25, diesel 0.83, HFO 0.68, lube oil 0.70 ×10⁻³/K)
- K — bulk modulus of the liquid (water 2.2, oils 1.5–1.6 GPa); E — Young's modulus; A — cross-section area
Water heating time calculator (tank, element, gas or heat pump)
Heat into the water and useful heater output:
Q = m × c × (T1 − T0), m = ρ V
P_heat = η × P (element, burner) or COP × P (heat pump)
Heating time without and with standing loss:
t = Q / P_heat (UA = 0)
t = τ × ln[(T_eq − T0) / (T_eq − T1)]
τ = m c / UA, T_eq = T_room + P_heat / UA
Energy drawn and recovery rate:
E = P × t
Recovery = P_heat / (ρ c ΔT_rise)
- V — tank volume; ρ = 999 kg/m³; c = 4 186 J/(kg·K), or 1 Btu/(lb·°F)
- T0, T1 — starting and target water temperatures; T_room — air around the tank
- η — element or burner efficiency; COP — heat pump coefficient of performance
- UA — standing loss coefficient of the tank in W/K; τ — its time constant
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.