How to calculate voltage drop and choose a cable size

By Christos Papandreou. Updated . About 12 minutes to read.

A cable has two jobs. It must carry the load current without overheating, and it must deliver enough of the source voltage to the far end for the load to work properly. The first is a table lookup corrected for the way the cable is installed; the second is a calculation, and on long runs, at low voltage and on DC it is usually the one that decides the size.

This guide sets out the voltage-drop formulas for DC, single-phase and three-phase circuits as IEC 60364-5-52 Annex G gives them, shows how conductor temperature changes the resistance, and then walks through the full sizing sequence for a three-phase motor feeder: design current, protective device, current-carrying capacity, voltage drop and short-circuit withstand. The cable sizing and voltage drop calculator reproduces every voltage-drop number here.

Why voltage drop matters

Every conductor has resistance, so current flowing through it loses voltage along the route. The load then sees less than the nominal voltage. A motor at reduced voltage draws more current for the same output, runs hotter and produces less starting torque, which varies with the square of the voltage. Lamps dim, electronic supplies drop out, contactors chatter during a motor start. The energy lost is heat in the cable, paid for for as long as the circuit runs.

Low-voltage DC systems are the most sensitive. A 24 V control supply that loses 1.5 V has lost over 6 % of its voltage, and the battery voltage already varies with its state of charge.

Conductor resistance and temperature

Designers take the resistance per kilometre from IEC 60228 Table 2, the maximum DC resistance of class 2 stranded conductors at 20 °C. A few values:

Size (mm²)Copper, Ω/km at 20 °CAluminium, Ω/km at 20 °C
2.57.41–
63.08–
161.151.91
250.7271.20
350.5240.868
500.3870.641
950.1930.320

Resistance rises with temperature:

R'_T = R'₂₀ × [1 + α (T − 20)]

with α = 0.00393 /K for copper and 0.00403 /K for aluminium (IEC 60287-1-1). For a size not in the table, the theoretical value is R' = ρ₂₀ / A, with ρ₂₀ = 1.7241 × 10⁻⁸ Ω·m for copper (IEC 60028) and 2.8264 × 10⁻⁸ Ω·m for aluminium.

Use the conductor's rated operating temperature, as Annex G does: 70 °C for PVC insulation and 90 °C for XLPE or EPR. Between 20 °C and 70 °C copper resistance rises by about 20 %, and to 90 °C by about 27.5 %. A cable that runs fully loaded will be at that temperature, so the cold value understates the drop. A lightly loaded cable runs cooler and drops a little less.

The voltage-drop formulas

Let L be the one-way route length in metres, R' and X' the conductor resistance and reactance in Ω/km, I the load current and cos φ the load power factor. First the resistance and reactance of one conductor over the route:

R = R'_T × L / 1000        X = X' × L / 1000        [Ω]

Then, depending on the system:

DC:            ΔU = 2 × I × R
Single-phase:  ΔU = 2 × I × (R cos φ + X sin φ)
Three-phase:   ΔU = √3 × I × (R cos φ + X sin φ)     (line-to-line)
ΔU% = 100 × ΔU / U_nominal

The factor 2 counts the outgoing and the return conductor, both carrying the full current. In a balanced three-phase circuit the neutral carries no current; the drop in each phase conductor is I(R cos φ + X sin φ), and the line-to-line drop is √3 times that. U_nominal is the line-to-line voltage for three-phase, phase-to-neutral for single-phase, and the DC voltage for DC.

The reactance term only matters in AC. Without catalogue data, Annex G takes X' = 0.08 Ω/km (0.08 mΩ/m), which suits multicore cables and touching single-core low-voltage cables. Widely spaced single cores, armoured and medium-voltage cables need the manufacturer's value. At a power factor of 0.85 on a 16 mm² cable the reactive part is only about 4 % of the drop, but on 95 mm² and above the resistance is small enough for reactance to dominate, and at a low power factor it becomes significant at any size.

