How to calculate voltage drop and choose a cable size
A cable has two jobs. It must carry the load current without overheating, and it must deliver enough of the source voltage to the far end for the load to work properly. The first is a table lookup corrected for the way the cable is installed; the second is a calculation, and on long runs, at low voltage and on DC it is usually the one that decides the size.
This guide sets out the voltage-drop formulas for DC, single-phase and three-phase circuits as IEC 60364-5-52 Annex G gives them, shows how conductor temperature changes the resistance, and then walks through the full sizing sequence for a three-phase motor feeder: design current, protective device, current-carrying capacity, voltage drop and short-circuit withstand. The cable sizing and voltage drop calculator reproduces every voltage-drop number here.
Why voltage drop matters
Every conductor has resistance, so current flowing through it loses voltage along the route. The load then sees less than the nominal voltage. A motor at reduced voltage draws more current for the same output, runs hotter and produces less starting torque, which varies with the square of the voltage. Lamps dim, electronic supplies drop out, contactors chatter during a motor start. The energy lost is heat in the cable, paid for for as long as the circuit runs.
Low-voltage DC systems are the most sensitive. A 24 V control supply that loses 1.5 V has lost over 6 % of its voltage, and the battery voltage already varies with its state of charge.
Conductor resistance and temperature
Designers take the resistance per kilometre from IEC 60228 Table 2, the maximum DC resistance of class 2 stranded conductors at 20 °C. A few values:
| Size (mm²) | Copper, Ω/km at 20 °C | Aluminium, Ω/km at 20 °C |
|---|---|---|
| 2.5 | 7.41 | – |
| 6 | 3.08 | – |
| 16 | 1.15 | 1.91 |
| 25 | 0.727 | 1.20 |
| 35 | 0.524 | 0.868 |
| 50 | 0.387 | 0.641 |
| 95 | 0.193 | 0.320 |
Resistance rises with temperature:
R'_T = R'₂₀ × [1 + α (T − 20)]
with α = 0.00393 /K for copper and 0.00403 /K for aluminium (IEC 60287-1-1). For a size not in the table, the theoretical value is R' = ρ₂₀ / A, with ρ₂₀ = 1.7241 × 10⁻⁸ Ω·m for copper (IEC 60028) and 2.8264 × 10⁻⁸ Ω·m for aluminium.
Use the conductor's rated operating temperature, as Annex G does: 70 °C for PVC insulation and 90 °C for XLPE or EPR. Between 20 °C and 70 °C copper resistance rises by about 20 %, and to 90 °C by about 27.5 %. A cable that runs fully loaded will be at that temperature, so the cold value understates the drop. A lightly loaded cable runs cooler and drops a little less.
The voltage-drop formulas
Let L be the one-way route length in metres, R' and X' the conductor resistance and reactance in Ω/km, I the load current and cos φ the load power factor. First the resistance and reactance of one conductor over the route:
R = R'_T × L / 1000 X = X' × L / 1000 [Ω]
Then, depending on the system:
DC: ΔU = 2 × I × R
Single-phase: ΔU = 2 × I × (R cos φ + X sin φ)
Three-phase: ΔU = √3 × I × (R cos φ + X sin φ) (line-to-line)
ΔU% = 100 × ΔU / U_nominal
The factor 2 counts the outgoing and the return conductor, both carrying the full current. In a balanced three-phase circuit the neutral carries no current; the drop in each phase conductor is I(R cos φ + X sin φ), and the line-to-line drop is √3 times that. U_nominal is the line-to-line voltage for three-phase, phase-to-neutral for single-phase, and the DC voltage for DC.
The reactance term only matters in AC. Without catalogue data, Annex G takes X' = 0.08 Ω/km (0.08 mΩ/m), which suits multicore cables and touching single-core low-voltage cables. Widely spaced single cores, armoured and medium-voltage cables need the manufacturer's value. At a power factor of 0.85 on a 16 mm² cable the reactive part is only about 4 % of the drop, but on 95 mm² and above the resistance is small enough for reactance to dominate, and at a low power factor it becomes significant at any size.
