Introduction
Boiler efficiency is the share of the fuel's heat that ends up in the steam. The direct method divides the heat gained by the water by the heat in the fuel burned. A gas-fired boiler making 5 000 kg/h of saturated steam at 10 bar g from 80 °C feedwater, on 290 kg/h of natural gas, is 80.7 % efficient on the gross (HHV) basis and 89.4 % on the net (LHV) basis.
This calculator works out the efficiency both ways. The direct method uses steam and fuel flows, with steam and feedwater enthalpies from the IAPWS-IF97 steam tables. The indirect method subtracts the flue gas, radiation and blowdown losses from 100 %. A fuel table gives the gross and net heating values. It is for boiler operators, energy auditors and plant engineers.
Formulas
Direct method:
η = ṁ_s × (h_s − h_fw) / (ṁ_f × CV)
h_s = h_f + x (h_g − h_f) for wet steam, or h(p, T) for superheated steam
Indirect method, flue gas loss by the Siegert formula (1. BImSchV), LHV basis:
q_A = (t_A − t_L) × (A2 / (21 − O2) + B) in %
η_LHV = (1 − q_A − q_rad) × (1 − r)
r = b' (h_f − h_fw) / [(h_s − h_fw) + b' (h_f − h_fw)], b' = b / (1 − b)
η_HHV = η_LHV × LHV / HHV
ṁ_s, ṁ_f — steam and fuel mass flows; CV — gross (HHV) or net (LHV) calorific value
h_s, h_f, h_fw — enthalpy of the steam, of saturated water at boiler pressure, and of the feedwater
t_A, t_L — flue gas and combustion air temperatures in °C; O2 — oxygen in the dry flue gas, %
A2, B — fuel constants: natural gas 0.66 and 0.009, heating oil 0.68 and 0.007, LPG 0.63 and 0.008
q_rad — radiation and convection loss; b — blowdown as a share of the feedwater
Assumptions and limitations
The heating values are the GREET values published by Oak Ridge National Laboratory. Coal and wood vary widely, so use the value from a fuel analysis when you have one.
The direct method counts only the steam as output, so all losses are inside the result. Its accuracy depends on the flow meters, and a 2 % error in fuel flow gives a 2 % error in efficiency.
The Siegert formula covers oil and gas firing with complete combustion. It ignores unburnt fuel (CO) and does not apply once the flue gas condenses, below about 60 °C.
US practice and ASME PTC 4 use the gross (HHV) basis; much of Europe and EN 12952-15 use the net (LHV) basis. Always state which one.
Worked example
The Bureau of Energy Efficiency (India) gives this direct-method example. A coal-fired boiler makes 8 t/h of dry saturated steam at 10 kg/cm² g from feedwater at 85 °C. It burns 1.6 t/h of coal with a gross calorific value of 4 000 kcal/kg.
Absolute pressure: 10 kg/cm² g is 9.81 bar g, or 10.82 bar abs. Saturation is 183.3 °C.
BEE prints 72.5 %, using 665 kcal/kg for the steam. For the indirect method on a gas boiler, a flue gas at 180 °C with 3 % O2 and 20 °C air loses 7.31 % by Siegert. With 1 % radiation and 3 % blowdown at 10 bar g, the efficiency is 91.2 % net, or 82.3 % gross.
FAQ
How do I calculate boiler efficiency?
Divide the heat added to the water, steam flow times the enthalpy rise from feedwater to steam, by the fuel flow times its calorific value. That is the direct method.
What is the difference between the direct and indirect methods?
The direct method needs accurate steam and fuel flows. The indirect method needs only a flue gas analysis and estimates of the other losses, and it shows where the heat goes.
What is the difference between HHV and LHV efficiency?
The gross (HHV) basis counts the latent heat of the water vapour in the flue gas as a loss; the net (LHV) basis does not. For natural gas LHV/HHV is 0.903, so 90 % net is 81.2 % gross.
How does excess air affect efficiency?
More oxygen means more flue gas carrying heat up the stack. At 180 °C flue gas, natural gas loses 7.31 % with 3 % O2 and 8.48 % with 6 % O2.
How much does a lower flue gas temperature save?
