Energy and renewables formulas
The formulas behind the 11 energy and renewables calculators, on one page you can print or save as a PDF. Each block lists its variables and standard; the heading opens the calculator, with its assumptions and a worked example.
Battery charge time
Charge to put back, and charge the charger must supply:
Q_back = Q_rated × (SoC_target − SoC_now)
Q_in = Q_back / η
Charge time and charge rate:
t = Q_in / I
C-rate = I / Q_rated (I in A, Q in Ah)
Typical charge efficiency η: flooded lead-acid 85 %, AGM or gel 90 %, lithium-ion 95 %, LiFePO4 97 %, NiMH 70 %.
Electricity cost and energy use
Energy per day of use:
E_day = P × duty × hours per day
Monthly and yearly energy, with the average month of 30.44 days:
E_month = E_day × (days per week / 7) × 30.44
E_year = E_day × (days per week / 7) × 365.25
Cost:
cost = E [kWh] × price per kWh
1 kWh = 1000 W for one hour = 3.6 MJ
- P — power while running, W or kW
- duty — share of the time the load actually draws that power, 0 to 100 %
EV charging time and cost calculator
Energy, time and cost:
E_bat = C × (SoC_end − SoC_start)
E_grid = E_bat / η
P = min(P_charger, P_car)
t = E_grid / P
cost = E_grid × price
Range:
range = E_bat / c
range per hour = P × η / c
- C — usable battery capacity; SoC — state of charge
- η — charging efficiency from the grid to the battery
- P_charger — charger power, volts × amps for AC
- P_car — onboard charger limit (AC) or maximum DC charging power
- c — consumption from the battery, in kWh per mile or per km
Heat pump vs gas boiler running cost calculator
Energy and cost for the same heat Q:
E_hp = Q / SCOP, cost_hp = E_hp × p_elec
E_fuel = Q / η, cost_boiler = E_fuel × p_fuel
saving = cost_boiler − cost_hp
Break-even COP for cost and for CO₂:
COP_cost = p_elec × η / p_fuel
COP_CO₂ = f_elec × η / f_fuel
- Q — heat needed per year for space heating and hot water
- SCOP — seasonal coefficient of performance of the heat pump
- η — seasonal efficiency of the boiler, gross basis
- p_elec, p_fuel — prices per kWh of electricity and of fuel
- f_elec, f_fuel — CO₂ per kWh of electricity and of fuel
Fuel units, EPA heat contents:
1 therm = 100 000 Btu = 29.31 kWh
1 ccf of natural gas = 102 600 Btu = 30.07 kWh
1 US gal of No. 2 heating oil = 138 000 Btu = 40.44 kWh
Inverter size calculator
Loads:
W_run = Σ W_i
S_run = Σ W_i / PF_i
surge = max(W_start,i − W_i) (one motor at a time)
W_peak = W_run + surge
Inverter and battery:
rating ≥ S_run × (1 + m) and rating ≥ W_peak / k_surge
I_dc = W / (V_bat × η)
- W_i, W_start,i — running and starting watts of each load
- PF_i — power factor of each load, 1 for heaters, lights and electronics with power factor correction
- m — design margin; k_surge — the inverter's surge rating as a multiple of its continuous rating
- V_bat — battery voltage; η — inverter efficiency
mAh to Wh battery capacity
Energy from capacity, and capacity from energy:
E [Wh] = Q [Ah] × V
E [Wh] = Q [mAh] × V / 1000
Q [Ah] = E [Wh] / V
- Q — capacity, Ah (1 Ah = 1000 mAh)
- V — nominal voltage, V: lithium-ion 3.6 to 3.7 V per cell, LiFePO4 3.2 V, lead-acid 2.0 V per cell, NiMH 1.2 V
- E — energy, Wh (1 kWh = 1000 Wh)
Airline limits for lithium-ion batteries carried by passengers (IATA):
up to 100 Wh allowed in carry-on
over 100, up to 160 airline approval needed
over 160 Wh not allowed in passenger baggage
Micro-hydro power calculator
Power and net head:
P = ρ g Q H_n η
H_n = H_g − h_f − K v² / (2g)
Friction loss in the penstock:
Darcy–Weisbach: h_f = f (L / D) v² / (2g), f from Colebrook
