Electrical engineering formulas

The formulas behind the 36 electrical calculators, on one page you can print or save as a PDF. Each block lists its variables and standard; the heading opens the calculator, with its assumptions and a worked example.

Basics and electronics

555 timer calculator

Astable, with R1 from the supply to the discharge pin and R2 from the discharge pin to the threshold and trigger pins:

t_H = ln 2 × (R1 + R2) × C ≈ 0.693 (R1 + R2) C
t_L = ln 2 × R2 × C ≈ 0.693 R2 C
f = 1 / (t_H + t_L) ≈ 1.44 / ((R1 + 2 R2) C)
D = t_H / (t_H + t_L) = (R1 + R2) / (R1 + 2 R2)

Monostable, with R1 from the supply to the discharge and threshold pins:

t = ln 3 × R1 × C ≈ 1.1 R1 C

Design from a target frequency f and duty cycle D:

S = R1 + 2 R2 = 1 / (ln 2 × f × C)
R1 = (2D − 1) × S,   R2 = (1 − D) × S
  • t_H, t_L — time the output is high and low, s
  • f — frequency, Hz; D — duty cycle, the share of each period the output is high
  • R1, R2 — timing resistors, Ω; C — timing capacitor, F

Air-core coil inductance calculator

Wheeler's formulas, with dimensions in inches and L in µH:

single layer:  L = d² N² / (18 d + 40 l)
multilayer:    L = 0.8 a² N² / (6 a + 9 b + 10 c)

Long solenoid and current sheet, in SI units:

L = μ0 N² A / l,   A = π d² / 4
L_sheet = K × μ0 N² A / l

Turns for a target inductance, single layer:

N = √(L × (18 d + 40 l)) / d
  • N — number of turns; d — coil diameter to the wire centres
  • l, b — winding length; a — mean radius of a multilayer coil
  • c — radial depth of the winding (outer minus inner radius)
  • μ0 = 4π × 10⁻⁷ H/m; K — Nagaoka's coefficient, from the ratio d / l

Decibel calculator (dB, dBm, dBV, dBu)

Ratios:

L = 10 log10(P2 / P1) dB = 20 log10(V2 / V1) dB
P2 / P1 = 10^(L/10),   V2 / V1 = 10^(L/20)

Absolute levels:

dBm = 10 log10(P / 1 mW),   dBW = 10 log10(P / 1 W) = dBm − 30
dBV = 20 log10(V / 1 V),   dBµV = 20 log10(V / 1 µV) = dBV + 120
dBu = 20 log10(V / 0.7746 V) = dBV + 2.218
P = V² / R

Adding uncorrelated levels:

L_total = 10 log10(10^(L1/10) + 10^(L2/10) + …)
  • P — power, W; V — r.m.s. voltage, V; R — impedance, Ω
  • 0.7746 V — the voltage of 1 mW in 600 Ω, √(0.001 × 600)

Filter cutoff frequency calculator (RC, RL, LC)

First-order RC and RL filters, with x = f / f_c:

f_c = 1 / (2π R C)   or   f_c = R / (2π L)
low-pass:   |H| = 1 / √(1 + x²),   φ = −arctan x
high-pass:  |H| = x / √(1 + x²),   φ = 90° − arctan x

Second-order filters, with x = f / f0:

f0 = 1 / (2π √(L C))
Q = √(L / C) / R  (series RLC),   Q = R √(C / L)  (LC with load R)
low-pass:   H = 1 / (1 − x² + j x / Q)
high-pass:  H = −x² / (1 − x² + j x / Q)

The −3 dB frequency of a second-order filter:

u = [(2 − 1/Q²) + √((2 − 1/Q²)² + 4)] / 2
f_3dB = f0 √u  (low-pass),   f0 / √u  (high-pass)
  • R — resistance, Ω; C — capacitance, F; L — inductance, H (entered in µH)
  • |H| — output over input voltage; gain in dB = 20 log10 |H|; φ — phase
  • Q — quality factor; 0.707 gives the flattest passband

LC resonant frequency calculator

Resonant frequency and the component for a target frequency:

f0 = 1 / (2π √(L C))
L = 1 / ((2π f0)² C),   C = 1 / ((2π f0)² L)

Characteristic impedance, quality factor and bandwidth with a series resistance R:

