Heat transfer and thermodynamics glossary
24 terms from the thermal calculators, each in two or three sentences with its symbol, its unit and a typical value. Every entry links to the calculators that use it; the formula sheet has the equations.
-
Biot numberBidimensionless
Also called Lumped capacitance
Ratio of the internal conduction resistance of a body to its surface convection resistance, Bi = h L_c/k, where L_c is volume divided by surface area. Below about 0.1 the inside stays at a nearly uniform temperature and the lumped-capacitance method is accurate within about 5 %. Larger values need a transient conduction solution.
Newton's law of cooling calculator, Heat transfer calculator: conduction, convection, radiation
-
Boiler efficiencyηbdimensionless
Also called Fuel-to-steam efficiency
Ratio of the heat taken up by the steam or hot water to the heat in the fuel fired. Non-condensing packaged boilers reach about 85 to 90 % on net calorific value, and condensing boilers can exceed 100 % on that basis, so the basis must always be stated. The direct method divides output by input; the indirect method subtracts the losses from 100 %.
Boiler efficiency calculator (direct and indirect method), Cargo tank heating time and steam
-
Carnot efficiencyηCdimensionless
Also called Carnot cycle, Carnot limit
Highest possible efficiency of a heat engine working between two temperatures, 1 − T_cold/T_hot with absolute temperatures. An engine between 500 °C and 30 °C cannot exceed about 61 %. Real steam and diesel plants reach roughly half to two thirds of their Carnot limit.
-
Coefficient of performanceCOPdimensionless
Also called COP, SCOP, Seasonal COP
Ratio of the useful heat delivered by a heat pump, or removed by a refrigerator, to the work or electricity put in. Air-source heat pumps typically give 2.5 to 4, and the ideal Carnot heating value is T_hot/(T_hot − T_cold) in kelvin. It falls as the temperature lift grows, so low flow temperatures raise it.
Carnot efficiency and COP calculator, Water heating time calculator (tank, element, gas or heat pump), Heat pump vs gas boiler running cost calculator
-
Coefficient of thermal expansionα1/K (µm/(m·K))
Also called Thermal expansion coefficient, CTE, Linear expansion coefficient
Fractional change in length per kelvin of temperature change, so that ΔL = α L ΔT. Carbon steel is about 12 µm/(m·K), austenitic stainless steel 16 to 17, aluminium 23 and HDPE about 150. A fully restrained steel bar heated by 1 K gains about 2.4 MPa of compressive stress.
Thermal expansion and restraint stress, Material properties table (steel, aluminium, plastics)
-
Convective heat transfer coefficienthW/(m²·K)
Also called Film coefficient, Heat transfer coefficient, Convection coefficient
Heat flow per unit area per kelvin of difference between a surface and the fluid moving past it, q = h ΔT. Still air gives about 5 to 10 W/(m²·K), forced air 10 to 200, flowing water 500 to 10 000 and condensing steam 5 000 to 100 000. It depends on the flow as much as on the fluid.
Heat transfer calculator: conduction, convection, radiation, Pipe and tank insulation heat loss, Newton's law of cooling calculator
-
Dryness fractionxdimensionless
Also called Steam quality, Quality
Mass fraction of vapour in a wet steam mixture, from 0 for saturated water to 1 for dry saturated steam, so that h = h_f + x h_fg. Boilers without superheaters typically deliver steam at 0.95 to 0.98. Wet steam carries less heat to heating coils and erodes turbine blades.
Steam table calculator (IAPWS-IF97), Boiler efficiency calculator (direct and indirect method)
-
Emissivityεdimensionless
Ratio of the thermal radiation a surface emits to that of a black body at the same temperature, between 0 and 1. Polished aluminium is about 0.05, oxidised steel about 0.8 and most paints, brick and water 0.9 to 0.95. Surface finish matters more than the base material.