The power lost in the cable is
P_loss = n × I² × R, n = 2 for DC and single-phase, 3 for three-phase
The UK mV/A/m method
BS 7671 tabulates the drop of each cable as millivolts per ampere per metre of route, so the drop is one multiplication:
ΔU = (mV/A/m) × I × L / 1000 [V]
It is the same formula as above, packaged. A resistance in Ω/km is numerically the same as mV/A/m for one conductor, so the tabulated figure is 2 × R'_T for a single-phase circuit and √3 × R'_T for three-phase, with the reactance included for the larger sizes. For 2.5 mm² copper at 70 °C, R'_T is 8.87 Ω/km and 2 × 8.87 = 17.7 mV/A/m, which the UK table rounds to 18. A 20 A load 30 m away then drops 17.7 × 20 × 30 / 1000 = 10.6 V, or 4.6 % of 230 V. BS 7671 uses the same 3 % and 5 % limits as IEC 60364 for an installation fed from the public supply.
Usual voltage-drop limits
- IEC 60364-5-52 suggests 3 % for lighting and 5 % for other uses, measured from the origin of the installation.
- IEC 60092-201 allows 6 % on ships between the main or emergency switchboard and the consumer.
- The NEC, in informational notes, suggests 3 % for a branch circuit and 5 % for feeder and branch circuit together.
- Battery-fed DC systems often need tighter limits, because the source voltage already varies.
During a motor start the current is several times the running current, and a larger transient drop, often 15 %, is accepted.
The sizing sequence
Voltage drop is one check of five. Take them in this order, because each one fixes a number the next one needs.
- Design current I_b. From the load: I = P / (√3 V cos φ) for three-phase, P / (V cos φ) single-phase, P / V for DC. For a motor, the nameplate kW is shaft output, so divide by the efficiency first. The three-phase power calculator does this from the nameplate.
- Protective device I_n. The next standard rating at or above I_b. Under IEC 60364-4-43 the rule is I_b ≤ I_n ≤ I_z. Under the NEC a continuous load needs at least 125 % of its current. The breaker size calculator applies both sets of rules. Motor circuits follow their own rules: IEC practice uses motor-protection breakers or fuses chosen for the starting current.
- Current-carrying capacity I_z. From the tables of IEC 60364-5-52 (or IEC 60092-352 on ships, NEC Table 310.16 in the US) for the installation method, then multiplied by the correction factors for ambient temperature and grouping. The derated I_z must be at least I_n. This step depends on how the cable is laid, so no general formula replaces the tables.
- Voltage drop. With the size from step 3, compute ΔU% at the design current and compare it with the limit. If it fails, go up a size and check again.
- Short-circuit withstand and disconnection. The cable must survive the fault current for as long as the protective device takes to clear it, and the earth-fault current at the far end must be large enough to trip the device in the permitted time.
The answer is the largest size any of the checks demands.
Worked example: a three-phase motor feeder
A 45 kW, 400 V pump motor has a nameplate efficiency of 93 % and a power factor of 0.86, and starts direct on line at 7 times full-load current. It is fed by a multicore copper XLPE cable along a 120 m route. The allowed running drop is 5 %.
Step 1: design current
Electrical input: 45 / 0.93 = 48.39 kW. Current: 48 387 / (√3 × 400 × 0.86) = 81.2 A.
Step 2: protective device
The next IEC preferred rating at or above 81.2 A is 100 A (the series runs 63, 80, 100, 125 A). So the cable needs I_z ≥ 100 A.
Step 3: current-carrying capacity
Take the installation-method table and correction factors for your actual route. For this example, assume they give 25 mm² a derated I_z of 110 A, and that 16 mm² falls short. That figure is an assumption for illustration, not a table value; it is the step you must take from the standard for the real installation. 81.2 ≤ 100 ≤ 110, so 25 mm² passes.
Step 4: voltage drop
- Resistance of 25 mm² copper at 20 °C: 0.727 Ω/km. At 90 °C: 0.727 × (1 + 0.00393 × 70) = 0.9270 Ω/km.