Z0 = √(L / C) = 2π f0 L = 1 / (2π f0 C)
Q = Z0 / R
BW = f0 / Q = R / (2π L)
f1, f2 = f0 × (√(1 + 1/(4Q²)) ∓ 1/(2Q))

Dynamic resistance of a parallel tank at resonance:

R_D = L / (C R) = Q² R
  • L — inductance, H (entered in µH); C — capacitance, F
  • R — total series loss resistance of the coil and capacitor, Ω
  • f1, f2 — the half-power (−3 dB) frequencies

LED series resistor

Series resistor:

R = (V_s − n × V_f) / I

Current with the standard resistor R_std, and powers:

I = (V_s − n × V_f) / R_std
P_R = I² × R_std
P_LED = n × V_f × I

Resistor rating: the smallest standard rating at least twice P_R.

  • V_s — supply voltage
  • V_f — forward voltage of one LED at the design current
  • n — number of LEDs in series
  • I — LED current

Ohm's law and electrical power

Ohm's law and the power law:

V = I R
P = V I = I² R = V² / R

From each pair of known values:

V and I:  R = V / I,        P = V I
V and R:  I = V / R,        P = V² / R
I and R:  V = I R,          P = I² R
P and V:  I = P / V,        R = V² / P
P and I:  V = P / I,        R = P / I²
P and R:  I = √(P / R),     V = √(P R)

Conductance is the inverse of resistance:

G = 1 / R   (siemens)
  • V — voltage across the element, volts (RMS for AC)
  • I — current through it, amperes (RMS for AC)
  • R — resistance, ohms
  • P — power dissipated, watts

PCB trace width calculator (IPC-2221)

IPC-2221 curve fit, solved for the copper cross-section:

I = k × ΔT^0.44 × A^0.725
A = (I / (k × ΔT^0.44))^(1/0.725)
w = A / t,   t = 1.378 mil × copper weight in oz/ft²

Resistance, voltage drop and loss of the trace:

R = ρ20 × (1 + α (T − 20)) × L / (w × t)
V = I × R,   P = I² × R
  • I — current, A; ΔT — temperature rise above ambient, °C
  • A — copper cross-section, mil² (1 mil = 0.001 in = 25.4 µm)
  • k — 0.048 for outer layers, 0.024 for inner layers
  • w — trace width; t — copper thickness; L — trace length
  • ρ20 = 1.7241 × 10⁻⁸ Ω·m, α = 0.00393 per °C; T — ambient plus rise

RC time constant and filter

Time constant:

τ = R × C

Charging from 0 towards V_s, and discharging from V_s:

V_C(t) = V_s × (1 − e^(−t/τ))
V_C(t) = V_s × e^(−t/τ)

Milestones: 63.2 % at t = τ, 86.5 % at 2τ, 95.0 % at 3τ, 99 % at 4.6τ, and 99.3 % at 5τ.

Cutoff (−3 dB) frequency of a first-order RC filter:

f_c = 1 / (2π × R × C)

Current at the first instant and stored energy:

I₀ = V_s / R,    E = ½ × C × V_s²

Resistor colour code

The colour code (IEC 60062):

black 0, brown 1, red 2, orange 3, yellow 4, green 5, blue 6, violet 7, grey 8, white 9

Resistance:

4 bands:     R = (10 d₁ + d₂) × 10^m
5 or 6 bands: R = (100 d₁ + 10 d₂ + d₃) × 10^m

Multiplier band m: silver −2, gold −1, then the digit colours black 0 to white 9.

Tolerance band: brown ± 1 %, red ± 2 %, green ± 0.5 %, blue ± 0.25 %, violet ± 0.1 %, gold ± 5 %, silver ± 10 %, no band ± 20 %.

Range within tolerance:

R_min = R (1 − t),   R_max = R (1 + t)

Sixth band, temperature coefficient in ppm/K: black 250, brown 100, red 50, yellow 25, green 20, orange 15, blue 10, violet 5, grey 1.

