Electrical engineering glossary
38 terms from the electrical calculators, each in two or three sentences with its symbol, its unit and a typical value. Every entry links to the calculators that use it; the formula sheet has the equations.
-
Active powerPW (kW)
Also called real power, true power
The rate at which an AC circuit delivers energy that does useful work, the real part of the complex power. In a three-phase system it equals √3 × line voltage × line current × power factor. Motors, heaters and loads on a bill are rated in it, in watts or kilowatts.
kVA to kW, kW to kVA, Three-phase power and motor current, Amps to kW, Watts to amps
-
American Wire Gaugenone
Also called AWG, wire gauge
The North American system of wire sizes in which a larger gauge number means a thinner conductor. Diameter changes by a factor of about 1.123 per step, so every 3 gauges doubles or halves the cross-section; 12 AWG is 3.31 mm². Sizes above 4/0 are given in kcmil.
AWG wire gauge chart and converter, Wire size calculator (AWG and mm²), Cable sizing and voltage drop, Conduit fill calculator (NEC)
-
AmpacityIzA
Also called current-carrying capacity, Iz
The maximum current a conductor can carry continuously without its insulation exceeding its rated temperature, under stated installation conditions. A 2.5 mm² copper PVC cable clipped direct carries about 27 A under IEC 60364-5-52; grouping, hot surroundings and thermal insulation reduce it. The protective device must not be rated above it.
Cable sizing and voltage drop, Wire size calculator (AWG and mm²), AWG wire gauge chart and converter, Breaker size calculator, Conduit fill calculator (NEC)
-
Apparent powerSVA (kVA)
Also called kVA
The product of RMS voltage and RMS current in an AC circuit, regardless of phase angle, and the vector sum of active and reactive power. For a three-phase load it is √3 × line voltage × line current. Transformers, generators and UPS units are rated in kVA because their heating depends on current, not on power factor.
kVA to amps, kVA to kW, kW to kVA, Transformer size calculator (kVA), Generator load, kVA and fuel
-
Breaking capacityIcukA
Also called interrupting rating, AIC, Icu, Ics
The highest prospective fault current a circuit breaker or fuse can interrupt at its rated voltage without failing. Miniature circuit breakers are commonly rated 6 kA or 10 kA, and moulded-case breakers from about 25 kA to over 100 kA. It must equal or exceed the prospective short-circuit current where the device is installed.
Short-circuit current (IEC 60909), Breaker size calculator, Cable short-circuit withstand
-
CapacitanceCF (µF, nF, pF)
The charge a component stores per volt across it, C = Q / V, measured in farads. Capacitors in parallel add directly, while in series their reciprocals add, the opposite of resistors. Practical values run from picofarads in radio circuits to thousands of microfarads in power supply smoothing.
Series and parallel capacitors, RC time constant and filter, LC resonant frequency calculator, Filter cutoff frequency calculator (RC, RL, LC), 555 timer calculator, Power factor correction
-
Conduit fill%
Also called conduit fill ratio
The share of a conduit’s internal cross-sectional area taken up by the cables inside it, insulation included. NEC Chapter 9 Table 1 allows 53 % for one cable, 31 % for two and 40 % for three or more. Overfilling makes pulling hard, damages insulation and traps heat.
Conduit fill calculator (NEC), Cable sizing and voltage drop
-
Cutoff frequencyfcHz
Also called corner frequency, -3 dB frequency, break frequency
The frequency at which a filter’s output falls to 1/√2 of its passband level, a drop of 3 dB or half the power. For a first-order RC filter it is 1 / (2πRC) and for an RL filter R / (2πL). Beyond it a first-order filter rolls off at 20 dB per decade.
Filter cutoff frequency calculator (RC, RL, LC), RC time constant and filter
-
DecibeldB
Also called dB, dBm, dBV, dBu
A logarithmic unit for a ratio: 10 log₁₀ of a power ratio, or 20 log₁₀ of a voltage or current ratio. Doubling power adds 3 dB and doubling voltage adds 6 dB. A suffix fixes the reference: dBm is relative to 1 mW, dBV to 1 V and dBu to 0.775 V.