Hazen–Williams: h_f = 10.67 L Q^1.852 / (C^1.852 D^4.8704)
- ρ — water density, 1 000 kg/m³; g = 9.81 m/s²; Q — design flow
- H_g — gross head; H_n — net head at the turbine
- η — overall efficiency from water to wire
- L, D — penstock length and inside diameter; v — water velocity; f — Darcy friction factor
- K — sum of the fitting loss coefficients; C — Hazen–Williams coefficient
Turbine types by net head, from ESHA Table 6.3:
| Turbine | Net head range |
|---|---|
| Kaplan and propeller | 2 to 40 m |
| Crossflow | 5 to 200 m |
| Francis | 25 to 350 m |
| Turgo | 50 to 250 m |
| Pelton | 50 to 1 300 m |
Solar battery bank calculator
Energy the bank must deliver, and the nominal capacity:
E_bank = E_day × N_days / η_inv
C_nom = E_bank × k_T × (1 + m) / DoD
Ah = C_nom / V_sys
Batteries:
N_series = V_sys / V_bat
N_parallel = ceil(Ah / Ah_bat)
usable energy = N_parallel × Ah_bat × V_sys × DoD / k_T
- E_day — energy used per day; N_days — days of autonomy
- η_inv — inverter efficiency, 1 for DC loads
- DoD — depth of discharge: 50 % for lead-acid, 80 % for LiFePO4 by default
- k_T — temperature correction factor of IEEE 485, 1.00 at 25 °C (77 °F)
- m — ageing and design margin
- V_sys, V_bat — bank voltage and the voltage of one battery; Ah_bat — capacity of one battery
Selected IEEE 485 temperature correction factors for vented lead-acid cells:
| Temperature | Factor |
|---|---|
| −3.9 °C (25 °F) | 1.52 |
| 4.4 °C (40 °F) | 1.30 |
| 10 °C (50 °F) | 1.19 |
| 15.6 °C (60 °F) | 1.11 |
| 21.1 °C (70 °F) | 1.04 |
| 25 °C (77 °F) | 1.00 |
Solar panel calculator: how many panels do I need?
What one kilowatt of panels produces in a year, the specific yield:
Y = PSH × 365 × (1 − losses) kWh per kW per year
System size and number of panels:
P = E × offset / Y
N = P / P_panel, rounded up
Yearly production of the installed panels:
E_out = N × P_panel × Y
- E — yearly electricity use, from 12 months of bills
- offset — the share of that use the panels should cover
- PSH — peak sun hours: the daily solar energy on the panels in kWh/m², averaged over the year
- losses — temperature, dirt, wiring, inverter and mismatch, about 14 %
- P_panel — the rated power of one panel at standard test conditions
Solar panel payback calculator
Production and saving in year n:
E_n = E_1 (1 − d)^(n−1), E_1 = P_kW × Y
S_n = E_n [s p_imp + (1 − s) p_exp] (1 + e)^(n−1) − O&M
Payback and value:
payback: the year in which Σ S_n reaches C_net
NPV = −C_net + Σ S_n / (1 + r)^n
ROI = (Σ S_n − C_net) / C_net
LCOE = (C_net + Σ O&M / (1 + r)^n) / Σ E_n / (1 + r)^n
- C_net — installed cost less tax credits, rebates and grants
- P_kW — system size; Y — specific yield in kWh per kW per year
- d — degradation per year; e — electricity price rise per year
- s — share of the production used on site; p_imp, p_exp — import and export prices
- r — discount rate; the IRR is the rate at which the NPV is zero
Wind turbine power calculator
Power and the Betz limit:
P = ½ ρ A v³ Cp, A = π D² / 4
Cp ≤ 16/27 = 0.593
Rayleigh distribution of the wind speed, mean v̄:
f(v) = (π v / (2 v̄²)) exp(−π v² / (4 v̄²))
P_mean = ∫ P(v) f(v) dv, E = 8 760 h × P_mean
Idealised power curve and density:
P(v) = 0 below v_in and above v_out; ½ ρ A v³ Cp up to v_r; P_r = ½ ρ A v_r³ Cp from v_r to v_out
ρ = p(h) / (R T), ISO 2533 standard atmosphere
- ρ — air density, 1.225 kg/m³ at sea level and 15 °C
- D — rotor diameter; v — wind speed; Cp — power coefficient from wind to electricity
- v_in, v_r, v_out — cut-in, rated and cut-out speeds
- capacity factor = P_mean / P_r
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.