Series and parallel capacitors

Parallel, with the same voltage across each capacitor:

C = C₁ + C₂ + … + Cₙ

Series, with the same charge on each capacitor:

1 / C = 1 / C₁ + 1 / C₂ + … + 1 / Cₙ
two capacitors:  C = C₁ C₂ / (C₁ + C₂)

Charge, energy and the voltage on each capacitor in series:

Q = C × V
E = ½ × C × V²
V_i = Q / C_i
  • C — capacitance, farads (1 µF = 10⁻⁶ F)
  • Q — charge, coulombs (shown in µC)
  • E — energy, joules (shown in mJ)

Series and parallel resistors

Series, with the same current through every resistor:

R = R₁ + R₂ + … + Rₙ

Parallel, with the same voltage across every resistor:

1 / R = 1 / R₁ + 1 / R₂ + … + 1 / Rₙ
two resistors:  R = R₁ R₂ / (R₁ + R₂)
n equal resistors:  R = R₁ / n

Voltage division in series and current division in parallel:

V_i = V × R_i / R_series
I_i = I × (1 / R_i) / (1 / R_parallel)

Voltage divider

Unloaded output:

V_out = V_in × R2 / (R1 + R2)

Bottom resistor for a target output:

R2 = R1 × V_out / (V_in − V_out)

Current and power:

I = V_in / (R1 + R2),   P_R1 = I² R1,   P_R2 = I² R2

With a load R_L on the output, R2 is replaced by R2 in parallel with R_L:

R2 ∥ R_L = R2 R_L / (R2 + R_L)

Source resistance seen from the output (Thévenin):

R_th = R1 ∥ R2 = R1 R2 / (R1 + R2)

Power conversions

Amps to kW

Real, apparent and reactive power:

three-phase:   P = √3 × V × I × cos φ,   S = √3 × V × I
single-phase:  P = V × I × cos φ,        S = V × I
DC:            P = V × I

Q = S × sin φ = √(S² − P²)
  • I — line current, A
  • V — voltage, V (line-to-line for three-phase)
  • cos φ — power factor

Amps to watts

Power from current:

DC:            P = V × I
single-phase:  P = V × I × cos φ
three-phase:   P = √3 × V × I × cos φ

Apparent power:

S = P / cos φ
  • I — current, A
  • V — voltage, V (line-to-line for three-phase)
  • cos φ — power factor (1 for resistive loads)

kVA to amps

Three-phase, with the line-to-line voltage:

I = S / (√3 × V)
S = √3 × V × I

Single-phase:

I = S / V
S = V × I

Active and reactive power at a power factor cos φ:

P = S × cos φ
Q = S × sin φ = S × √(1 − cos² φ)
  • S — apparent power, VA (1 kVA = 1000 VA)
  • V — voltage, V (line-to-line for three-phase)
  • I — line current, A

kVA to kW

Real and reactive power from apparent power:

P = S × cos φ
Q = S × sin φ = S × √(1 − cos² φ)

Rated line current:

three-phase:   I = S / (√3 × V)
single-phase:  I = S / V
  • S — apparent power, kVA
  • P — real power, kW
  • cos φ — power factor of the load

kW to amps

Electrical input power:

P_in = P                 (electrical load)
P_in = P_shaft / η       (motor nameplate)

Current:

three-phase:   I = P_in / (√3 × V × cos φ)
single-phase:  I = P_in / (V × cos φ)
DC:            I = P_in / V

Apparent power:

S = P_in / cos φ
  • V — voltage, V (line-to-line for three-phase)
  • cos φ — power factor (motors about 0.8 to 0.9 at full load)
  • η — motor efficiency (IE3 motors about 0.89 at 5 kW to 0.95 at 100 kW)

kW to kVA

The power triangle:

S = P / cos φ
Q = S × sin φ = √(S² − P²)

Line current:

three-phase:   I = S / (√3 × V)
single-phase:  I = S / V
  • P — real power, kW
  • S — apparent power, kVA
  • Q — reactive power, kvar
  • cos φ — power factor of the whole load

Watts to amps

Current from power:

DC:            I = P / V
single-phase:  I = P / (V × cos φ)
three-phase:   I = P / (√3 × V × cos φ)

Apparent power:

S = P / cos φ
  • P — real power, W
  • V — voltage, V (line-to-line for three-phase)
  • cos φ — power factor: 1 for heaters and kettles, about 0.8 to 0.9 for motors

Wires, cables and protection

Breaker size calculator

Load current from power:

DC:            I_b = P / V
single-phase:  I_b = P / (V × cos φ)
three-phase:   I_b = P / (√3 × V × cos φ)

NEC minimum rating, for continuous and non-continuous loads:

