Introduction
Building codes limit how far beams, joists and roof members may sag, so that ceilings do not crack and floors do not feel soft. The limit is a fraction of the span, written L/360 or L/240. A floor joist spanning 14 ft may deflect 168 / 360 = 0.47 in under live load and 168 / 240 = 0.70 in under dead plus live load, by IBC Table 1604.3.
This calculator lists every deflection limit for a member under the IBC, the UK National Annex for steel, Eurocode 2 for concrete or Eurocode 5 for timber. It handles cantilevers and compares your computed deflections with each limit. It is for engineers, builders and students checking a beam or joist after computing its deflection.
Formulas
Allowable deflection and utilisation:
Δ_allow = l / n
utilisation = Δ_actual / Δ_allow
span ratio = l / Δ_actual
IBC Table 1604.3, main rows (live L, snow or wind S or W, dead plus live D + L):
floor members L/360 — L/240
roof, plaster or stucco ceiling L/360 L/360 L/240
roof, non-plaster ceiling L/240 L/240 L/180
roof, no ceiling L/180 L/180 L/120
l — span; for IBC cantilevers, twice the cantilever length
UK NA steel: span/360 with brittle finishes, span/200 for other beams, length/180 for cantilevers
EN 1992 concrete: span/250 for sag, span/500 after the finishes are built
EN 1995 timber: w_inst l/300 to l/500, w_net,fin l/250 to l/350, w_fin l/150 to l/300
Assumptions and limitations
Each limit applies to the deflection under the loads its column names. Compute those deflections first, for example with the beam deflection calculator.
Under the IBC, the D + L check may use half the dead load for dry wood, and zero dead load for steel members. Wind for these checks may be taken as 0.42 times the component and cladding loads.
The UK steel limits apply to variable actions alone. Eurocode 5 gives ranges, and the national annex picks the value; choose the lenient or strict end.
Deflection limits do not ensure a floor will not bounce or a flat roof will not pond. Those need vibration and ponding checks.
Worked example
A floor joist spans 14 ft. Its computed deflections are 0.35 in under live load and 0.55 in under dead plus live load. Check it to IBC Table 1604.3.
Span in inches: 14 × 12 = 168 in.
Live-load limit: 168 / 360 = 0.47 in. The joist uses 0.35 / 0.467 = 75.0 % of it.
Total-load limit: 168 / 240 = 0.70 in. The joist uses 0.55 / 0.70 = 78.6 % of it.
The live-load deflection is span / 480, better than the required span / 360.
The joist passes both checks. As a 6 ft roof cantilever with no ceiling, the same member would be checked over 12 ft, at L/180 = 0.80 in.
FAQ
What does L/360 mean?
The deflection may not exceed the span divided by 360. For a 20 ft span that is 240 / 360 = 0.67 in.
When is L/240 used instead of L/360?
L/360 limits live-load deflection of floors and of roofs with plaster ceilings. L/240 limits total dead plus live deflection of floors, and live-load deflection of roofs with other ceilings.
How are cantilevers treated?
The IBC checks a cantilever as if its span were twice its length. The UK steel annex uses length/180, and Eurocode 5 has its own cantilever limits.
Is L/360 enough for tile or stone floors?
Not always. Tile and stone floors often need a stiffer limit than the code minimum. Check the setting standard and the finish manufacturer's requirement.
Do deflection limits include creep?
The IBC D + L limit applies to the long-term deflection. For wood it may use half the dead load when the wood is dry at installation. Eurocodes 2 and 5 include creep in their final deflections.
Are deflection limits a safety requirement?
They are serviceability limits. Exceeding them cracks finishes and alarms occupants, but strength is checked separately.
Before every release the calculator must reproduce each case below. The note under each case says where the expected answer comes from: a standard, a textbook, a published table, or a hand calculation shown in full.
IBC Table 1604.3: floor L/360 and D+L/240; roof with plaster ceiling 360/360/240, non-plaster 240/240/180, no ceiling 180/180/120; walls 360/240/120; farm 180, greenhouse 120IBC 2021 Table 1604.3 Deflection Limits
Worked example: 14 ft floor joist, L/360 = 0.467 in and L/240 = 0.700 in; 0.35 in and 0.55 in use 75.0 % and 78.6 %, span/480Hand calculation: 14 × 12 = 168 in; 168/360, 168/240
IBC cantilever: a 6 ft roof cantilever with no ceiling uses l = 12 ft, so L/180 = 0.80 in; walls cannot be cantileversIBC Table 1604.3 footnote i: for cantilever members, l is twice the length of the cantilever
UK NA steel: 8 m beam with brittle finish span/360 = 22.2 mm, other beam span/200 = 40 mm, 2 m cantilever length/180 = 11.1 mmNA to BS EN 1993-1-1, NA.2.23 (vertical deflections under variable actions)
EN 1992: 6 m slab span/250 = 24 mm and span/500 = 12 mm; EN 1995: 4 m beam w_inst l/300 = 13.3 mm (lenient) or l/500 = 8 mm (strict), w_fin l/150 = 26.7 mmEN 1992-1-1 7.4.1(4), (5); EN 1995-1-1 Table 7.2
A deflection over the limit fails; zero deflections are not checked; a negative deflection and an unknown member are refusedBehaviour check: warnings and rejected inputs
Worked example of the article: the calculator reproduces 0.47 in, 0.70 in, 78.6 %, 480 to the digits printedThe worked example on this page, to the digits printed
Assumptions and sources
Assumptions and limits
IBC Table 1604.3 limits apply to the deflection under each load named in its columns; the D + L column may use 0.5 D for dry wood (footnote d) and zero dead load for steel members (footnote g), and wind may be taken as 0.42 times the component and cladding loads (footnote f).
For cantilevers the IBC uses l = twice the cantilever length (footnote i); the UK National Annex to EN 1993-1-1 gives length/180 directly, and EN 1995-1-1 has its own cantilever row.
The UK National Annex limits for steel apply to characteristic variable actions only, without the permanent load. EN 1992-1-1 7.4.1 gives span/250 for the sag under quasi-permanent loads and span/500 for deflection after construction.
EN 1995-1-1 Table 7.2 gives ranges; the national annex fixes the value. Choose the lenient or the strict end of each range.
These are code serviceability limits. Vibration of floors, ponding of flat roofs and limits for glass or crane runways need separate checks.
Sources
International Building Code 2021, Table 1604.3 Deflection Limits and footnotes a to i (same values in IBC 2018)
NA+A1:2014 to BS EN 1993-1-1:2005+A1:2014, clause NA.2.23 (vertical and horizontal deflection limits for buildings)
EN 1992-1-1:2004, 7.4.1(4) and (5) (span/250 and span/500)
EN 1995-1-1:2004+A1:2008, 7.2 and Table 7.2 (limiting values for deflections of beams)