HVAC glossary
18 terms from the hvac and building services calculators, each in two or three sentences with its symbol, its unit and a typical value. Every entry links to the calculators that use it; the formula sheet has the equations.
-
Air changes per hourACH1/h
Also called ACH, Air change rate, CFM per room
Number of times the air volume of a room is replaced in one hour, the airflow in m³/h divided by the room volume. Dwellings are commonly ventilated at 0.35 to 0.5, offices at about 4 to 6 and laboratories at 6 to 12. It assumes the supply air mixes fully, so poor air distribution gives less effective ventilation.
Air changes per hour (ACH) and CFM calculator, Building heat loss calculator (U-values), Enclosed space purge time, Engine-room ventilation (ISO 8861)
-
British thermal unitBtuJ (Btu/h for power)
Also called BTU, Btu/h, BTU per hour
Heat needed to raise one pound of water by one degree Fahrenheit, about 1 055 J. Heating and cooling equipment is rated in Btu per hour: 1 000 Btu/h is 0.293 kW, so a 12 000 Btu/h room air conditioner gives about 3.5 kW of cooling.
BTU calculator: AC size for a room, Heat pump vs gas boiler running cost calculator, Engineering unit converter
-
Cooling loadQcW (Btu/h, tons)
Also called Heat gain, Cooling capacity, AC size
Rate at which heat must be removed from a space to hold its design temperature and humidity: the sensible and latent gains from sun, conduction, people, lights, equipment and outdoor air. Rule-of-thumb figures for offices are about 80 to 120 W per m² of floor. A unit sized well above the load short-cycles and dehumidifies poorly.
BTU calculator: AC size for a room, Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air)
-
Dew pointTd°C
Also called Dew point temperature, Frost point
Temperature to which air must be cooled at constant pressure and moisture content for its water vapour to start condensing. Air at 20 °C and 50 % relative humidity has a dew point of about 9.3 °C. Any surface colder than the dew point gathers condensation, which is why cold pipes are insulated with a vapour barrier.
Dew point calculator, Cargo ventilation and dew point, Latent and sensible heat calculator (air and water)
-
Dry-bulb temperatureTdb°C
Also called Dry bulb, DB
Air temperature read by an ordinary thermometer shielded from radiation and moisture, the horizontal axis of the psychrometric chart. Design conditions are quoted as a dry-bulb with a coincident wet-bulb, for example 35 °C and 24 °C for summer cooling in a hot climate. On its own it says nothing about humidity.
Dew point calculator, Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air), Cargo ventilation and dew point
-
Equal friction methodnone
Also called Friction rate, Constant friction method, Ductulator
Duct sizing method that gives every section the same pressure loss per unit length. Low-pressure systems commonly use about 0.65 to 1 Pa/m (0.08 to 0.12 in. w.c. per 100 ft), which keeps velocities and noise moderate. Branches to near and remote outlets still need dampers to balance, as their total lengths differ.
-
Equivalent duct diameterDem (in)
Also called Equivalent diameter, Huebscher equation, Rectangular to round duct
Diameter of a round duct that carries the same airflow with the same friction loss per length as a given rectangular duct, D_e = 1.30 (ab)^0.625/(a + b)^0.25 after Huebscher. A 12 × 12 in duct equals a 13.1 in round one. It differs from the hydraulic diameter, which matches friction at equal velocity rather than equal flow.
-
Heating degree daysHDDK·day (°F·day)
Also called HDD, Degree days
Sum over a year of the daily amounts by which the mean outdoor temperature falls below a base temperature, commonly 15.5 °C, 18 °C or 65 °F. Annual heat use is roughly 24 × UA × HDD in watt-hours. London has roughly 1 900 to 2 300 K·day on a 15.5 °C base, and Chicago about 6 000 to 6 500 °F·day on a 65 °F base.
Building heat loss calculator (U-values), Heat pump vs gas boiler running cost calculator
-
Humidity ratioWkg/kg dry air (g/kg)
Also called Moisture content, Mixing ratio
Mass of water vapour per unit mass of dry air, W = 0.622 p_w/(p − p_w) with p_w the vapour partial pressure. Air at 20 °C and 50 % relative humidity holds about 7.3 g/kg, and saturated air at 30 °C about 27 g/kg. It stays constant when air is heated or cooled without condensation, so it tracks latent load.
Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air), Dew point calculator, Air density calculator
-
Latent heathfgkJ/kg (load in W)
Also called Latent heat of vaporisation, Latent heat of fusion, Latent load
Heat absorbed or released when a substance changes phase at constant temperature, such as water vapour condensing on a cooling coil. Water needs 2 257 kJ/kg to evaporate at 100 °C, about 2 450 kJ/kg near room temperature, and 334 kJ/kg to melt. An air-conditioning latent load is the moisture removed times about 2 450 kJ/kg.
Latent and sensible heat calculator (air and water), Steam table calculator (IAPWS-IF97), Cargo tank heating time and steam
-
Outdoor air fractionXoadimensionless
Also called Outside air fraction, OA fraction, Mixed air temperature
Share of the supply airflow drawn from outdoors rather than recirculated from the return. From measured temperatures it is (T_return − T_mixed)/(T_return − T_outdoor), as the mixed air temperature is close to the flow-weighted average of the two streams. Ventilation codes such as ASHRAE 62.1 set the minimum, and economisers raise it to 100 % in mild weather.
Mixed air temperature calculator (outdoor and return air), Air changes per hour (ACH) and CFM calculator
-
Psychrometric chartnone
Also called Psychrometrics, Psych chart
Chart of the properties of moist air at one pressure, with dry-bulb temperature along the bottom and humidity ratio up the side, crossed by lines of relative humidity, wet-bulb temperature, enthalpy and specific volume. Any two known properties fix the state. Heating, cooling and dehumidifying trace simple paths on it, and mixing two airstreams lies on the straight line between them.
Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air), Dew point calculator, Air density calculator
-
R-valueRm²·K/W (ft²·°F·h/Btu)
Also called Thermal resistance, RSI
Thermal resistance of a layer per unit area, its thickness divided by its thermal conductivity. Resistances in series add, and the U-value is the reciprocal of the total including surface films. 100 mm of mineral wool at 0.04 W/(m·K) gives 2.5 m²·K/W, about R-14 in US units, since 1 m²·K/W equals 5.68 ft²·°F·h/Btu.
Building heat loss calculator (U-values), Pipe and tank insulation heat loss
-
Relative humidityRH%
Also called RH, Humidity
Ratio of the partial pressure of water vapour in air to the saturation pressure at the same temperature, in per cent. Indoor comfort is usually kept between about 30 and 60 %. Heating air lowers its relative humidity without changing its moisture content, which is why heated winter air feels dry.
Dew point calculator, Air density calculator, Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air), Cargo ventilation and dew point
-
Sensible heatQsW (Btu/h)
Also called Sensible heat ratio, SHR, Sensible load
Heat that changes the temperature of air or a material without a change of phase. For air at standard density, Q_s is about 1.2 W per L/s per kelvin, or 1.08 × cfm × ΔT in Btu/h with ΔT in °F. The sensible heat ratio, sensible over total load, is typically 0.7 to 0.85 for offices and homes.
Latent and sensible heat calculator (air and water), BTU calculator: AC size for a room, Building heat loss calculator (U-values)
-
Ton of refrigerationTRkW (12 000 Btu/h)
Also called Refrigeration ton, RT, Tons of cooling
Unit of cooling capacity equal to 12 000 Btu/h or 3.517 kW, originally the rate of melting one short ton of ice in 24 hours. Homes in hot climates often need about one ton per 35 to 55 m² of floor. Chiller performance is often quoted in kW of electricity per ton.
-
U-valueUW/(m²·K) (Btu/(h·ft²·°F))
Also called Thermal transmittance, U-factor
Heat flow through one square metre of a building element for each kelvin of difference between inside and outside air, the reciprocal of its total thermal resistance including surface films. New walls in northern Europe reach 0.15 to 0.3 W/(m²·K), low-e double glazing 1.1 to 1.6 and triple glazing 0.5 to 1.0. Fabric heat loss is U × A × ΔT.
Building heat loss calculator (U-values), Cargo tank heating time and steam
-
Wet-bulb temperatureTwb°C
Also called Wet bulb, WB
Temperature shown by a thermometer whose bulb is covered by a wet wick in moving air, lowered by evaporation. It lies between the dew point and the dry-bulb temperature and equals both at saturation. With the dry-bulb it fixes the humidity, and it sets the lowest water temperature a cooling tower can reach.
Latent and sensible heat calculator (air and water), Mixed air temperature calculator (outdoor and return air), Cargo ventilation and dew point