I_min = 1.25 × I_continuous + I_noncontinuous

IEC coordination of the breaker and the cable:

I_b ≤ I_n ≤ I_z
  • I_b — design (load) current; I_n — rated current of the breaker; I_z — ampacity of the cable
  • NEC standard ratings (240.6(A)): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A and up
  • IEC preferred ratings (IEC 60898-1): 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A, then 160, 200, 250, 315, 400 A and up

Cable short-circuit withstand

k factor:              k = K √ln((θf + β)/(θi + β))   (K = 226, β = 234.5 °C copper; 148, 228 °C aluminium)
Adiabatic limit:       I² t ≤ k² S²,   t_max = (k S / I)²,   S_min = I √t / k
Hot resistance:        R(θ) = R20 (β + θ)/(β + 20)
Loop impedance:        Zs = Ze + R1 + R2
Fault current:         If = c U0 / Zs
  • θi, θf — maximum operating and short-circuit temperatures; R1, R2 — line and protective conductor resistances over the cable length.

Cable sizing and voltage drop

Conductor resistance per unit length:

R'₂₀ = IEC 60228 Table 2 value for the size (Ω/km), or ρ₂₀ / A for a non-standard size
R'_T = R'₂₀ [1 + α (T − 20)]
  • ρ₂₀ — resistivity at 20 °C: copper 1.7241 × 10⁻⁸ Ω·m, aluminium 2.8264 × 10⁻⁸ Ω·m
  • α — temperature coefficient: copper 0.00393/K, aluminium 0.00403/K
  • T — conductor temperature, °C (70 for PVC, 90 for XLPE at full load)

Voltage drop (L one-way route length):

R = R'_T L / 1000,   X = X' L / 1000            [Ω]
DC:            ΔU = 2 I R
Single-phase:  ΔU = 2 I (R cos φ + X sin φ)
Three-phase:   ΔU = √3 I (R cos φ + X sin φ)     (line-to-line)
ΔU% = 100 ΔU / U_nominal

Power loss:

P_loss = n I² R,   n = 2 (DC, single-phase) or 3 (three-phase)

Minimum size: the smallest IEC 60228 standard cross-section whose ΔU% ≤ allowed drop.

Conduit fill calculator (NEC)

Total conductor area and percent fill:

A_wires = Σ n_i × A_i
fill = A_wires / A_conduit

The fill must not exceed the NEC Chapter 9 Table 1 limit:

1 conductor:           53 %
2 conductors:          31 %
3 or more conductors:  40 %
nipple ≤ 24 in:        60 % (Note 4)

Most conductors of one size:

N = 0.40 × A_conduit / A_wire, rounded down, or up when the decimal is 0.8 or more (Note 7)
  • n_i, A_i — number and area of each wire size, from Chapter 9 Table 5
  • A_conduit — total inside area of the conduit, from Chapter 9 Table 4

Wire size calculator (AWG and mm²)

Voltage drop of a circuit of one-way length L:

DC and single-phase:   ΔV = 2 × I × L × R′
three-phase:           ΔV = √3 × I × L × R′

Resistance per metre of a conductor of area A at temperature T:

R′ = ρ20 × (1 + α (T − 20)) / A × k_s

Minimum area for an allowed drop ΔV_max = p × V:

A_min = b × I × L × ρ(T) × k_s / (p × V)
  • b — 2 for DC and single-phase, √3 for three-phase
  • I — load current; L — one-way length; V — supply voltage; p — allowed drop as a fraction
  • ρ20, α — copper 1.7241 × 10⁻⁸ Ω·m and 0.00393 /K; aluminium 2.8264 × 10⁻⁸ Ω·m and 0.00403 /K
  • k_s — 1.02 for stranded wire (ASTM B8), 1 for solid

The result is the smallest AWG size and the smallest IEC 60228 metric size with at least A_min.

Power systems and machines

Battery capacity and runtime

Load current (DC, or AC through an inverter of efficiency η_inv):

I = P / (η_inv V)

Peukert's law (capacity C rated over H hours, exponent k):

t_empty = H (C_derated / (I H))^k,     C_derated = C × derating
effective capacity = I t_empty
runtime = DoD × t_empty
Ah removed = I × runtime

Required rated capacity for a target runtime t_target:

C = I H (t_target / (DoD H))^(1/k) / derating

Energy and recharge:

E_nominal = V C,    E_usable = V × Ah removed
Ah to recharge = Ah removed / η_charge,    t_recharge (bulk) = Ah to recharge / I_charger
C-rate = I / C

Typical presets: flooded lead-acid k 1.25, DoD 50 %, charge efficiency 85 %; AGM k 1.12; gel k 1.15; LiFePO4 k 1.03, DoD 80 %, 97 %; NiCd k 1.10, DoD 80 %, 80 %.