The power lost in the cable is

P_loss = n × I² × R,   n = 2 for DC and single-phase, 3 for three-phase

The UK mV/A/m method

BS 7671 tabulates the drop of each cable as millivolts per ampere per metre of route, so the drop is one multiplication:

ΔU = (mV/A/m) × I × L / 1000        [V]

It is the same formula as above, packaged. A resistance in Ω/km is numerically the same as mV/A/m for one conductor, so the tabulated figure is 2 × R'_T for a single-phase circuit and √3 × R'_T for three-phase, with the reactance included for the larger sizes. For 2.5 mm² copper at 70 °C, R'_T is 8.87 Ω/km and 2 × 8.87 = 17.7 mV/A/m, which the UK table rounds to 18. A 20 A load 30 m away then drops 17.7 × 20 × 30 / 1000 = 10.6 V, or 4.6 % of 230 V. BS 7671 uses the same 3 % and 5 % limits as IEC 60364 for an installation fed from the public supply.

Usual voltage-drop limits

During a motor start the current is several times the running current, and a larger transient drop, often 15 %, is accepted.

The sizing sequence

Voltage drop is one check of five. Take them in this order, because each one fixes a number the next one needs.

  1. Design current I_b. From the load: I = P / (√3 V cos φ) for three-phase, P / (V cos φ) single-phase, P / V for DC. For a motor, the nameplate kW is shaft output, so divide by the efficiency first. The three-phase power calculator does this from the nameplate.
  2. Protective device I_n. The next standard rating at or above I_b. Under IEC 60364-4-43 the rule is I_b ≤ I_n ≤ I_z. Under the NEC a continuous load needs at least 125 % of its current. The breaker size calculator applies both sets of rules. Motor circuits follow their own rules: IEC practice uses motor-protection breakers or fuses chosen for the starting current.
  3. Current-carrying capacity I_z. From the tables of IEC 60364-5-52 (or IEC 60092-352 on ships, NEC Table 310.16 in the US) for the installation method, then multiplied by the correction factors for ambient temperature and grouping. The derated I_z must be at least I_n. This step depends on how the cable is laid, so no general formula replaces the tables.
  4. Voltage drop. With the size from step 3, compute ΔU% at the design current and compare it with the limit. If it fails, go up a size and check again.
  5. Short-circuit withstand and disconnection. The cable must survive the fault current for as long as the protective device takes to clear it, and the earth-fault current at the far end must be large enough to trip the device in the permitted time.

The answer is the largest size any of the checks demands.

Worked example: a three-phase motor feeder

A 45 kW, 400 V pump motor has a nameplate efficiency of 93 % and a power factor of 0.86, and starts direct on line at 7 times full-load current. It is fed by a multicore copper XLPE cable along a 120 m route. The allowed running drop is 5 %.

Step 1: design current

Electrical input: 45 / 0.93 = 48.39 kW. Current: 48 387 / (√3 × 400 × 0.86) = 81.2 A.

Step 2: protective device

The next IEC preferred rating at or above 81.2 A is 100 A (the series runs 63, 80, 100, 125 A). So the cable needs I_z ≥ 100 A.

Step 3: current-carrying capacity

Take the installation-method table and correction factors for your actual route. For this example, assume they give 25 mm² a derated I_z of 110 A, and that 16 mm² falls short. That figure is an assumption for illustration, not a table value; it is the step you must take from the standard for the real installation. 81.2 ≤ 100 ≤ 110, so 25 mm² passes.

Step 4: voltage drop

  1. Resistance of 25 mm² copper at 20 °C: 0.727 Ω/km. At 90 °C: 0.727 × (1 + 0.00393 × 70) = 0.9270 Ω/km.
  2. Over 120 m: R = 0.9270 × 0.120 = 0.1112 Ω. X = 0.08 × 0.120 = 0.0096 Ω.
  3. cos φ = 0.86, so sin φ = √(1 − 0.86²) = 0.5103.
  4. R cos φ + X sin φ = 0.1112 × 0.86 + 0.0096 × 0.5103 = 0.09566 + 0.00490 = 0.1006 Ω.
  5. ΔU = √3 × 81.2 × 0.1006 = 14.14 V, which is 14.14 / 400 = 3.54 %. Within 5 %. The motor sees 385.9 V.
  6. Loss: 3 × 81.2² × 0.1112 = 2.20 kW, about 4.5 % of the input power.

