Inverter size calculator

What size power inverter you need: running watts and VA of your loads, motor starting surge, design margin, the next common size and the DC battery current.

Units

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report a problem

Introduction

What size inverter do you need? Add up the running watts of everything that can be on at the same time, allow for the power factor of motors, and add a margin. Then check that the inverter's surge rating covers the largest motor starting. The battery side matters too: a 1 000 W load on a 12 V battery draws about 93 A through a 90 % efficient inverter.

This calculator sums your loads in watts and volt-amperes, adds the starting surge, and recommends the next common inverter size. It also gives the battery current at the nominal and at the low-cutoff voltage, which sets the cable and fuse sizes. It is for owners of off-grid cabins, vans, boats and backup systems, and for the installers who size them.

Formulas

Loads:

W_run = Σ W_i
S_run = Σ W_i / PF_i
surge = max(W_start,i − W_i)    (one motor at a time)
W_peak = W_run + surge

Inverter and battery:

rating ≥ S_run × (1 + m)   and   rating ≥ W_peak / k_surge
I_dc = W / (V_bat × η)
  • W_i, W_start,i — running and starting watts of each load
  • PF_i — power factor of each load, 1 for heaters, lights and electronics with power factor correction
  • m — design margin; k_surge — the inverter's surge rating as a multiple of its continuous rating
  • V_bat — battery voltage; η — inverter efficiency

Assumptions and limitations

  • Take running and starting watts from the nameplate or manual. The default list is an illustrative example only.
  • The VA of the loads are added directly. This ignores their different phase angles and errs on the safe side.
  • By default only one motor starts at a time. Choose "all together" if several motors can start at once, for example when power returns.
  • Surge ratings vary widely between inverters and last only a few seconds. Take the multiple from the data sheet.
  • Inverter ratings are not a standard series. The page picks the next common catalogue size, so check what the maker offers.

Worked example

A cabin runs a refrigerator (150 W, starting 750 W, power factor 0.8), a 1/2 hp well pump (800 W, starting 2 400 W, power factor 0.75), a microwave (1 000 W), lights (200 W), a TV and router (150 W) and a laptop (60 W). The battery is 24 V, the inverter is 90 % efficient and can surge to twice its rating. What size inverter is needed?

  1. Running watts: 150 + 800 + 1 000 + 200 + 150 + 60 = 2 360 W.
  2. Apparent power: 150 / 0.8 + 800 / 0.75 + 1 410 = 2 664 VA, an overall power factor of 0.89.
  3. Largest surge: the pump, 2 400 − 800 = 1 600 W, so the peak is 3 960 W.
  4. Continuous need with a 25 % margin: 2 664 × 1.25 = 3 330 VA.
  5. Surge need: 3 960 / 2 = 1 980 W, below the continuous need.
  6. The next common size is 3 500 W.
  7. Battery current: 2 360 / (24 × 0.9) = 109 A running. At the peak and a 21 V cutoff it is 3 960 / (21 × 0.9) = 209.5 A.

FAQ

What size inverter do I need?

At least the running watts of everything on at the same time, plus a margin of about 25 %. Its surge rating must also cover the largest motor starting.

How do I calculate inverter size from watts?

Add the watts of all loads that run together and divide motor loads by their power factor. Multiply by 1.25 and choose the next size up.

What is inverter surge power?

The power an inverter can deliver for a few seconds while a motor starts. Many inverters manage about twice their continuous rating, but check the data sheet.

How many amps does an inverter draw from the battery?

Watts divided by battery volts and by the efficiency. A 2 000 W load on 12 V at 90 % draws 185 A.

Should I use a 12 V, 24 V or 48 V battery?

A higher voltage halves the current each time it doubles. Above about 2 kW, 24 V or 48 V keeps the cables and fuses a practical size.

Do I need a pure sine wave inverter?

For motors, compressors, chargers and most modern electronics, yes. Modified sine wave output makes many motors run hotter and noisier.

Related calculators

What this calculator is checked against

Before every release the calculator must reproduce each case below. The note under each case says where the expected answer comes from: a standard, a textbook, a published table, or a hand calculation shown in full.

  1. Default list: 2 360 W, 2 664 VA, pump surge 1 600 W, peak 3 960 W, 3 330 VA with 25 % margin, 3 500 W inverter, 109.3 A at 24 V and 90 %Hand calculation: Σ W, Σ W/PF, largest (start − run), I = P / (V η)
  2. A 1 000 W pump starting at 3 000 W alone with a 2× surge inverter needs 1 500 W, set by the surge, not the 1 250 VA running loadHand calculation: peak / surge multiple = 3 000 / 2
  3. All motors starting together add every surge: 600 + 1 600 = 2 200 W on the default listDefinition of simultaneous starting
  4. 1 000 W from a 12 V battery through a 90 % inverter draws 92.6 A, and 105.8 A at the 10.5 V cutoffI = P / (V η)
  5. A load above the largest common size gives no size and says so; the parser fills in starting watts and power factorDesign decision; parser contract
  6. A power factor above 1, starting watts below running watts, an empty list and zero watts are rejectedBehaviour check: warnings and rejected inputs
  7. Worked example of the article: the calculator reproduces 2 360 W, 2 664 VA, 3 960 W, 3 330 VA, 3 500 W, 109 A, 209.5 A to the digits printedThe worked example on this page, to the digits printed

Assumptions and sources

Assumptions and limits

  • Running watts are what each load draws once running and starting watts what a motor draws for a few seconds while it starts; take both from the nameplate or manual. The default list is an illustrative example only.
  • Apparent power is the sum of each load's watts divided by its power factor; adding the VA arithmetically ignores the different phase angles and errs on the safe side. Loads without a power factor are taken as resistive (1).
  • By default the motors start one at a time, so only the largest surge adds to the running total; choose "all together" if several can start at once. The inverter's surge rating is its continuous rating times the surge multiple from its data sheet, held for a few seconds.
  • The recommended size is the next common catalogue rating above both requirements; inverter ratings are not a standard series, so check the sizes the maker offers.
  • Battery current is the AC output power divided by the battery voltage and the inverter efficiency; it is highest at the low-voltage cutoff, which sets the cable and fuse sizes.

Sources

  • Sandia National Laboratories, Stand-Alone Photovoltaic Systems: A Handbook of Recommended Design Practices, SAND87-7023 (inverter sizing for continuous and surge loads)
  • IEEE Std 1562-2007, Guide for Array and Battery Sizing in Stand-Alone Photovoltaic Systems (load determination)
  • NEMA MG 1-2021, Motors and Generators, Part 10 (locked-rotor kVA code letters behind the starting surge of motor loads)

Cite this calculator

Papandreou, C. (2026). Inverter size calculator. Engineering Bible. https://engineeringbible.com/energy/inverter-size/

Embed this calculator on your site

Copy this HTML into your page. The calculator stays free to use and links back here.

By Christos Papandreou. Updated . How the numbers are checked.