Generator load sharing with droop

Droop line:          f = f_nl − D f_r P / P_r
Load on a set:       P = P_r (f_nl − f) / (D f_r)
Bus frequency:       f = (Σ c_i f_nl,i − P_load) / Σ c_i,   c_i = P_r,i / (D_i f_r)
Proportional share:  P_load × P_r,i / Σ P_r
  • f_nl — no-load frequency setting; D — droop as a fraction; f_r — rated frequency; P_r — rating.

Generator load, kVA and fuel

Ratings and load:

P_set = S_rated × pf_rated                 rated kW of one set
P_installed = n × P_set
S_load = P_load / pf_load,    I = S_load / (√3 V)
load % (kW)  = P_load / P_installed,    load % (kVA) = S_load / (n S_rated)

Redundancy and set count:

N−1 load % = P_load / ((n − 1) P_set)
n_recommended = ceil( P_load / (band_max × P_set) )

Fuel, cost and emissions:

SFOC(load) = SFOC₁₀₀ × f(load)      f: 1.00 at 100 %, 1.02 at 75 %, 1.10 at 50 %, 1.27 at 25 %, linear between
fuel/h = P_load × SFOC(load)
fuel over the period = fuel/h × hours,    cost = fuel × price,    CO₂ = fuel × C_F
  • S_rated — kVA rating of each set; pf_rated — alternator rated power factor (0.8); C_F — IMO carbon factor of the fuel

Generator size calculator

Running load and starting surge:

W_run = Σ W_running
surge = max(W_starting − W_running)       motors starting one at a time
surge = Σ (W_starting − W_running)        all starting together
W_peak = W_run + surge

Minimum ratings:

running rating ≥ W_run / k_max
starting rating ≥ W_peak
standby kVA = running rating / 0.8
  • W_running, W_starting — running and starting watts of each load, from the nameplate or manual
  • k_max — the highest share of its rating you want the generator to run at, 80 % by default
  • 0.8 — the power factor at which standby generators are rated (ISO 8528-1)

Lighting design (lumen method)

K = L W / (h_m (L + W))                      room index (h_m above the working plane)
N = E A / (Φ UF MF)                          luminaires for the maintained illuminance E
E_achieved = N Φ UF MF / A,   E_initial = E_achieved / MF
SHR = max(spacing) / h_m  ≤ SHR_max          uniformity criterion
power density = N P / A,   energy = N P × hours

Typical UF (direct luminaire, ceiling/walls/floor 70/50/20): K 1.0 → 0.45, 1.5 → 0.54, 2.0 → 0.59, 3.0 → 0.65, 5.0 → 0.70 (darker surfaces 10–15 % less). MF 0.8 clean, 0.67 dirty, 0.9 sealed LED in clean rooms. EN 12464-1: offices 500 lx, drawing 750, corridors 100, rough workshop 300, fine bench work 500; engine rooms 200 lx.

Motor starting current and voltage dip

I_n = P / (√3 V η cos φ),   S_start = √3 V I_n × m
m: DOL = LRC,  star-delta = LRC/3,  autotransformer = LRC a²,  soft starter = current limit,  drive ≈ 1.0–1.5
generator:  dip = X s / (1 + X s),   s = S_start / S_gen,   X = X'd (conservative) or X''d
network:    dip = S_start / (S_sc + S_start)
T_start / T_n = LRT × (1, 1/3, a², (limit/LRC)²) × (1 − dip)²      (drive: ≈ current multiple)

Dip limits: ISO 8528-5 G1 −25 %, G2 −20 %, G3 −15 % (standard load steps); IACS UR E5 a.c. transient ±20 % with recovery in 1.5 s.