Decibel calculator (dB, dBm, dBV, dBu), Filter cutoff frequency calculator (RC, RL, LC)
-
Derating factordimensionless
Also called correction factor, rating factor
A multiplier below 1 applied to a rated capacity when conditions are harsher than the rating assumes, such as high ambient temperature, grouping or altitude. Six loaded circuits bunched together reduce cable ampacity by a factor of about 0.57. Several factors multiply, and the product is applied to the tabulated rating.
Cable sizing and voltage drop, Conduit fill calculator (NEC), Generator size calculator, Transformer size calculator (kVA), Battery capacity and runtime
-
Direct-on-line startingnone
Also called DOL, across-the-line starting
Starting an induction motor by switching it straight onto full supply voltage. It draws the full locked-rotor current, typically 6 to 8 times rated current, and gives full starting torque. It is the simplest and cheapest method but causes the largest voltage dip and mechanical shock.
Motor starting current and voltage dip, Generator size calculator, Three-phase power and motor current
-
Droop%
Also called speed droop, governor droop
The fall in a generator’s speed, and so its frequency, from no load to full load, expressed as a percentage of rated speed. Governors are commonly set to 3 % to 5 %. Sets running in parallel with equal droop share load in proportion to their ratings.
Generator load sharing with droop, Generator load, kVA and fuel
-
Duty cycleD%
The fraction of each period during which a pulsed signal or a device is on. A basic 555 astable always runs above 50 % unless a diode bypasses the discharge resistor, and fuel injectors are usually kept below 80 % to 85 %. Average power or flow is the full value times the duty cycle.
555 timer calculator, Fuel injector size calculator, Electricity cost and energy use
-
Earth fault loop impedanceZsΩ
Also called Zs, loop impedance
The total impedance of the path a fault current takes from the source, out through the line conductor to the fault and back through the protective conductor. It fixes the earth-fault current, U0 ÷ Zs, which must trip the protective device in time: 0.4 s for 230 V final circuits up to 32 A in TN systems.
Cable short-circuit withstand, Short-circuit current (IEC 60909)
-
Forward voltageVFV
Also called Vf, LED voltage drop
The voltage across a diode or LED when it conducts its rated forward current. Typical values are 0.6 to 0.7 V for a silicon diode, about 2 V for red LEDs and about 3 V for white and blue. The LED series resistor is supply voltage minus forward voltage, divided by the current.
-
IlluminanceElx (fc)
Also called lux, light level, foot-candles
The luminous flux falling on a surface per unit area, measured in lux, one lumen per square metre. EN 12464-1 asks for 500 lx at office desks and 100 lx in corridors. The lumen method multiplies target illuminance by floor area and divides by the utilisation and maintenance factors to find the lumens needed.
-
ImpedanceZΩ
Also called reactance, AC resistance
The total opposition a circuit presents to alternating current, combining resistance and reactance as a complex quantity, Z = R + jX. Its magnitude is √(R² + X²), and Ohm’s law in AC form is V = I × Z. Inductive reactance is 2πfL and capacitive reactance 1 / (2πfC).
Ohm's law and electrical power, Short-circuit current (IEC 60909), Filter cutoff frequency calculator (RC, RL, LC), Cable short-circuit withstand, Motor starting current and voltage dip, LC resonant frequency calculator
-
Impedance voltageuk%
Also called percent impedance, %Z, short-circuit voltage, uk
The voltage, as a percentage of rated voltage, that drives rated current through a transformer with its secondary short-circuited. Distribution transformers usually have 4 % to 6 %. Rated current divided by it gives the transformer-limited fault current, so 5 % means about 20 times rated current.
Short-circuit current (IEC 60909), Transformer size calculator (kVA)
-
InductanceLH (mH, µH)
The property of a coil or conductor that opposes changes in current by inducing a back voltage, V = L × dI/dt, measured in henries. An air-core coil’s inductance grows with the square of its number of turns. Inductors in series add like resistors, and their reactance rises with frequency as 2πfL.
Air-core coil inductance calculator, LC resonant frequency calculator, Filter cutoff frequency calculator (RC, RL, LC)
-
Let-through energyI²tA²s
Also called I2t, adiabatic equation, k factor
The integral of the square of current over the time a protective device takes to clear a fault. A cable survives the fault if k²S² is at least I²t, the adiabatic equation of IEC 60364-4-43, with k = 115 for copper PVC and 143 for copper XLPE insulation.