Heat transfer calculator: conduction, convection, radiation, Pipe and tank insulation heat loss
-
Fouling factorRfm²·K/W
Also called Fouling resistance
Extra thermal resistance of the deposits that build up on heat exchanger surfaces in service, added in series to the clean resistance 1/U. TEMA tables give about 0.00009 m²·K/W for sea water below 50 °C, 0.00018 for treated cooling tower water and 0.0009 for fuel oil. Overstating it oversizes the exchanger.
Heat exchanger LMTD, Heat exchanger effectiveness–NTU calculator
-
Heat exchanger effectivenessεdimensionless
Also called Effectiveness, Thermal effectiveness
Ratio of the actual heat transfer to the maximum possible, C_min (T_h,in − T_c,in), where C_min is the smaller of the two heat capacity rates. It lies between 0 and 1, and with NTU and the capacity ratio it fixes the outlet temperatures. Counterflow gives the highest effectiveness for a given size.
Heat exchanger effectiveness–NTU calculator, Heat exchanger LMTD
-
Ideal gas lawnone
Also called PV = nRT, Perfect gas law, Specific gas constant
Equation of state pV = nRT, or pV = mRT with the specific gas constant, relating the pressure, volume, temperature and amount of a gas. The molar constant is 8.314 J/(mol·K), and dry air has 287 J/(kg·K). It is accurate within a few per cent for air and common gases near ambient conditions; high-pressure gases need a compressibility factor.
Ideal gas law (PV = nRT), Air density calculator, Compressed air calculator: leaks, receiver, pipe drop and power, Gas compressibility factor Z calculator (natural gas and pure gases)
-
Log mean temperature differenceΔTlmK
Also called LMTD
Effective mean temperature difference driving heat transfer between two streams, (ΔT1 − ΔT2)/ln(ΔT1/ΔT2), with ΔT1 and ΔT2 the differences at each end. The duty is then Q = U A F ΔT_lm. End differences of 40 K and 10 K give about 21.6 K, well below the arithmetic mean of 25 K.
Heat exchanger LMTD, Heat exchanger effectiveness–NTU calculator, Cargo tank heating time and steam
-
Newton’s law of coolingnone
Also called Cooling time constant
Statement that the rate of heat loss from a body is proportional to its temperature difference from the surroundings. For a body of uniform temperature it gives exponential decay, T − T∞ = (T0 − T∞) e^(−t/τ), with time constant τ = ρVc/(hA). After one time constant about 63 % of the initial difference has gone.
Newton's law of cooling calculator, Heat transfer calculator: conduction, convection, radiation
-
Number of transfer unitsNTUdimensionless
Also called NTU, ε-NTU method, Effectiveness-NTU
Measure of heat exchanger size, UA divided by the smaller heat capacity rate C_min. Values of 1 to 3 cover most practical units; beyond about 3 the effectiveness rises only slowly. With effectiveness it rates an exchanger when the outlet temperatures are unknown, without the iteration the LMTD method needs.
Heat exchanger effectiveness–NTU calculator, Heat exchanger LMTD
-
Overall heat transfer coefficientUW/(m²·K)
Also called UA, Overall U
Heat flow per unit area per kelvin of mean temperature difference through all the resistances in series between two fluids: both films, the wall and any fouling. Water-to-water shell-and-tube units typically give 800 to 1 500 W/(m²·K), plate units 3 000 to 6 000 and gas-to-gas units 10 to 50. It is quoted on a stated area, usually the outside.
Heat exchanger LMTD, Heat exchanger effectiveness–NTU calculator, Pipe and tank insulation heat loss, Cargo tank heating time and steam
-
Rankine cyclenone
Also called Steam cycle
Steam power cycle of four steps: a pump raises the feedwater pressure, a boiler evaporates and usually superheats it, a turbine expands the steam and a condenser returns it to liquid. Simple plants reach 30 to 40 % thermal efficiency, and reheat with feedwater heating takes large units to about 45 %. Steam table enthalpies give the work and heat of each step.