For comparison, 16 mm² (1.15 × 1.2751 = 1.466 Ω/km) gives 21.97 V or 5.49 %, which fails the drop limit on its own. On this route voltage drop and ampacity both point to 25 mm². Run the cable sizing calculator with three-phase, 400 V, 81.2 A, 120 m, copper, XLPE 90 °C, 25 mm², power factor 0.86 and a 5 % limit and it returns 14.14 V and 3.54 %, and names 25 mm² as the smallest size that meets the limit.

Two variations show how sensitive the result is. Calculated at 20 °C instead of 90 °C, the same 35 mm² cable shows 2.07 % instead of 2.60 %: ignoring temperature understates the drop by about a fifth. In aluminium, 25 mm² gives 5.75 % and fails, while 35 mm² gives 4.21 %: one size up from copper, as the 1.6 times higher resistance predicts.

Starting

Direct-on-line starting at 7 × 81.2 = 568 A with a starting power factor of 0.3 gives a cable drop of 41.9 V, or 10.5 %, on 25 mm². That is inside a typical 15 % transient allowance, but the source dips as well, and on a generator or a weak transformer that dip can be larger than the cable's. The motor starting calculator works out that supply dip and compares star-delta, soft starter and drive options.

Step 5: short-circuit withstand

The adiabatic check of IEC 60364-4-43 requires the fault energy to stay below what the conductor can absorb:

I² t ≤ k² S²
k = K √ln((θf + β)/(θi + β))   copper: K = 226, β = 234.5 °C

For copper XLPE, from 90 °C to 250 °C, k = 143.1; for copper PVC, from 70 °C to 160 °C, k = 115. Suppose the supply has an external loop impedance Ze of 0.1 Ω at 230 V to earth and the cable has a 25 mm² protective core. With hot conductors the loop impedance is Zs = 0.311 Ω and the minimum earth-fault current 0.95 × 230 / 0.311 = 702 A. If the breaker's curve shows it clearing 702 A in 0.1 s, the energy is 702² × 0.1 = 4.9 × 10⁴ A²s against k²S² = 1.28 × 10⁷ A²s: a wide margin, and the conductor would withstand that current for about 26 s. Whether the device actually clears 702 A within the 5 s permitted for a distribution circuit, or faster for final circuits, comes from its time–current curve. The cable short-circuit withstand calculator reproduces these figures.

At the switchboard end the concern is the opposite: the maximum prospective current, which sets the breaking capacity of the device and the energy a small cable near a large transformer must survive. The short-circuit current calculator follows IEC 60909-0 for that.

Metric sizes and AWG

IEC 60228 sizes run 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm² and up. North American wire is sized by AWG, defined in ASTM B258, where a larger number is a thinner wire, and above 4/0 in kcmil. The two series do not line up: 25 mm² falls between 4 AWG (21.15 mm²) and 3 AWG (26.67 mm²), and 12 AWG (3.31 mm²) sits between 2.5 and 4 mm². When converting, choose the size with at least the same area, never the nearest. The AWG wire gauge chart lists the areas and the next IEC size for each gauge.

The wire size calculator finds the smallest AWG and metric sizes for a given drop. It neglects reactance and uses 75 °C, the NEC resistance basis, so for the feeder above it gives 4 AWG and 25 mm². Use it for building wire; for larger AC feeders at a low power factor, include reactance.

Common mistakes

Limits of the method

The governing documents are IEC 60364-5-52 (Annex G for voltage drop, the current-carrying capacity tables), IEC 60364-4-43 (overcurrent protection and the adiabatic check), IEC 60228 (conductor sizes and resistance), IEC 60287-1-1 (temperature coefficients), and on ships IEC 60092-201 and IEC 60092-352.

Calculators used in this guide

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report an error in this guide

By Christos Papandreou. How the numbers are checked.