Cable short-circuit withstand, Short-circuit current (IEC 60909), Breaker size calculator
-
Line voltageULV
Also called line-to-line voltage, phase-to-phase voltage
The voltage between two line conductors of a three-phase system, √3 times the line-to-neutral voltage in a balanced star system. A 400 V line voltage gives 230 V to neutral and 480 V gives 277 V. Three-phase power formulas use it with the √3 factor: P = √3 × U_L × I × cos φ.
Three-phase power and motor current, kW to amps, kVA to amps, Amps to kW, Cable sizing and voltage drop
-
Locked-rotor currentILRA
Also called LRA, starting current, inrush current
The current an induction motor draws at standstill with full voltage applied, the first instant of a direct-on-line start. It is typically 6 to 8 times rated current, and can exceed 8 for high-efficiency IE3 and IE4 motors, at a power factor of only 0.2 to 0.4. It sizes starters, generators and the voltage dip.
Motor starting current and voltage dip, Generator size calculator, Three-phase power and motor current, Breaker size calculator
-
Ohm’s lawnone
Also called V = IR
The relation between voltage, current and resistance in a conductor at constant temperature: V = I × R. Combined with P = V × I it gives power as I²R or V²/R. A 12 V supply across 6 Ω drives 2 A and dissipates 24 W.
Ohm's law and electrical power, LED series resistor, Voltage divider, Watts to amps, Amps to watts
-
Power factorcos φdimensionless
Also called PF, cos phi
The ratio of active power to apparent power in an AC circuit, equal to cos φ for sinusoidal waveforms. Induction motors run at 0.80 to 0.90 at full load and much lower at light load, and utilities often charge for averages below 0.90 to 0.95. A low value raises current, losses and cable size for the same useful power.
Power factor correction, kW to kVA, kVA to kW, Three-phase power and motor current, Amps to kW, kW to amps
-
Power factor correctionkvar
Also called PFC, capacitor bank, reactive power compensation
Adding capacitors, or an active compensator, to supply locally the reactive power that inductive loads need, so the network carries less current. The capacitor rating is P × (tan φ1 − tan φ2); raising 100 kW from 0.80 to 0.95 needs about 42 kvar. Overcorrection gives a leading power factor and risks resonance with harmonics.
Power factor correction, Three-phase power and motor current, Series and parallel capacitors
-
Prime power ratingkW (kVA)
Also called PRP, standby rating, ESP, generator rating
The power a generating set can supply for an unlimited number of hours a year at variable load, as defined in ISO 8528-1, with the average over 24 hours not above 70 % of the rating. The standby rating is usually about 10 % higher but limited to emergency use, typically up to 200 hours a year.
-
Prospective short-circuit currentIk″kA
Also called PSCC, fault current, fault level, initial symmetrical short-circuit current
The current that would flow at a point if the supply were shorted there through negligible impedance, before any protective device acts. IEC 60909 calculates the initial symmetrical value as c × U_n ÷ (√3 × Z_k). Behind a 1000 kVA, 6 % transformer at 400 V it is roughly 25 kA.
Short-circuit current (IEC 60909), Cable short-circuit withstand, Breaker size calculator, Transformer size calculator (kVA)
-
RC time constantτs
Also called time constant, tau
The product of resistance and capacitance, the time a capacitor takes to charge through the resistor to 63.2 % of the applied voltage. After five time constants it is above 99 % and treated as fully charged. 10 kΩ with 100 µF gives τ = 1 s.
RC time constant and filter, Filter cutoff frequency calculator (RC, RL, LC), 555 timer calculator, Series and parallel capacitors
-
Reactive powerQvar (kvar)
Also called kvar, VAR
The power that oscillates between the source and the magnetic or electric fields of inductive and capacitive loads, doing no net work. It equals √(S² − P²), or P × tan φ, so a motor at power factor 0.8 draws 0.75 kvar per kW. It still loads cables and transformers, which is why it is corrected.