- Over 120 m: R = 0.9270 × 0.120 = 0.1112 Ω. X = 0.08 × 0.120 = 0.0096 Ω.
- cos φ = 0.86, so sin φ = √(1 − 0.86²) = 0.5103.
- R cos φ + X sin φ = 0.1112 × 0.86 + 0.0096 × 0.5103 = 0.09566 + 0.00490 = 0.1006 Ω.
- ΔU = √3 × 81.2 × 0.1006 = 14.14 V, which is 14.14 / 400 = 3.54 %. Within 5 %. The motor sees 385.9 V.
- Loss: 3 × 81.2² × 0.1112 = 2.20 kW, about 4.5 % of the input power.
For comparison, 16 mm² (1.15 × 1.2751 = 1.466 Ω/km) gives 21.97 V or 5.49 %, which fails the drop limit on its own. On this route voltage drop and ampacity both point to 25 mm². Run the cable sizing calculator with three-phase, 400 V, 81.2 A, 120 m, copper, XLPE 90 °C, 25 mm², power factor 0.86 and a 5 % limit and it returns 14.14 V and 3.54 %, and names 25 mm² as the smallest size that meets the limit.
Two variations show how sensitive the result is. Calculated at 20 °C instead of 90 °C, the same 35 mm² cable shows 2.07 % instead of 2.60 %: ignoring temperature understates the drop by about a fifth. In aluminium, 25 mm² gives 5.75 % and fails, while 35 mm² gives 4.21 %: one size up from copper, as the 1.6 times higher resistance predicts.
Starting
Direct-on-line starting at 7 × 81.2 = 568 A with a starting power factor of 0.3 gives a cable drop of 41.9 V, or 10.5 %, on 25 mm². That is inside a typical 15 % transient allowance, but the source dips as well, and on a generator or a weak transformer that dip can be larger than the cable's. The motor starting calculator works out that supply dip and compares star-delta, soft starter and drive options.
Step 5: short-circuit withstand
The adiabatic check of IEC 60364-4-43 requires the fault energy to stay below what the conductor can absorb:
I² t ≤ k² S²
k = K √ln((θf + β)/(θi + β)) copper: K = 226, β = 234.5 °C
For copper XLPE, from 90 °C to 250 °C, k = 143.1; for copper PVC, from 70 °C to 160 °C, k = 115. Suppose the supply has an external loop impedance Ze of 0.1 Ω at 230 V to earth and the cable has a 25 mm² protective core. With hot conductors the loop impedance is Zs = 0.311 Ω and the minimum earth-fault current 0.95 × 230 / 0.311 = 702 A. If the breaker's curve shows it clearing 702 A in 0.1 s, the energy is 702² × 0.1 = 4.9 × 10⁴ A²s against k²S² = 1.28 × 10⁷ A²s: a wide margin, and the conductor would withstand that current for about 26 s. Whether the device actually clears 702 A within the 5 s permitted for a distribution circuit, or faster for final circuits, comes from its time–current curve. The cable short-circuit withstand calculator reproduces these figures.
At the switchboard end the concern is the opposite: the maximum prospective current, which sets the breaking capacity of the device and the energy a small cable near a large transformer must survive. The short-circuit current calculator follows IEC 60909-0 for that.
Metric sizes and AWG
IEC 60228 sizes run 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm² and up. North American wire is sized by AWG, defined in ASTM B258, where a larger number is a thinner wire, and above 4/0 in kcmil. The two series do not line up: 25 mm² falls between 4 AWG (21.15 mm²) and 3 AWG (26.67 mm²), and 12 AWG (3.31 mm²) sits between 2.5 and 4 mm². When converting, choose the size with at least the same area, never the nearest. The AWG wire gauge chart lists the areas and the next IEC size for each gauge.
The wire size calculator finds the smallest AWG and metric sizes for a given drop. It neglects reactance and uses 75 °C, the NEC resistance basis, so for the feeder above it gives 4 AWG and 25 mm². Use it for building wire; for larger AC feeders at a low power factor, include reactance.
Common mistakes
- Loop length entered as route length, or the other way round. The formulas above take the one-way route length and include the return through the factor 2 or √3. Entering the loop length doubles the drop; using a one-way length in a formula written for the loop halves it.