Power factor correction

Q_c = P (tan φ₁ − tan φ₂)                        tan φ = √(1 − cos²φ)/cos φ
C = Q_c / (3 ω V²)   (delta),   C = Q_c / (ω V²)   (star),   ω = 2π f
S = P / cos φ,   I = S / (√3 V),   released = S₁ − S₂
loss reduction = 1 − (cos φ₁ / cos φ₂)²
h_r = √(S_sc / Q_c),   f_r = h_r f                parallel resonance with the supply
detuned: h_t = 1/√p,   capacitor voltage V/(1 − p)

Short-circuit current (IEC 60909)

I_k″ = c U_n / (√3 Z_k),   Z_k = √(R_k² + X_k²)
network:     Z_Qt = 1.10 U_n² / S_kQ″,  X_Q = 0.995 Z_Qt,  R_Q = 0.1 X_Q
transformer: Z_T = u_kr U_n²/S_rT,  R_T = P_krT U_n²/S_rT²,  X_T = √(Z_T² − R_T²),  K_T = 0.95 c_max/(1 + 0.6 x_T)
cable:       R_C = R′ L / n,  X_C = X′ L / n;  for the minimum current R_C,θ = R_C [1 + 0.004 (θ_e − 20)]
κ = 1.02 + 0.98 e^(−3 R_k/X_k),   i_p = κ √2 I_k″
m = (e^(4 f T_k ln(κ−1)) − 1)/(2 f T_k ln(κ−1)),   I_th = I_k″ √(m + 1)
I_k,min″ = c_min U_n / (√3 Z_k,θ)

Voltage factors (Table 1): LV systems +6 % c_max 1.05 / c_min 0.95; LV +10 % 1.10 / 0.95; MV and HV 1.10 / 1.00.

Solar PV array and storage sizing

P_array = E_day / (PSH × η_sys) × (1 + margin)
modules = strings × N_series,   strings = ceil(P_array / (N_series P_module))
E_yield = P_installed × PSH × η_sys
V_oc,cold = N_series V_oc (1 + 0.003 (25 − T_min))  ≤ V_controller,max
I_controller = P_installed / V_bat × 1.25   (MPPT)   or   strings × I_sc × 1.25   (PWM)
C_bank = E_day × days / (DoD × η_inverter),   Ah = C_bank / V_bat,   usable = C_bank × DoD
I_charge,avg = E_yield / PSH / V_bat,   recharge days = usable / (E_yield − E_day)
P_inverter = P_peak × 1.25,   I_DC = P_peak / (η_inv V_bat)

Typical values: η_sys 0.70–0.80; DoD 50 % lead-acid, 80 % LiFePO4; autonomy 2–3 days (5+ for critical loads); PSH from the site's irradiation data for the array tilt.

Three-phase power and motor current

Power triangle (V line-to-line for three-phase, I line current):

Three-phase:  S = √3 V I,    Single-phase:  S = V I,    DC:  P = V I
P = S cos φ,   Q = S sin φ = √(S² − P²),   φ = acos(pf)

Current from power:

I = P / (√3 V cos φ)   (three-phase),   I = P / (V cos φ)   (single-phase),   I = P / V   (DC)

Motor from nameplate:

P_in = P_shaft / η,   I_FL = P_in / (√3 V cos φ),   losses = P_in − P_shaft
I_start = k × I_FL,   S_start = √3 V I_start

Power-factor correction:

Q_c = P (tan φ₁ − tan φ₂),   I_after = P / (√3 V cos φ₂)

Generator apparent power drawn = S.

  • η — motor efficiency at rated load; k — starting current multiple (DOL 6–8, star-delta ≈ 1/3 of that, soft starter 2–4, VFD 1–1.5)

Transformer size calculator (kVA)

S = P / cos φ,   S_req = S (1 + g) / k_load   → next standard rating S_r (IEC R10: 25 … 5 000 kVA; ANSI: 15 … 10 000 kVA)
I_HV = S_r/(√3 U_HV),   I_LV = S_r/(√3 U_LV),   x = S/S_r
u_r = P_k / S_r,   u_x = √(u_k² − u_r²)
ε = x (u_r cos φ + u_x sin φ) + x² (u_x cos φ − u_r sin φ)² / 2    (per unit; sin φ > 0 lagging)
U_LV,load = U_LV (1 − ε)
P_loss = P_0 + x² P_k,   η = P/(P + P_loss),   x_η,max = √(P_0/P_k)
I_sc ≈ I_LV / u_k

Results are estimates. They do not replace the governing code, class or flag requirements, or a check by a competent person.