At 3 % O2 on natural gas, every 20 K lower flue gas temperature cuts the loss by about 0.9 points. An economiser that cools the gas from 180 to 160 °C raises the net efficiency from 91.2 to 92.1 %.
Can boiler efficiency exceed 100 %?
Only on the net (LHV) basis, in a condensing boiler that recovers the latent heat of the water vapour. On the gross basis it always stays below 100 %.
Before every release the calculator must reproduce each case below. The note under each case says where the expected answer comes from: a standard, a textbook, a published table, or a hand calculation shown in full.
BEE example: 8 t/h steam at 10 kg/cm² g, feedwater 85 °C, 1.6 t/h coal of GCV 4 000 kcal/kg gives 72.5 %Bureau of Energy Efficiency, Book 4 Ch. 1 Boilers, direct method example (72.5 % with h_s = 665 kcal/kg)
Steam at 10 bar absolute: dry saturated h_g = 2 777.1 kJ/kg, wet x = 0.9 gives h_f + 0.9 h_fg = 2 575.7 kJ/kg; 250 °C superheated 2 943.1 kJ/kgIAPWS-IF97 steam tables (saturation at 1 MPa: h_f 762.7, h_g 2 777.1 kJ/kg; 1 MPa, 250 °C: 2 943.1 kJ/kg; Çengel & Boles Tables A-5 and A-6)
Siegert: natural gas, flue 180 °C, air 20 °C, 3 % O2 gives 7.31 % loss; heating oil 200 °C, 4 % O2 gives 8.46 %1. BImSchV Anlage 2 Nr. 3.4: q_A = (t_A − t_L)(A2/(21 − O2) + B), gas 0.66/0.009, oil 0.68/0.007; hand calculation
Indirect without blowdown: η_LHV = 1 − q_A − q_rad and η_HHV = η_LHV × LHV/HHV (natural gas 47.141 / 52.225 MJ/kg)Loss balance; GREET heating values (ORNL Biomass Energy Data Book, Appendix A)
Blowdown share: 5 % blowdown at 10 bar g, feedwater 80 °C takes (0.05/0.95)(h_f − h_fw) of the heat absorbedEnergy balance of the boiler water (blowdown leaves as saturated liquid); hand calculation
Invalid input: Siegert table for coal, feedwater above saturation, superheat below saturation and LHV above HHV are rejectedBehaviour check: warnings and rejected inputs
Worked example of the article: the calculator reproduces 2 780 kJ/kg, 356.7 kJ/kg, 5 385 kW, 7 443 kW, 72.3 % to the digits printedThe worked example on this page, to the digits printed
Assumptions and sources
Assumptions and limits
Steam and feedwater enthalpies come from IAPWS-IF97 at the boiler pressure (atmospheric pressure 1.01325 bar added to the gauge pressure); the feedwater is compressed liquid at that pressure.
The direct method counts only the heat in the steam as output, so blowdown, flue gas and casing losses all appear as losses. Fuel heating values are the GREET values (ORNL Biomass Energy Data Book); enter measured values from a fuel analysis where available, especially for coal and wood.
The Siegert formula gives the sensible flue gas loss on the lower heating value basis for oil and gas firing (1. BImSchV); it assumes complete combustion and a flue gas above its dew point, and does not include unburnt fuel (CO) losses.
Efficiency on the HHV basis is the LHV efficiency times LHV/HHV: the latent heat of the water vapour in the flue gas is then a loss. US practice and ASME PTC 4 use HHV; European practice and EN 12952-15 often use LHV.
The radiation and convection loss is entered as a percentage of the fuel input at full load: about 0.5 to 2 %, higher at part load. Blowdown leaves as saturated water at the boiler pressure.
Sources
Bureau of Energy Efficiency (India), Energy Performance Assessment for Equipment and Utility Systems, Book 4 Ch. 1 Boilers: direct and indirect methods (worked direct-method example)
IAPWS R7-97(2012) Revised Release on the IAPWS Industrial Formulation 1997 (regions 1, 2 and 4) for steam and feedwater enthalpy
Erste Verordnung zur Durchführung des Bundes-Immissionsschutzgesetzes (1. BImSchV, 2010), Anlage 2 Nr. 3.4: Siegert formula q_A = (t_A − t_L)(A2/(21 − O2) + B) with A2 and B for heating oil, natural gas and LPG