- Wrong factor. 2 for DC and single-phase, √3 for three-phase with the line-to-line voltage. Using 2 on a three-phase circuit overstates the drop by 15 %; using √3 with the phase voltage, or 3 with anything, gives a number that matches no percentage.
- Percentage against the wrong voltage. A three-phase line-to-line drop is divided by the line-to-line voltage (400 V), not the phase voltage (230 V).
- Cold resistance. The 20 °C value understates the drop of a loaded PVC cable by about 20 % and of an XLPE cable by about 27 %.
- Ignoring grouping and ambient. The tabulated current rating is for one circuit at the reference ambient temperature. Cables bunched on a tray or run through a hot engine room carry much less. Apply every correction factor before comparing with I_n.
- Aluminium sized like copper. Aluminium has about 1.6 times the resistance of copper for the same area, so it needs roughly 1.6 times the cross-section for the same drop. IEC 60228 class 2 aluminium starts at 16 mm², and terminations must be rated for it.
- Sizing for voltage drop alone. A cable that passes the drop check can still overheat, or fail the short-circuit check. The 16 mm² size that would meet a 5 % drop on a short run is not automatically the right size for the current.
- Default reactance on large or spaced cables. 0.08 Ω/km is for multicore and touching single cores. Spaced single cores have more, and on large sizes at low power factor the reactive term matters.
Limits of the method
- The load is balanced and sinusoidal. Harmonic-rich loads such as drives and LED drivers increase losses and neutral current and need a separate assessment.
- The IEC 60228 resistances are maximum values, so the drop is slightly conservative; real cables are up to 5 to 7 % better.
- The calculator does not compute current-carrying capacity, short-circuit withstand or protection coordination; those come from the installation tables and the dedicated checks above.
- Mechanical minimum sizes still apply. IEC 60092 requires at least 1.0 mm² for power circuits on ships.
The governing documents are IEC 60364-5-52 (Annex G for voltage drop, the current-carrying capacity tables), IEC 60364-4-43 (overcurrent protection and the adiabatic check), IEC 60228 (conductor sizes and resistance), IEC 60287-1-1 (temperature coefficients), and on ships IEC 60092-201 and IEC 60092-352.
Calculators used in this guide
- ElectricalCable sizing and voltage dropVoltage drop, power loss and the minimum IEC conductor size for DC, single-phase and three-phase circuits from current, length, material and allowed drop.
- ElectricalThree-phase power and motor currentkW, kVA, kvar and line current for three-phase, single-phase and DC circuits; motor full-load and starting current from the nameplate; power-factor correction.
- ElectricalBreaker size calculatorBreaker size for a load in amps or watts, by the NEC 125 % continuous-load rule or IEC Ib ≤ In ≤ Iz, with the standard rating and a wire check.
- ElectricalCable short-circuit withstandAdiabatic short-circuit check of a cable and its protective conductor, with the earth-fault loop impedance, fault current and disconnection time.
- ElectricalWire size calculator (AWG and mm²)Smallest AWG and metric wire size that keeps the voltage drop within your limit for a DC, single-phase or three-phase circuit, with the drop and the loss.
- ElectricalShort-circuit current (IEC 60909)Three-phase short-circuit current at a switchboard from source, transformer and cable impedances; peak current and breaker check.
- ElectricalMotor starting current and voltage dipStarting current and kVA by method (DOL, star-delta, autotransformer, soft starter, VFD), voltage dip on a generator or network, torque at reduced voltage.
- ElectricalAWG wire gauge chart and converterDiameter, mm², circular mils, resistance and weight of every AWG size from 4/0 to 40, or the gauge of a measured wire, with the matching metric size.
Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person. Report an error in this guide
More guides
- Cargo securing calculation to CSS Code Annex 13
- How to do a draft survey calculation, step by step
- How EU ETS and FuelEU Maritime costs are calculated
- How much concrete do I need? Slabs, footings and posts
- How to calculate a ship's CII rating, step by step
- Hull and propeller performance in service with ISO 19030