Power factor correction, Three-phase power and motor current, kVA to kW, kW to kVA
-
ResistivityρΩ·m (Ω·mm²/m)
Also called specific resistance, electrical resistivity
The resistance of a material per unit length for unit cross-section, an intrinsic property, so R = ρL / A. At 20 °C copper is 0.0172 Ω·mm²/m and aluminium 0.0282 Ω·mm²/m, and both rise about 0.4 % per kelvin. It sets conductor resistance, voltage drop and heating.
Cable sizing and voltage drop, Wire size calculator (AWG and mm²), AWG wire gauge chart and converter, PCB trace width calculator (IPC-2221), Cable short-circuit withstand
-
Resistor colour codenone
Also called resistor color code, colour bands, E24 series
The IEC 60062 scheme of coloured bands that marks a resistor’s value, multiplier and tolerance. Black to white stand for the digits 0 to 9, so a four-band resistor marked yellow, violet, red, gold reads 4, 7, × 100, ±5 %, or 4.7 kΩ. Values come from preferred-number series such as E12 and E24.
-
Resonant frequencyf0Hz
Also called LC resonance, tank circuit frequency
The frequency at which inductive and capacitive reactance in an LC circuit are equal, f_0 = 1 / (2π√(LC)). A series LC circuit has minimum impedance there and a parallel one maximum. 10 µH with 100 pF resonates near 5.03 MHz.
LC resonant frequency calculator, Filter cutoff frequency calculator (RC, RL, LC), Air-core coil inductance calculator
-
Star-delta startingnone
Also called wye-delta starting, Y-Δ starter
A reduced-voltage start in which an induction motor runs up connected in star and then switches to delta for normal running. Each winding sees 1/√3 of line voltage, so line current and starting torque both fall to one third of their direct-on-line values. The motor must be delta-rated for the line voltage, with six terminals.
Motor starting current and voltage dip, Three-phase power and motor current
-
Subtransient reactanceX″dper unit (%)
Also called Xd″, transient reactance, generator reactance
A synchronous generator’s reactance in the first few cycles after a fault or sudden load, while damper winding currents still flow. Diesel generating sets typically have 0.10 to 0.20 per unit on their own rating, and the transient reactance X′_d, governing the following cycles, 0.15 to 0.30. Both set fault current and the voltage dip on motor starting.
Motor starting current and voltage dip, Short-circuit current (IEC 60909), Generator size calculator
-
Voltage dip%
Also called voltage sag, voltage dip on motor starting
A short fall in supply voltage when a large load, usually a motor, starts or a fault occurs nearby, expressed as a percentage of nominal voltage. Generator-supplied systems are commonly designed for no more than 15 % to 20 % on motor starting. It is estimated by comparing starting kVA with the short-circuit power of the source.
Motor starting current and voltage dip, Generator size calculator, Transformer size calculator (kVA)
-
Voltage dividernone
Also called potential divider
Two resistors in series across a supply, with the output taken from their junction, giving V_out = V_in × R2 ÷ (R1 + R2). It scales voltages for ADC inputs and sets bias points. Any load on the output acts in parallel with R2 and lowers the voltage, so it should draw far less current than the divider.
Voltage divider, Series and parallel resistors, Ohm's law and electrical power
-
Voltage dropΔUV (%)
Also called cable voltage drop, line loss
The fall in voltage along a cable caused by its resistance and reactance carrying load current. IEC 60364-5-52 suggests 3 % for lighting and 5 % for other uses; NEC informational notes suggest 3 % on a branch and 5 % in total. For a single-phase run it is about 2 × length × current × resistance per metre.
Cable sizing and voltage drop, Wire size calculator (AWG and mm²), Motor starting current and voltage dip, AWG wire gauge chart and converter, PCB trace width calculator (IPC-2221)
-
Voltage factorcdimensionless
Also called c factor, c_max, c_min
A multiplier applied to nominal voltage in IEC 60909 short-circuit calculations to allow for supply variation and machine behaviour. In low-voltage systems with +10 % tolerance c_max is 1.10 and c_min 0.95; with +6 % tolerance c_max is 1.05. Use c_max for breaking capacity and c_min for the minimum fault current that must trip protection.
Short-circuit current (IEC 60909), Cable short-circuit withstand