Steam table calculator (IAPWS-IF97), Boiler efficiency calculator (direct and indirect method), Carnot efficiency and COP calculator
-
Saturation temperatureTsat°C (K)
Also called Boiling point, Saturation pressure
Temperature at which a liquid and its vapour coexist at a given pressure, the boiling point at that pressure. Water boils at 100 °C at 1.013 bar absolute, 120.2 °C at 2 bar and 184.1 °C at 11 bar. Steam supply is often quoted as gauge pressure, so add atmospheric pressure before looking it up.
Steam table calculator (IAPWS-IF97), Cargo tank heating time and steam, Pump NPSH and suction lift
-
Specific enthalpyhkJ/kg (Btu/lb)
Also called Enthalpy
Internal energy plus the product of pressure and specific volume, per unit mass, h = u + pv; its change in steady flow gives the heat added or work done. On the IAPWS scale, with zero near liquid water at 0.01 °C, saturated water at 100 °C has 419 kJ/kg and dry saturated steam at 100 °C 2 676 kJ/kg.
Steam table calculator (IAPWS-IF97), Boiler efficiency calculator (direct and indirect method), Latent and sensible heat calculator (air and water)
-
Specific entropyskJ/(kg·K)
Also called Entropy, Isentropic
Property whose change per unit mass equals the reversible heat added divided by absolute temperature. An ideal turbine or pump keeps it constant, so isentropic efficiency compares a real machine with that path. Dry saturated steam at 10 bar absolute has about 6.59 kJ/(kg·K).
Steam table calculator (IAPWS-IF97), Carnot efficiency and COP calculator
-
Specific heat capacitycpJ/(kg·K)
Also called Specific heat, c_p, c_v
Heat needed to raise the temperature of one kilogram of a substance by one kelvin, so that Q = m c ΔT. Water has about 4.18 kJ/(kg·K), air 1.005, steel 0.46 to 0.50 and fuel oils around 1.8 to 2.1. Gases have two values, at constant pressure and at constant volume.
Specific heat calculator (Q = mcΔT), Cargo tank heating time and steam, Heat exchanger LMTD, Water heating time calculator (tank, element, gas or heat pump)
-
Stefan–Boltzmann lawnone
Also called Thermal radiation, Stefan–Boltzmann constant
Law that a surface radiates heat in proportion to the fourth power of its absolute temperature, q = εσT⁴, with σ = 5.67 × 10⁻⁸ W/(m²·K⁴). Net exchange with large surroundings is εσA(T_s⁴ − T_sur⁴). Because of the fourth power, radiation dominates the loss from hot surfaces such as exhaust pipes and furnace walls.
Heat transfer calculator: conduction, convection, radiation, Pipe and tank insulation heat loss
-
Superheated steamnone
Also called Superheat, Degree of superheat
Steam heated above the saturation temperature for its pressure, so that it holds no liquid; the excess is the degree of superheat. Power turbines usually take 150 K or more of superheat, while process heating prefers saturated steam, which gives up its heat at a fixed temperature as it condenses. Its properties depend on both pressure and temperature.
Steam table calculator (IAPWS-IF97), Boiler efficiency calculator (direct and indirect method)
-
Temperature difference correction factorFdimensionless
Also called LMTD correction factor, F factor
Multiplier applied to the counterflow log mean temperature difference to account for multipass or crossflow arrangements, such as a shell-and-tube unit with two tube passes. It equals 1 for pure counterflow. Designs keep it above about 0.8, as lower values sit on the steep part of the curve and signal a poor arrangement.
-
Thermal conductivitykW/(m·K)
Also called λ, k-value, Fourier’s law
Rate of heat conduction through a material per unit area per unit temperature gradient, from Fourier’s law q = −k dT/dx. Copper has about 400 W/(m·K), carbon steel about 50, stainless steel 15, water 0.6 and mineral wool insulation 0.035 to 0.045. It varies with temperature, so insulation is rated at its mean temperature.
Heat transfer calculator: conduction, convection, radiation, Pipe and tank insulation heat loss, Material properties table (steel, aluminium, plastics)
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.